Felicity T-REX-3KLP1G01 Error Codes: Causes & Fixes (47 codes)

This is the complete fault table for the Felicity T-REX-3KLP1G01 Inverter family — 47 codes shared by 6 model numbers, transcribed from the official manual. On Felicity units, a fault code means the unit has cut its output and the red LED stays solid; a warning flashes the red LED while the unit keeps running.

Also coversT-REX-3K6LP1G01T-REX-4KLP1G01T-REX-4K6LP1G01T-REX-5KLP1G01T-REX-6KLP1G01

Last checked against the official manuals on July 10, 2026.

How to read the severity labels

  • Fault(47)output stops · red LED solid

Fault codes (47)output stops · red LED solid

01Fault

PV voltage is too high.

Fault

CauseThe PV string voltage exceeds the inverter's maximum DC input rating — typically a string configured with too many modules in series.

Recommended fixReduce the number of PV modules in series.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 37

02Fault

Over current happen at PV port.

Fault

CauseCurrent from the PV array exceeded the input stage's protection limit, so the inverter shut the PV input down.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 37

04Fault

Short circuit happen at PV port.

Fault

CauseA short circuit was detected at the PV input — the array wiring presents a near-zero-resistance path, so the input stage shut down.

Recommended fixCheck if wiring is connect well.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 37

06Fault

PV current sensor failed.

Fault

CauseThe PV current sensor returned an out-of-range or implausible reading, so the control board can no longer trust its PV current measurement.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 37

07Fault

Battery voltage is too high.

Fault

The battery voltage is too low, it should be charging.

CauseWhen shown as a fault, the battery voltage at the terminals is above the inverter's permitted range — usually a battery bank whose specification or series count does not match the unit. The same number appears in the warning list for low battery voltage, meaning the pack needs charging.

Recommended fixCheck if spec and quantity of batteries are meet requirements.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 37T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 37

09Fault

Overload.

Fault

CauseThe connected load exceeds the inverter's continuous output rating; the buzzer beeps twice every second and protection will cut the output if the load is not reduced.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 37

10Fault

Abnormal LLC.

Fault

CauseThe LLC resonant converter (the isolated DC link inside the unit) is operating outside its normal envelope — an internal converter fault rather than a wiring issue.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 37

11Fault

Over current happen at Buckboost.

Fault

CauseThe buck-boost converter stage drew current above its protection limit.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 37

14Fault

BuckBoost is out of balance.

Fault

CauseThe buck-boost converter stage has drifted out of balance — its internal operating points are no longer matched, which is an internal converter fault rather than a wiring issue.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 37

15Fault

Buckboost current sensor failed.

Fault

CauseThe buck-boost current sensor returned an out-of-range or implausible reading, so the control board can no longer trust that stage's current measurement.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 37

16Fault

NO.2 Buckboost current sensor failed.

Fault

CauseThe second buck-boost current sensor returned an out-of-range or implausible reading, so the control board can no longer trust that channel's current measurement.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 37

17Fault

Overload time out.

Fault

CauseThe output ran in overload longer than the permitted grace period, so protection tripped rather than allow continued operation above rating.

Recommended fixReduce the connected load by switching off some equipment.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 38

19Fault

Output short circuited.

Fault

CauseA short circuit was detected on the inverter output: current spiked while voltage collapsed, pointing to a wiring fault or an abnormal (shorted) load.

Recommended fixCheck if wiring is connected well and remove abnormal load.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 38

20Fault

Input output reverse.

Fault

CauseThe AC input and output wiring are swapped — the inverter detects source voltage on its output terminals, so it refuses to run until the connections are corrected.

Recommended fixConfirm that the input and output wiring is correct.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 38

21Fault

OP current sensor failed.

Fault

Output current sensor failed.

CauseThe output current sensor returned an out-of-range or implausible reading, so the control board can no longer trust its output-current measurement.

Recommended fixOutput current sensor failed.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 38

22Fault

Output voltage is too low.

Fault

CauseThe AC output voltage sagged below the permitted range — usually the connected load exceeds what the inverter can hold voltage into.

Recommended fixReduce the connected load.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 38

23Fault

Output voltage is too high.

Fault

CauseThe inverter measured its own AC output voltage above the permitted range — an internal regulation fault rather than a wiring issue.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 38

24Fault

Over current or surge detected by Software.

Fault

CauseThe control software measured a current or surge on the power stage beyond its protection limit. The software trip catches sustained overcurrent, as opposed to the instantaneous hardware trip of code 25.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 38

25Fault

Hardware detect over current at inverter port.

Fault

CauseA hardware protection circuit tripped on overcurrent at the inverter port. It acts independently of the firmware and reacts to fast transients such as load inrush or a surge.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 37T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 38

26Fault

Invert soft start failed.

Fault

Internal components failed. Invert soft start failed.

CauseInternal components failed — the inverter stage could not complete its soft-start ramp to the working voltage.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 38

28Fault

The DC component of the inverter current is abnormal.

Fault

CauseThe DC component riding on the inverter's output current exceeded the permitted limit — the output waveform has developed an asymmetry, typically from an output-stage or current-feedback fault.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 38

29Fault

Inverter current sensor failed.

Fault

CauseThe inverter-stage current sensor returned an out-of-range or implausible reading, so the control board can no longer trust its inverter current measurement.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 38

30Fault

Bus voltage is too low.

Fault

CauseThe internal DC bus voltage fell below its operating range. The bus is regulated entirely inside the unit, so a persistent low reading points to an internal conversion-stage fault rather than external wiring.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 38

31Fault

Bus voltage is too high.

Fault

AC Surge or internal components failed. Bus voltage is too high.

CauseAn AC surge or failed internal components pushed the internal DC bus above its protection ceiling.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 38

33Fault

Bus soft start failed.

Fault

Internal components failed. Bus soft start failed.

CauseInternal components failed — the DC bus could not be brought up to its working voltage during the soft-start ramp.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 38

34Fault

Over temperature happen at heat sink.

Fault

CauseInverter internal temperature has exceeded the safe operating threshold. Causes include high ambient temperature, blocked cooling vents, failed cooling fan, or installation in direct sunlight.

Recommended fixCheck whether the ambient temperature is too high.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 38

35Fault

The inner temperature over.

Fault

CauseThe temperature inside the enclosure exceeded its limit — high ambient temperature or blocked airflow is the usual reason.

Recommended fixCheck whether the ambient temperature is too high.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 38

36Fault

Internal fan locking fault.

Fault

CauseInternal cooling fan failure detected. Often caused by dust buildup, bearing wear, or debris fouling the fan blades.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 38

38Fault

Leakage current fault.

Fault

CauseGround leakage current above the safety limit was detected — insulation or grounding on the PV or AC side is letting current return outside the normal conductors.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 38

39Fault

Leakage current sensor failed.

Fault

CauseThe leakage current sensor returned an out-of-range or implausible reading, so the inverter can no longer verify that its leakage protection is working.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 38

40Fault

Isolation resistance to ground of the PV string is too low.

Fault

CauseA fault has been detected in the PV input stage — usually a short, ground fault, or isolation failure between the PV array and the inverter chassis. Wet connectors, damaged cable insulation, or moisture in a junction box are common causes.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 38

42Fault

Relay check failure.

Fault

CauseA safety relay inside the inverter has failed self-test or is stuck. The inverter is designed to refuse grid connection in this state, so this is not an issue you can clear with restart cycles.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 38

43Fault

Parallel CAN COMM abnormality.

Fault

CauseCommunication has been lost between the inverter and a peripheral device — typically a battery BMS, smart meter, or external monitoring dongle.

Recommended fixTest the parallel communication line, restart still have problems please contact the after-sales service.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 39

44Fault

Loss of parallel hosts.

Fault

CauseThe unit lost contact with the parallel host (master) inverter — usually a fault on the parallel communication line or the host powering down.

Recommended fixTest the parallel communication line, restart still have problems please contact the after-sales service.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 39

45Fault

Parallel Synchronisation Signal Abnormal.

Fault

CauseThe synchronization signal shared across the parallel communication line is abnormal or missing, so the units can no longer lock their outputs together.

Recommended fixTest the parallel communication line, restart still have problems please contact the after-sales service.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 39

46Fault

Inconsistency in parallel versions.

Fault

CauseThe paralleled inverters are running different firmware versions; every unit on the link must match before the group will run.

Recommended fix1. Update all inverter firmware to the same version. 2. Check the version of each inverter via the LCD settings to ensure that the CPU versions are the same. if it is not the same, please contact after-sales personnel to update the firmware. 3. After updating, if the problem still exists, please contact after-sales.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 39

47Fault

Inconsistent parallel settings.

Fault

CauseThe parallel configuration is set up wrong across the group — typically a mix-up between single-phase parallel and three-phase group settings on the units.

Recommended fixSingle-phase parallel system and group three-phase system setup error.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 39

48Fault

Failure of the parallel system as a whole.

Fault

CauseAnother inverter in the parallel group has an active fault, so the whole system reports a group-level failure until that unit is cleared.

Recommended fixSpecific faults in other machines in the parallel system.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 39

49Fault

Parallel negative power protection.

Fault

CauseOne unit in the parallel group was detected absorbing power from the others (negative power flow), which the protection treats as a load-sharing fault and shuts down.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 39

50Fault

EEPROM failure.

Fault

CauseA read/write error occurred in the EEPROM that stores the inverter's settings and calibration, so the control board cannot reliably save or recall its configuration.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 39

51Fault

BMS doesn't allow inverter to discharge battery.

Fault

CauseThe battery's BMS is refusing discharge — it has signalled over the communication link that the pack must not be drawn down, and the inverter stops discharging automatically.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 37T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 39

52Fault

BMS require inverter to charge battery.

Fault

CauseThe battery's BMS has requested charging over the communication link — the pack needs energy, and the inverter starts charging automatically.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 37T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 39

53Fault

PV parallel failure.

Fault

CauseThe PV1/PV2 parallel-mode setting does not match how the strings are actually wired — the unit expects paralleled inputs and does not see them, or the reverse.

Recommended fixPlease confirm whether PV1 and PV2 need to be set to parallel mode. if not, please turn off this function in APP. if necessary, please confirm whether the wiring of PV1 and PV2 is connected to parallel mode.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 39

54Fault

Temperature sensor disconnected.

Fault

CauseAn internal temperature sensor is no longer detected, so the inverter has lost a measurement it needs for thermal protection.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 39

60Fault

BMS firmware version is not matched.

Fault

CauseThe BMS firmware version does not match what the inverter's protocol expects, so battery communication cannot run reliably until the BMS is updated.

Recommended fixUpgrade the firmware of BMS.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 37

87Fault

Battery input circuit failure.

Fault

CauseThe battery input circuit failed its self-check — the path between the battery terminals and the internal DC stage is not behaving as expected, which points to an internal fault rather than the battery itself.

Recommended fixRestart the unit, if the error persists, contact the repair center.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 39

b50Fault

BMS doesn't allow inverter to charge battery.

Fault

BMS doesn't allow inverter to charge battery (LCD information code shown during BMS communication).

CauseCommunication has been lost between the inverter and a peripheral device — typically a battery BMS, smart meter, or external monitoring dongle.

Recommended fixInformational; inverter follows BMS instruction.

Source:T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf· page 17

Still seeing a code on your T-REX-3KLP1G01?

Send us the code on your screen and a Felicity technician will reply with the exact steps for your unit. Support is free for life — a first diagnosis never needs a callout.

Keep troubleshooting

Related devices

Common questions about T-REX-3KLP1G01 error codes

What is the difference between a fault and a warning on the T-REX-3KLP1G01?
A fault cuts the unit's output and the red LED stays solid — this page lists 47 of them for the T-REX-3KLP1G01. The T-REX-3KLP1G01 manual defines no separate warning table — every listed code stops operation. Resolve the cause of a fault before restarting; warnings can usually be cleared while the unit runs.
Which model numbers does this page cover?
The T-REX-3KLP1G01 shares its firmware and fault table with 5 other model numbers: T-REX-3K6LP1G01, T-REX-4KLP1G01, T-REX-4K6LP1G01, T-REX-5KLP1G01, T-REX-6KLP1G01. If your unit is any of these, every code on this page applies to it.
Where do these codes come from?
Every entry was transcribed from T-REX-3_3.6_4_4.6_5_6KLP1G01-hybrid-inverter-user-guide-English.pdf — Felicity's official documentation. Each row cites its source manual (and page where printed), so you can verify the wording before acting on it.