What it means
Current feedback into the inverter is detected — Power is feeding back into the inverter output.
Cause: L and N cables are connected reversely, or sharing cables are wired between inverters on different phases.
How to fix it
- Restart the inverter.
- Check if the L and N cables are not connected reversely in all inverters.
- For a parallel system in single phase, make sure the sharing cables are connected in all inverters; for three-phase or split-phase systems, make sure the sharing cables are connected in the inverters on the same phase and disconnected in the inverters on different phases.
- If the problem remains, contact your installer.