75kW rated output and 82.5kVA of maximum apparent power
apparent rating is 75kVA on the IVGM75KHP3G1, which stands 1.5 times rated power for 10s

InvertersModel IVGM75KHP3G1
Rated 75kW and 75kVA, the IVGM75KHP3G1 lifts to 82.5kVA of apparent power and tracks 150kW of array inside a 416-850V full-load window.
What sets the IVGM75KHP3G1 apart from the other 8 models in the family: AC Output Line Voltage 380-400 V; AC Output Voltage 220-230 V; AC Rated Output Current 108.7 A; Backup Rated Output Power 75 kW; Battery Voltage Range 160-1000 V; Grid Regulation IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4110; MPPT Full-Load Voltage Range 416-850 V; MPPT Trackers 8.
In stock
apparent rating is 75kVA on the IVGM75KHP3G1, which stands 1.5 times rated power for 10s
two strings, 45A and up to 1000V per input, tracked 416-850V at full load and 150-850V in service
rated output current is 108.7A and the AC pass-through carries 270A on a 3L+N+PE connection
charge and discharge both run at 120+120A, with the charge algorithm keyed to the BMS over RS485 and CAN
peak efficiency is 97.6%, harmonic distortion below 3%, and power factor adjusts 0.8 leading to 0.8 lagging
200kg gross, wall-mounted, working from -40 to 60°C with derating above 45°C and up to 4000m of altitude
Rated 75kW and 75kVA with 82.5kVA of maximum apparent power, the IVGM75KHP3G1 from Felicity Solar is a three-phase hybrid inverter that takes 150kW of PV input over 8 MPPT trackers, holds 97.6% maximum efficiency, drives up to 119.6A of output current, and carries a 2 Years warranty. At full load those trackers work between 416V and 850V, widening to 150-850V in service from a 180V start-up and a 600V rated PV input voltage; every input carries two strings, 45A and up to 1000V. AC wiring runs 3L+N+PE, with 380-400V between lines and 220-230V per phase, rated 108.7A, protected at 218A and able to pass 270A through. Two inputs run LFP batteries between 160V and 1000V at 120+120A in each direction, and the 75kW backup output picks up in 0ms. The Non-Isolated cabinet is smart-cooled, IP66 and wall-mounted, 156kg net and 200kg gross, working from -40 to 60°C with derating above 45°C. We are an authorised Felicity Solar distributor and supply the IVGM75KHP3G1 from our own stock.
Specifications last updated 17 August 2026
| AC Output Line Voltage | 380-400 V |
|---|---|
| AC Output Voltage | 220-230 V |
| AC Rated Output Current | 108.7 A |
| AC Wiring Mode | 3L+N+PE |
| Backup Rated Output Power | 75 kW |
| Battery Inputs | 2 |
| Battery Type | LFP |
| Battery Voltage Range | 160-1000 V |
| Charge Algorithm | Self-Adaption to BMS |
| Grid Frequency Range (50 Hz) | 45-55 Hz |
| Grid Frequency Range (60 Hz) | 55-65 Hz |
| Grid Regulation | IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4110 |
| Ground Fault Current Monitoring | Yes |
| Input Voltage Range | 184-264.5 V |
| MPPT Full-Load Voltage Range | 416-850 V |
| MPPT Trackers | 8 |
| MPPT Voltage Range | 150-850 V |
| Max AC Input Current | 119.6 A |
| Max AC Pass-Through Current | 270 A |
| Max Apparent Power | 82.5 kVA |
| Max Charging Current | 120+120 A |
| Max Discharging Current | 120+120 A |
| Max Efficiency | 97.6 % |
| Max Output Current | 119.6 A |
| Max Output Overcurrent Protection | 218 A |
| Max PV Input Current | 45+45+45+45+45+45+45+45 A |
|---|---|
| Max PV Input Power | 150 kW |
| Max PV Voltage | 1000 V |
| Max Short-Circuit Current | 68+68+68+68+68+68+68+68 A |
| Nominal AC Input Line Voltage | 380-400 V |
| Nominal AC Input Voltage | 220-230 V |
| Nominal Input Frequency | 50/60 Hz |
| Output Frequency | 50/60 Hz |
| Output Short-Circuit Protection | Yes |
| Overload Protection | Yes |
| Overvoltage Category (AC) | III |
| Overvoltage Category (DC) | II |
| Phase | Three Phase |
| Power Factor Adjustment Range | 0.8 leading to 0.8 lagging |
| Protection | PV Input Lightning Protection, PV String Input Reverse Polarity Protection, Battery Input Lightning Protection, Battery Input Reverse Polarity Protection, DC Component Detection, Insulation Resistor Detection, Residual Current Monitoring Unit, Arc Fault Monitoring (optional), Output Over Current Protection, Output Shorted Protection, Output Over Voltage Protection, Remaining Current (RCD) Monitoring, Overheat Protection, Anti-islanding Protection, AC Output Lightning Protection |
| Rated Apparent Output Power | 75 kVA |
| Rated Output Power | 75 kW |
| Rated PV Input Voltage | 600 V |
| Start-Up Voltage | 180 V |
| Strings per MPPT | 2 |
| Surge Protection Level (AC) | III |
| Surge Rating | 1.5*rated (10s) |
| Total Harmonic Distortion | <3 % |
| Transfer Time | 0 ms |
| BMS Communication | RS485, CAN |
|---|---|
| Communication Interface | RS232, RS485 |
| Display | LCD, LED |
| Gross Weight | 200 kg |
| Installation Style | Wall-Mounted |
| Monitoring Module | WiFi/Bluetooth/4G/LAN |
| Net Weight | 156 kg |
|---|---|
| Package Dimensions | 1410 x 960 x 646 mm |
| Parallel Capability | 12 |
| Safety Standard | IEC/EN 62109-1, IEC/EN 62109-2 |
| Topology | Non-Isolated |
| Cooling | Smart Cooling |
|---|---|
| IP Rating | IP66 |
| Operating Altitude | 4000 m |
| Operating Temperature Range | -40 to 60 (>45 derating) °C |
| Relative Humidity | 0-100 (non-condensing) % |
75kW of rated output power, rated 75kVA apparent, rising to 82.5kVA of maximum apparent power and 1.5 times rated power for 10s. The backup output is 75kW as well, presented as 380-400V between lines and 220-230V per phase on a 3L+N+PE connection.
150kW is the maximum PV input power, split over 8 MPPT trackers of two strings each at 45A and up to 1000V. Tracking covers 150-850V, narrows to 416-850V at full load, opens from 180V, and maximum efficiency reads 97.6%.
IEC 61727 and IEC 62116 first, alongside CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99 and VDE-AR-N 4110. Its AC input takes 184-264.5V, at 45-55Hz on a 50Hz grid and 55-65Hz on a 60Hz grid.
LFP batteries from 160V to 1000V across two inputs rated 120+120A for charge and for discharge, the charge algorithm adapting itself to the BMS over RS485 and CAN. The warranty is 2 Years, and safety approval covers IEC 62109-1, EN 62109-1, IEC 62109-2 and EN 62109-2.