Felicity IVEM8048-II Error Codes: Causes & Fixes (56 codes)

This is the complete fault table for the Felicity IVEM8048-II Inverter family — 56 codes shared by 3 model numbers, transcribed from the official manual. On Felicity units, a fault code means the unit has cut its output and the red LED stays solid; a warning flashes the red LED while the unit keeps running.

Also coversIVEM12048-IIIVEM 8K-12K Series II

Last checked against the official manuals on July 10, 2026.

How to read the severity labels

  • Fault(42)output stops · red LED solid
  • Warning(14)unit keeps running · red LED flashing

Fault codes (42)output stops · red LED solid

F01Fault

Bus voltage is too high.

Fault

Fault: Bus voltage is too high. Inverter cuts off output, fault LED solid on, ERROR icon shown on LCD.

CauseAC Surge or internal components failed.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:IVEM8K-12K-II_compressed.pdf· page 42

F02Fault

Bus voltage is too low.

Fault

Fault: Bus voltage is too low.

CauseInternal bus voltage abnormally low.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:IVEM8K-12K-II_compressed.pdf· page 43

F03Fault

Bus soft start fail.

Fault

Fault: Bus soft start fail.

CauseInternal components failed.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:IVEM8K-12K-II_compressed.pdf· page 43

F04Fault

Inverter soft start fail.

Fault

Fault: Inverter soft start fail.

CauseInternal components failed.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:IVEM8K-12K-II_compressed.pdf· page 43

F05Fault

Over current or surge detected by Software.

Fault

Fault: Over current or surge detected by Software.

CauseSoftware-detected over current or surge condition.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:IVEM8K-12K-II_compressed.pdf· page 43

F06Fault

Over current or surge detected by hardware.

Fault

Fault: Over current or surge detected by hardware.

CauseHardware-detected over current or surge condition.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:IVEM8K-12K-II_compressed.pdf· page 43

F07Fault

Output voltage is too low.

Fault

Fault: Output voltage is too low.

CauseOutput voltage below acceptable range, possibly due to overload.

Recommended fixReduce the connected load. Restart the unit, if the error persists, contact the repair center.

Source:IVEM8K-12K-II_compressed.pdf· page 43

F08Fault

Output voltage is too high.

Fault

Fault: Output voltage is too high.

CauseOutput voltage exceeds acceptable range.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:IVEM8K-12K-II_compressed.pdf· page 43

F09Fault

Output short circuited.

Fault

Fault: Output short circuited.

CauseShort circuit on AC output wiring or connected load.

Recommended fixCheck if wiring is connected well and remove abnormal load.

Source:IVEM8K-12K-II_compressed.pdf· page 43

F10Fault

Overload time out.

Fault

Fault: Overload time out.

CauseConnected load has exceeded the inverter's overload capacity for too long.

Recommended fixReduce the connected load by switching off some equipment.

Source:IVEM8K-12K-II_compressed.pdf· page 43

F11Fault

Battery voltage is too high.

Fault

Fault: Battery voltage is too high.

CauseBattery voltage exceeds the inverter's allowed maximum.

Recommended fixCheck if spec and quantity of batteries are meet requirements.

Source:IVEM8K-12K-II_compressed.pdf· page 43

F12Fault

Over current happen at DC/DC circuit.

Fault

Fault: Over current happen at DC/DC circuit.

CauseOver current detected in the DC/DC converter circuit.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:IVEM8K-12K-II_compressed.pdf· page 43

F13Fault

PV voltage is too high.

Fault

Fault: PV voltage is too high.

CausePV array open-circuit voltage exceeds the inverter's maximum input voltage.

Recommended fixReduce the number of PV modules in series.

Source:IVEM8K-12K-II_compressed.pdf· page 43

F14Fault

Short circuited happen at PV port.

Fault

Fault: Short circuited happen at PV port.

CauseShort circuit detected at the PV input port or wiring.

Recommended fixCheck if wiring is connected well.

Source:IVEM8K-12K-II_compressed.pdf· page 43

F15Fault

PV power is abnormal.

Fault

Fault: PV power is abnormal.

CausePV input power exceeds the inverter's allowed maximum.

Recommended fixReduce the number of PV modules.

Source:IVEM8K-12K-II_compressed.pdf· page 43

F16Fault

Over current happen at PV port.

Fault

Fault: Over current happen at PV port.

CauseOver current detected at the PV input port.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:IVEM8K-12K-II_compressed.pdf· page 43

F17Fault

Fan is locked.

Fault

Fault: Fan is locked.

CauseFan wiring not connected well or fan failure.

Recommended fixCheck if wiring is connected well. Replace the fan.

Source:IVEM8K-12K-II_compressed.pdf· page 43

F18Fault

Over temperature happen at PV circuit.

Fault

Fault: Over temperature happen at PV circuit.

CauseThe temperature of internal PV component is over the limitation.

Recommended fixCheck whether the air flow of the unit is blocked or whether the ambient temperature is too high.

Source:IVEM8K-12K-II_compressed.pdf· page 43

F19Fault

Over temperature happen at Convert L circuit.

Fault

Fault: Over temperature happen at Convert L circuit.

CauseThe temperature of Convert L battery converter component is over the limitation.

Recommended fixCheck whether the air flow of the unit is blocked or whether the ambient temperature is too high.

Source:IVEM8K-12K-II_compressed.pdf· page 43

F20Fault

Over temperature happen at INV circuit.

Fault

Fault: Over temperature happen at INV circuit.

CauseThe temperature of internal INV component is over the limitation.

Recommended fixCheck whether the air flow of the unit is blocked or whether the ambient temperature is too high.

Source:IVEM8K-12K-II_compressed.pdf· page 43

F21Fault

The inner temperature over.

Fault

Fault: The inner temperature over.

CauseThe inner temperature is over the limitation.

Recommended fixCheck whether the air flow of the unit is blocked or whether the ambient temperature is too high.

Source:IVEM8K-12K-II_compressed.pdf· page 44

F22Fault

DCDC current sensor failed.

Fault

Fault: DCDC current sensor failed.

CauseDCDC current sensor failure.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:IVEM8K-12K-II_compressed.pdf· page 44

F23Fault

No.2 DCDC current sensor failed.

Fault

Fault: No.2 DCDC current sensor failed.

CauseSecond DCDC current sensor failure.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:IVEM8K-12K-II_compressed.pdf· page 44

F24Fault

Inverter current sensor failed.

Fault

Fault: Inverter current sensor failed.

CauseInverter current sensor failure.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:IVEM8K-12K-II_compressed.pdf· page 44

F25Fault

OP current sensor failed.

Fault

Fault: OP current sensor failed.

CauseOutput current sensor failure.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:IVEM8K-12K-II_compressed.pdf· page 44

F26Fault

Sharing current sensor failed.

Fault

Fault: Sharing current sensor failed.

CauseCurrent-sharing sensor failure (parallel system).

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:IVEM8K-12K-II_compressed.pdf· page 44

F27Fault

The AC input and output wires are inversely connected.

Fault

Fault: The AC input and output wires are inversely connected.

CauseAC input and output wires connected reversely.

Recommended fix1. Please check AC input and output wires are connected correctly. 2. if this error happens during parallel installation, please check wires connection. if they are connected correctly, please funish parallel installation first, and then restart inverters. 3. if the problem remains, please contact your installer.

Source:IVEM8K-12K-II_compressed.pdf· page 44

F28Fault

Single unit is installed to parallel system.

Fault

Fault: Single unit is installed to parallel system.

CauseA single unit is detected as installed in a parallel system.

Recommended fix1. Please check if single unit is installed to parallel system. 2. if this error happens during parallel installation, please check wires connectiotn. if they are connected correctly, please funish parallel installation first, and then restart inverters. 3. if the problem remains, please contact your installer.

Source:IVEM8K-12K-II_compressed.pdf· page 44

F29Fault

DC/DC soft start fail.

Fault

Fault: DC/DC soft start fail.

CauseDC/DC converter soft start failure.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:IVEM8K-12K-II_compressed.pdf· page 44

F31Fault

Over temperature happen at convert H circuit.

Fault

Fault: Over temperature happen at convert H circuit.

CauseThe temperature of internal convert H component is over the limitation.

Recommended fixCheck whether the air flow of the unit is blocked or whether the ambient temperature is too high.

Source:IVEM8K-12K-II_compressed.pdf· page 44

F32Fault

Over temperature happen at LLC TX.

Fault

Fault: Over temperature happen at LLC TX.

CauseThe temperature of internal DC/DC TX is over the limitation.

Recommended fixCheck whether the air flow of the unit is blocked or whether the ambient temperature is too high.

Source:IVEM8K-12K-II_compressed.pdf· page 44

F33Fault

Over current happen at LLC circuit.

Fault

Fault: Over current happen at LLC circuit.

CauseOver current detected in the LLC circuit.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:IVEM8K-12K-II_compressed.pdf· page 44

F34Fault

DC/DC hardware overflows.

Fault

Fault: DC/DC hardware overflows.

CauseDC/DC converter hardware overflow.

Recommended fixRestart the unit, if the eror happens again, contact the repair center.

Source:IVEM8K-12K-II_compressed.pdf· page 44

F35Fault

Overvoltage occurs in BUS.

Fault

Fault: Overvoltage occurs in BUS.

CauseAC surge or PV surge or internal components failed.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:IVEM8K-12K-II_compressed.pdf· page 44

F40Fault

CAN data loss.

Fault

Fault: CAN data loss.

CauseCAN communication data loss between parallel inverters.

Recommended fix1. Check if communication cables are connected well and restart the inverter. 2. if the problem remains, please contact your installer.

Source:IVEM8K-12K-II_compressed.pdf· page 44

F41Fault

Host data loss.

Fault

Fault: Host data loss.

CauseHost data loss in parallel communication.

Recommended fix1. Check if communication cables are connected well and restart the inverter. 2. if the problem remains, please contact your installer.

Source:IVEM8K-12K-II_compressed.pdf· page 44

F42Fault

Synchronization data loss.

Fault

Fault: Synchronization data loss.

CauseSynchronization data loss in parallel communication.

Recommended fix1. Check if communication cables are connected well and restart the inverter. 2. if the problem remains, please contact your installer.

Source:IVEM8K-12K-II_compressed.pdf· page 44

F43Fault

Current feedback into the inverter is detected.

Fault

Fault: Current feedback into the inverter is detected.

CauseReverse current feedback detected at the inverter.

Recommended fix1. Restart the inverter. 2. Check if L/N cables are not connected reversely in all inverters. 3. For parallel system in single phase, make sure the sharing cables are connected in all inverters. For supporting three-phase system, make sure the sharing cables are connected in the inverters in the same phase, and disconnected in the inverters in different phases. 4. if the problem remains, please contact your installer.

Source:IVEM8K-12K-II_compressed.pdf· page 45

F44Fault

The firmware version of each inverter is not the same.

Fault

Fault: The firmware version of each inverter is not the same.

CauseFirmware versions on parallel inverters do not match.

Recommended fix1. Update all inverter firmware to the same version. 2. Check the version of each inverter via LCD setting and make sure the CPU versions are same. if not, please contact your installer to provide the firmware to update. 3. After updating, if the problem still remains, please contact your installer.

Source:IVEM8K-12K-II_compressed.pdf· page 45

F45Fault

The output current of each inverter is different.

Fault

Fault: The output current of each inverter is different.

CauseOutput current imbalance between parallel inverters.

Recommended fix1. Check if sharing cables are connected well and restart the inverter. 2. if the problem remains, please contact your installer.

Source:IVEM8K-12K-II_compressed.pdf· page 45

F46Fault

AC output mode setting is different.

Fault

Fault: AC output mode setting is different.

CauseAC output mode setting (LCD program 28) does not match across parallel units.

Recommended fix1. Switch off the inverter and check LCD setting program 28. 2. For parallel system in single phase, make sure no 3P1, 3P2 or 3P3 is set on program 28. For supporting three-phase system, make sure no 'PAL' is set on program 28. 3. if the problem remains, please contact your installer.

Source:IVEM8K-12K-II_compressed.pdf· page 45

F47Fault

Generator current sensor failed.

Fault

Fault: Generator current sensor failed.

CauseGenerator current sensor failure.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:IVEM8K-12K-II_compressed.pdf· page 45

Warning codes (14)unit keeps running · red LED flashing

W01Warning

Fan is locked.

Warning

Warning: Fan is locked. Beep three times every second.

CauseFan wiring not connected well or fan failure.

Recommended fixCheck if the Fans wiring connected well. Replace the fan.

Source:IVEM8K-12K-II_compressed.pdf· page 42

W02Warning

Overload.

Warning

Warning: Overload. Beep twice every second.

CauseConnected load exceeds the inverter capacity.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:IVEM8K-12K-II_compressed.pdf· page 42

W03Warning

Low battery.

Warning

Warning: Low battery. Beep once every second.

CauseBattery voltage is too low.

Recommended fixThe battery voltage is too low, it should be charging.

Source:IVEM8K-12K-II_compressed.pdf· page 42

W04Warning

Grid anomaly.

Warning

Warning: Grid anomaly. Grid icon blinking.

CauseGrid input is over voltage or over frequency.

Recommended fixCheck whether the input is overvoltage or overfrequency.

Source:IVEM8K-12K-II_compressed.pdf· page 42

W05Warning

Three-phase input missing phase.

Warning

Warning: Three-phase input missing phase. Fault LED flashing.

CauseThree-phase mains input is not normal (missing phase).

Recommended fixCheck whether the three-phase mains input is normal.

Source:IVEM8K-12K-II_compressed.pdf· page 42

W06Warning

The three-phase parallel is abnormal.

Warning

Warning: The three-phase parallel is abnormal. Fault LED flashing.

CauseThree-phase parallel communication is abnormal.

Recommended fixVerify that the three-phase communication is normal.

Source:IVEM8K-12K-II_compressed.pdf· page 42

W07Warning

Generator anomaly.

Warning

Warning: Generator anomaly. Generator icon blinking.

CauseGenerator input is over voltage or over frequency.

Recommended fixCheck whether the input is overvoltage or overfrequency.

Source:IVEM8K-12K-II_compressed.pdf· page 42

W08Warning

Three-phase parallel generator input phase deficiency.

Warning

Warning: Three-phase parallel generator input phase deficiency. Fault LED flashing.

CauseThree-phase mains input is not normal (missing phase) on generator input.

Recommended fixCheck whether the three-phase mains input is normal.

Source:IVEM8K-12K-II_compressed.pdf· page 42

W50Warning

BMS firmware version is not matched.

Warning

Warning: BMS firmware version is not matched.

CauseBMS firmware version mismatch.

Recommended fixUpgrade the firmware of BMS.

Source:IVEM8K-12K-II_compressed.pdf· page 42

W51Warning

BMS doesn't allow inverter to charge battery.

Warning

Warning: BMS doesn't allow inverter to charge battery. Inverter will stop charging battery automatically.

CauseBMS has prohibited charging the battery.

Recommended fixInverter will stop charging battery automatically.

Source:IVEM8K-12K-II_compressed.pdf· page 42

W52Warning

BMS doesn't allow inverter to discharge battery.

Warning

Warning: BMS doesn't allow inverter to discharge battery. Inverter will stop discharging battery automatically.

CauseBMS has prohibited discharging the battery.

Recommended fixInverter will stop discharging battery automatically.

Source:IVEM8K-12K-II_compressed.pdf· page 42

W53Warning

BMS require inverter to charge battery.

Warning

Warning: BMS require inverter to charge battery. Inverter will charge battery automatically.

CauseBMS is requesting the inverter to charge the battery.

Recommended fixInverter will charge battery automatically.

Source:IVEM8K-12K-II_compressed.pdf· page 42

W54-W65Warning

BMS detect something wrongs happened.

Warning

Warning: BMS detect something wrongs happened (range covers BMS internal alarm codes 54 through 65).

CauseBMS has detected an internal fault or abnormal condition.

Recommended fixIf the code is keeping for long time, please contact with your installer.

Source:IVEM8K-12K-II_compressed.pdf· page 42

W80Warning

The BMS communication is abnormal.

Warning

Warning: The BMS communication is abnormal. Beep once every second.

CauseBMS communication cable is not properly connected or communication failure.

Recommended fixCheck whether the BMS communication cable is connected.

Source:IVEM8K-12K-II_compressed.pdf· page 42

Still seeing a code on your IVEM8048-II?

Send us the code on your screen and a Felicity technician will reply with the exact steps for your unit. Support is free for life — a first diagnosis never needs a callout.

Keep troubleshooting

Related devices

Common questions about IVEM8048-II error codes

What is the difference between a fault and a warning on the IVEM8048-II?
A fault cuts the unit's output and the red LED stays solid — this page lists 42 of them for the IVEM8048-II. A warning only flashes the red LED and the unit keeps running; there are 14 warning codes here. Resolve the cause of a fault before restarting; warnings can usually be cleared while the unit runs.
Which model numbers does this page cover?
The IVEM8048-II shares its firmware and fault table with 2 other model numbers: IVEM12048-II, IVEM 8K-12K Series II. If your unit is any of these, every code on this page applies to it.
Where do these codes come from?
Every entry was transcribed from IVEM8K-12K-II_compressed.pdf — Felicity's official documentation. Each row cites its source manual (and page where printed), so you can verify the wording before acting on it.

Compiled from official Felicity user manuals. Always consult your device manual and a qualified technician before performing repairs.