What it means
AC input voltage and frequency are detected different — The inverters in the parallel system detect different AC input voltage or frequency.
Cause: The utility wiring differs between inverters, or the units do not receive utility power at the same time.
How to fix it
- Check the utility wiring connection and restart the inverter.
- Make sure the utility starts up at the same time; if there are breakers installed between the utility and the inverters, make sure all breakers can be turned on at the AC input at the same time.
- If the problem remains, contact your installer.