Felicity Solar IVGM75KHP3G1 Hybrid Inverter

InvertersModel IVGM75KHP3G1

Felicity Solar IVGM75KHP3G1 75kW Three-Phase Hybrid Solar Inverter

Rated 75kW and 75kVA, the IVGM75KHP3G1 lifts to 82.5kVA of apparent power and tracks 150kW of array inside a 416-850V full-load window.

  • Rated Output Power: 75 kW
  • Max Apparent Power: 82.5 kVA
  • Max Efficiency: 97.6 %
  • Max PV Input Power: 150 kW

Models in the IVGM25KHP3G2 – IVGM125KHP3G1 family

What sets the IVGM75KHP3G1 apart from the other 8 models in the family: AC Output Line Voltage 380-400 V; AC Output Voltage 220-230 V; AC Rated Output Current 108.7 A; Backup Rated Output Power 75 kW; Battery Voltage Range 160-1000 V; Grid Regulation IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4110; MPPT Full-Load Voltage Range 416-850 V; MPPT Trackers 8.

AED 1incl. VAT

In stock

  • Delivered within 3 business days, door to door, to every market we serve.
  • Dispatched the same business day for an order placed before 21:00 (Dubai time), or the next business day after.
  • Delivery charge: AED 1,000
  • 2-year warranty

Felicity Solar IVGM75KHP3G1 75kW Three-Phase Hybrid Solar Inverter features

  • 75kW rated output and 82.5kVA of maximum apparent power

    apparent rating is 75kVA on the IVGM75KHP3G1, which stands 1.5 times rated power for 10s

  • 150kW of PV input shared over 8 MPPT trackers

    two strings, 45A and up to 1000V per input, tracked 416-850V at full load and 150-850V in service

  • 119.6A of output current behind 218A overcurrent protection

    rated output current is 108.7A and the AC pass-through carries 270A on a 3L+N+PE connection

  • Two LFP battery inputs spanning 160V to 1000V

    charge and discharge both run at 120+120A, with the charge algorithm keyed to the BMS over RS485 and CAN

  • 0ms transfer to a 75kW backup output

    peak efficiency is 97.6%, harmonic distortion below 3%, and power factor adjusts 0.8 leading to 0.8 lagging

  • Smart-cooled IP66 enclosure weighing 156kg net

    200kg gross, wall-mounted, working from -40 to 60°C with derating above 45°C and up to 4000m of altitude

About the Felicity Solar IVGM75KHP3G1 75kW Three-Phase Hybrid Solar Inverter

Rated 75kW and 75kVA with 82.5kVA of maximum apparent power, the IVGM75KHP3G1 from Felicity Solar is a three-phase hybrid inverter that takes 150kW of PV input over 8 MPPT trackers, holds 97.6% maximum efficiency, drives up to 119.6A of output current, and carries a 2 Years warranty. At full load those trackers work between 416V and 850V, widening to 150-850V in service from a 180V start-up and a 600V rated PV input voltage; every input carries two strings, 45A and up to 1000V. AC wiring runs 3L+N+PE, with 380-400V between lines and 220-230V per phase, rated 108.7A, protected at 218A and able to pass 270A through. Two inputs run LFP batteries between 160V and 1000V at 120+120A in each direction, and the 75kW backup output picks up in 0ms. The Non-Isolated cabinet is smart-cooled, IP66 and wall-mounted, 156kg net and 200kg gross, working from -40 to 60°C with derating above 45°C. We are an authorised Felicity Solar distributor and supply the IVGM75KHP3G1 from our own stock.

Specifications last updated 17 August 2026

Felicity Solar IVGM75KHP3G1 75kW Three-Phase Hybrid Solar Inverter full specifications

Electrical(49)

AC Output Line Voltage380-400 V
AC Output Voltage220-230 V
AC Rated Output Current108.7 A
AC Wiring Mode3L+N+PE
Backup Rated Output Power75 kW
Battery Inputs2
Battery TypeLFP
Battery Voltage Range160-1000 V
Charge AlgorithmSelf-Adaption to BMS
Grid Frequency Range (50 Hz)45-55 Hz
Grid Frequency Range (60 Hz)55-65 Hz
Grid RegulationIEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4110
Ground Fault Current MonitoringYes
Input Voltage Range184-264.5 V
MPPT Full-Load Voltage Range416-850 V
MPPT Trackers8
MPPT Voltage Range150-850 V
Max AC Input Current119.6 A
Max AC Pass-Through Current270 A
Max Apparent Power82.5 kVA
Max Charging Current120+120 A
Max Discharging Current120+120 A
Max Efficiency97.6 %
Max Output Current119.6 A
Max Output Overcurrent Protection218 A
Max PV Input Current45+45+45+45+45+45+45+45 A
Max PV Input Power150 kW
Max PV Voltage1000 V
Max Short-Circuit Current68+68+68+68+68+68+68+68 A
Nominal AC Input Line Voltage380-400 V
Nominal AC Input Voltage220-230 V
Nominal Input Frequency50/60 Hz
Output Frequency50/60 Hz
Output Short-Circuit ProtectionYes
Overload ProtectionYes
Overvoltage Category (AC)III
Overvoltage Category (DC)II
PhaseThree Phase
Power Factor Adjustment Range0.8 leading to 0.8 lagging
ProtectionPV Input Lightning Protection, PV String Input Reverse Polarity Protection, Battery Input Lightning Protection, Battery Input Reverse Polarity Protection, DC Component Detection, Insulation Resistor Detection, Residual Current Monitoring Unit, Arc Fault Monitoring (optional), Output Over Current Protection, Output Shorted Protection, Output Over Voltage Protection, Remaining Current (RCD) Monitoring, Overheat Protection, Anti-islanding Protection, AC Output Lightning Protection
Rated Apparent Output Power75 kVA
Rated Output Power75 kW
Rated PV Input Voltage600 V
Start-Up Voltage180 V
Strings per MPPT2
Surge Protection Level (AC)III
Surge Rating1.5*rated (10s)
Total Harmonic Distortion<3 %
Transfer Time0 ms

Mechanical(11)

BMS CommunicationRS485, CAN
Communication InterfaceRS232, RS485
DisplayLCD, LED
Gross Weight200 kg
Installation StyleWall-Mounted
Monitoring ModuleWiFi/Bluetooth/4G/LAN
Net Weight156 kg
Package Dimensions1410 x 960 x 646 mm
Parallel Capability12
Safety StandardIEC/EN 62109-1, IEC/EN 62109-2
TopologyNon-Isolated

Environmental(5)

CoolingSmart Cooling
IP RatingIP66
Operating Altitude4000 m
Operating Temperature Range-40 to 60 (>45 derating) °C
Relative Humidity0-100 (non-condensing) %

Certifications(4)

  • IEC 62109-1
  • EN 62109-1
  • IEC 62109-2
  • EN 62109-2

Downloads & support

Frequently Asked Questions

How much power does the IVGM75KHP3G1 deliver?

75kW of rated output power, rated 75kVA apparent, rising to 82.5kVA of maximum apparent power and 1.5 times rated power for 10s. The backup output is 75kW as well, presented as 380-400V between lines and 220-230V per phase on a 3L+N+PE connection.

What size PV array fits the IVGM75KHP3G1?

150kW is the maximum PV input power, split over 8 MPPT trackers of two strings each at 45A and up to 1000V. Tracking covers 150-850V, narrows to 416-850V at full load, opens from 180V, and maximum efficiency reads 97.6%.

Which grid codes can the IVGM75KHP3G1 be commissioned to?

IEC 61727 and IEC 62116 first, alongside CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99 and VDE-AR-N 4110. Its AC input takes 184-264.5V, at 45-55Hz on a 50Hz grid and 55-65Hz on a 60Hz grid.

What batteries does the IVGM75KHP3G1 take, and how long is the warranty?

LFP batteries from 160V to 1000V across two inputs rated 120+120A for charge and for discharge, the charge algorithm adapting itself to the BMS over RS485 and CAN. The warranty is 2 Years, and safety approval covers IEC 62109-1, EN 62109-1, IEC 62109-2 and EN 62109-2.

Customer reviews