IVEM8048-LV

Inverter47 codes
also coversIVEM8048
39 Fault 8 Warning
F01Bus voltage is too high.Fault
Description

Bus voltage is too high.

Cause

AC Surge or internal components failed.

Recommended fix

Restart the unit, if the error persists, contact the repair center.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 37
F02Bus voltage is too low.Fault
Description

Bus voltage is too low.

Recommended fix

Restart the unit, if the error persists, contact the repair center.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 37
F03Bus soft start fail.Fault
Description

Bus soft start fail.

Cause

Internal components failed.

Recommended fix

Restart the unit, if the error persists, contact the repair center.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 37
F04Inverter soft start fail.Fault
Description

Inverter soft start fail.

Cause

Internal components failed.

Recommended fix

Restart the unit, if the error persists, contact the repair center.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 37
F05Over current or surge detected by Software.Fault
Description

Over current or surge detected by Software.

Recommended fix

Restart the unit, if the error persists, contact the repair center.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 37
F06Over current or surge detected by hardware.Fault
Description

Over current or surge detected by hardware.

Recommended fix

Restart the unit, if the error persists, contact the repair center.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 37
F07Output voltage is too low.Fault
Description

Output voltage is too low.

Recommended fix

Reduce the connected load. Restart the unit, if the error persists, contact the repair center.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 38
F08Output voltage is too high.Fault
Description

Output voltage is too high.

Recommended fix

Restart the unit, if the error persists, contact the repair center.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 38
F09Output short circuited.Fault
Description

Output short circuited.

Cause

Wiring not connected well or abnormal load.

Recommended fix

Check if wiring is connected well and remove abnormal load.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 38
F10Overload time out.Fault
Description

Overload time out.

Cause

Connected load exceeds inverter capacity for an extended time.

Recommended fix

Reduce the connected load by switching off some equipment.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 38
F11Battery voltage is too high.Fault
Description

Battery voltage is too high.

Cause

Battery spec or quantity does not meet requirements.

Recommended fix

Check if spec and quantity of batteries are meet requirements.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 38
F12Over current happen at DC/DC circuit.Fault
Description

Over current happen at DC/DC circuit.

Recommended fix

Restart the unit, if the error persists, contact the repair center.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 38
F13PV voltage is too high.Fault
Description

PV voltage is too high.

Cause

Too many PV modules in series.

Recommended fix

Reduce the number of PV modules in series.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 38
F14Short circuited happen at PV port.Fault
Description

Short circuited happen at PV port.

Cause

Wiring not connected well.

Recommended fix

Check if wiring is connected well.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 38
F15PV power is abnormal.Fault
Description

PV power is abnormal.

Cause

Excessive PV power input.

Recommended fix

Reduce the number of PV modules.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 38
F16Over current happen at PV port.Fault
Description

Over current happen at PV port.

Recommended fix

Restart the unit, if the error persists, contact the repair center.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 38
F17Fan is locked.Fault
Description

Fan is locked.

Cause

Fan wiring problem or fan failure.

Recommended fix

Check if wiring is connected well. Replace the fan.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 38
F18Over temperature happen at PV circuit.Fault
Description

Over temperature happen at PV circuit.

Cause

The temperature of internal PV component is over the limitation.

Recommended fix

Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 38
F19Over temperature happen at Convert L circuit.Fault
Description

Over temperature happen at Convert L circuit.

Cause

The temperature of Convert L battery converter component is over the limitation.

Recommended fix

Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 38
F20Over temperature happen at INV circuit.Fault
Description

Over temperature happen at INV circuit.

Cause

The temperature of internal INV component is over the limitation.

Recommended fix

Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 38
F21The inner temperature over.Fault
Description

The inner temperature over.

Cause

The inner temperature is over the limitation.

Recommended fix

Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 38
F22DCDC current sensor failed.Fault
Description

DCDC current sensor failed.

Recommended fix

Restart the unit, if the error persists, contact the repair center.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 38
F23No.2 DCDC current sensor failed.Fault
Description

No.2 DCDC current sensor failed.

Recommended fix

Restart the unit, if the error persists, contact the repair center.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 38
F24Inverter current sensor failed.Fault
Description

Inverter current sensor failed.

Recommended fix

Restart the unit, if the error persists, contact the repair center.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 38
F25OP current sensor failed.Fault
Description

OP current sensor failed.

Recommended fix

Restart the unit, if the error persists, contact the repair center.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 38
F26Sharing current sensor failed.Fault
Description

Sharing current sensor failed.

Recommended fix

Restart the unit, if the error persists, contact the repair center.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 38
F27The AC input and output wires are inversely connected.Fault
Description

The AC input and output wires are inversely connected.

Cause

AC input and output wiring reversed, possibly during parallel installation.

Recommended fix

1. Please check AC input and output wires are connected correctly. 2. if this error happens during parallel installation, please check wires connection. if they are connected correctly, please funish parallel installation first, and then restart inverters. 3. if the problem remains, please contact your installer.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 39
F28Single unit is installed to parallel system.Fault
Description

Single unit is installed to parallel system.

Cause

Single unit configured into a parallel system, or wiring problem during parallel installation.

Recommended fix

1. Please check if single unit is installed to parallel system. 2. if this error happens during parallel installation, please check wires connection. if they are connected correctly, please funish parallel installation first, and then restart inverters. 3. if the problem remains, please contact your installer.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 39
F29DC/DC soft start fail.Fault
Description

DC/DC soft start fail.

Recommended fix

Restart the unit, if the error persists, contact the repair center.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 39
F31Over temperature happen at convert H circuit.Fault
Description

Over temperature happen at convert H circuit.

Cause

The temperature of internal convert H component is over the limitation.

Recommended fix

Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 39
F32Over temperature happen at LLC TX.Fault
Description

Over temperature happen at LLC TX.

Cause

The temperature of internal DC/DC TX is over the limitation.

Recommended fix

Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 39
F33Over current happen at LLC circuit.Fault
Description

Over current happen at LLC circuit.

Recommended fix

Restart the unit, if the error persists, contact the repair center.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 39
F40CAN data loss.Fault
Description

CAN data loss.

Cause

Communication failure between paralleled inverters.

Recommended fix

1. Check if communication cables are connected well and restart the inverter. 2. if the problem remains, please contact your installer.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 39
F41Host data loss.Fault
Description

Host data loss.

Cause

Communication failure between paralleled inverters.

Recommended fix

1. Check if communication cables are connected well and restart the inverter. 2. if the problem remains, please contact your installer.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 39
F42Synchronization data loss.Fault
Description

Synchronization data loss.

Cause

Communication failure between paralleled inverters.

Recommended fix

1. Check if communication cables are connected well and restart the inverter. 2. if the problem remains, please contact your installer.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 39
F43Current feedback into the inverter is detected.Fault
Description

Current feedback into the inverter is detected.

Cause

Reverse-connected L/N cables, or sharing cables not connected/connected across phases in three-phase setup.

Recommended fix

1. Restart the inverter. 2. Check if L/N cables are not connected reversely in all inverters. 3. For parallel system in single phase, make sure the sharing cables are connected in all inverters. For supporting three-phase system, make sure the sharing cables are connected in the inverters in the same phase, and disconnected in the inverters in different phases. 4. if the problem remains, please contact your installer.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 39
F44The firmware version of each inverter is not the same.Fault
Description

The firmware version of each inverter is not the same.

Cause

Mismatched firmware versions across paralleled inverters.

Recommended fix

1. Update all inverter firmware to the same version. 2. Check the version of each inverter via LCD setting and make sure the CPU versions are same. if not, please contact your installer to provide the firmware to update. 3. After updating, if the problem still remains, please contact your installer.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 39
F45The output current of each inverter is different.Fault
Description

The output current of each inverter is different.

Cause

Sharing cable connection issue between paralleled inverters.

Recommended fix

1. Check if sharing cables are connected well and restart the inverter. 2. if the problem remains, please contact your installer.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 39
F46AC output mode setting is different.Fault
Description

AC output mode setting is different.

Cause

Inconsistent AC output mode (program 28) settings across inverters.

Recommended fix

1. Switch off the inverter and check LCD setting program 28. 2. For parallel system in single phase, make sure no 3P1, 3P2 or 3P3 is set on program 28. For supporting three-phase system, make sure no "PAL" is set on program 28. 3. if the problem remains, please contact your installer.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 39
W01Fan is locked.Warning
Description

Warning: Fan is locked. Beep three times every second.

Cause

Fan wiring not connected well or fan failure.

Recommended fix

Check if the Fan's wiring connected well. Replace the fan.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 37
W02Overload.Warning
Description

Warning: Overload. Beep twice every second.

Cause

Connected load exceeds the inverter capacity.

Recommended fix

Reduce the loads.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 37
W03Low battery.Warning
Description

Warning: Low battery. Beep once every second.

Cause

The battery voltage is too low.

Recommended fix

It should be charging.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 37
W50BMS firmware version is not matched.Warning
Description

BMS firmware version is not matched.

Cause

BMS firmware version mismatch.

Recommended fix

Upgrade the firmware of BMS.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 37
W51BMS doesn't allow inverter to charge battery.Warning
Description

BMS doesn't allow inverter to charge battery.

Cause

BMS has blocked charging.

Recommended fix

Inverter will stop charging battery automatically.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 37
W52BMS doesn't allow inverter to discharge battery.Warning
Description

BMS doesn't allow inverter to discharge battery.

Cause

BMS has blocked discharging.

Recommended fix

Inverter will stop discharging battery automatically.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 37
W53BMS require inverter to charge battery.Warning
Description

BMS require inverter to charge battery.

Cause

BMS has requested charging.

Recommended fix

Inverter will charge battery automatically.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 37
W54~65BMS detect something wrongs happened.Warning
Description

BMS detect something wrongs happened (range of codes 54 through 65).

Cause

BMS has detected an internal fault.

Recommended fix

If the code is keeping for long time, please contact with your installer.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 37