Also applies to:IVPS5048P1G1-LVIVPS7548P2G1IVPS10048P2G1IVPS3.5~10kVA-USIVPS3-5-10KVA
What it means
AC output mode setting is different — The AC output mode (LCD setting #28) is not set consistently across the parallel system.
Cause: LCD program #28 is set to different output modes on the paralleled inverters.
How to fix it
- Switch off the inverter and check LCD setting #28.
- For a parallel system in single phase, make sure no 3P1, 3P2, 3P3, 2P1 or 2P2 is set on #28.
- For supporting three-phase systems, make sure no PAL, 2P1 or 2P2 is set on #28.
- For supporting split-phase systems, make sure no PAL, 3P1, 3P2 or 3P3 is set on #28.
- If the problem remains, contact your installer.
Source: IVPS3524P1G1-LV IVPS5048P1G1-LV IVPS7548P2G1 IVPS10048P2G1 User Guide - EN.pdf, p.25