160kW of PV input across 8 MPPT trackers
two strings and 45A per tracker at up to 1000V, tracked from 150V to 850V and 444-850V at full load

InvertersModel IVGM80KHP3G1
Carrying 160kW of array on 8 MPPT trackers, the IVGM80KHP3G1 puts out 80kW continuously, 88kVA at its apparent-power ceiling, and 127.5A of current.
What sets the IVGM80KHP3G1 apart from the other 8 models in the family: AC Output Line Voltage 380-400 V; AC Output Voltage 220-230 V; AC Rated Output Current 116 A; Backup Rated Output Power 80 kW; Battery Voltage Range 160-1000 V; Grid Regulation IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4110; MPPT Full-Load Voltage Range 444-850 V; MPPT Trackers 8.
In stock
two strings and 45A per tracker at up to 1000V, tracked from 150V to 850V and 444-850V at full load
80kVA is its apparent rating, and the IVGM80KHP3G1 takes 1.5 times its rated power for 10s
output overcurrent protection is set at 218A and 270A can transit the AC pass-through
charge and discharge each reach 120+120A, and transfer to the 80kW backup output takes 0ms
156kg net and 200kg gross, 1271 mm wide by 814.5 mm high and 379.5 mm deep, wall-mounted up to 4000m
the IVGM80KHP3G1 reports over RS232 and RS485, shows status on LCD and LED, and monitors on WiFi, Bluetooth, 4G or LAN
The Felicity Solar IVGM80KHP3G1 accepts 160kW of PV across 8 MPPT trackers and turns it into 80kW of three-phase output, 80kVA rated apparent and 88kVA at maximum, alongside 127.5A of output current, 97.6% peak efficiency, a 160-1000V battery window and a warranty of 2 Years. Every tracker holds two strings at 45A, tolerates 1000V of PV, and works from a 180V start-up across 150-850V, tightening to 444-850V when the unit runs at full load; rated PV input voltage is 600V. The output is 3L+N+PE, at 380-400V of line voltage and 220-230V per phase, rated 116A, protected at 218A, with 270A available through the AC pass-through. Two inputs move 120+120A into and out of LFP packs, the charge algorithm following the BMS on RS485 and CAN; transfer to the 80kW backup output takes 0ms and surge capacity is 1.5 times rated power for 10s. The wall-mounted, Non-Isolated IP66 cabinet is smart-cooled, stands 814.5 mm tall by 1271 mm wide and 379.5 mm deep, and carries 156kg net. We are an authorised Felicity Solar distributor and supply the IVGM80KHP3G1 from our own stock.
Specifications last updated 17 August 2026
| AC Output Line Voltage | 380-400 V |
|---|---|
| AC Output Voltage | 220-230 V |
| AC Rated Output Current | 116 A |
| AC Wiring Mode | 3L+N+PE |
| Backup Rated Output Power | 80 kW |
| Battery Inputs | 2 |
| Battery Type | LFP |
| Battery Voltage Range | 160-1000 V |
| Charge Algorithm | Self-Adaption to BMS |
| Grid Frequency Range (50 Hz) | 45-55 Hz |
| Grid Frequency Range (60 Hz) | 55-65 Hz |
| Grid Regulation | IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4110 |
| Ground Fault Current Monitoring | Yes |
| Input Voltage Range | 184-264.5 V |
| MPPT Full-Load Voltage Range | 444-850 V |
| MPPT Trackers | 8 |
| MPPT Voltage Range | 150-850 V |
| Max AC Input Current | 127.5 A |
| Max AC Pass-Through Current | 270 A |
| Max Apparent Power | 88 kVA |
| Max Charging Current | 120+120 A |
| Max Discharging Current | 120+120 A |
| Max Efficiency | 97.6 % |
| Max Output Current | 127.5 A |
| Max Output Overcurrent Protection | 218 A |
| Max PV Input Current | 45+45+45+45+45+45+45+45 A |
|---|---|
| Max PV Input Power | 160 kW |
| Max PV Voltage | 1000 V |
| Max Short-Circuit Current | 68+68+68+68+68+68+68+68 A |
| Nominal AC Input Line Voltage | 380-400 V |
| Nominal AC Input Voltage | 220-230 V |
| Nominal Input Frequency | 50/60 Hz |
| Output Frequency | 50/60 Hz |
| Output Short-Circuit Protection | Yes |
| Overload Protection | Yes |
| Overvoltage Category (AC) | III |
| Overvoltage Category (DC) | II |
| Phase | Three Phase |
| Power Factor Adjustment Range | 0.8 leading to 0.8 lagging |
| Protection | PV Input Lightning Protection, PV String Input Reverse Polarity Protection, Battery Input Lightning Protection, Battery Input Reverse Polarity Protection, DC Component Detection, Insulation Resistor Detection, Residual Current Monitoring Unit, Arc Fault Monitoring (optional), Output Over Current Protection, Output Shorted Protection, Output Over Voltage Protection, Remaining Current (RCD) Monitoring, Overheat Protection, Anti-islanding Protection, AC Output Lightning Protection |
| Rated Apparent Output Power | 80 kVA |
| Rated Output Power | 80 kW |
| Rated PV Input Voltage | 600 V |
| Start-Up Voltage | 180 V |
| Strings per MPPT | 2 |
| Surge Protection Level (AC) | III |
| Surge Rating | 1.5*rated (10s) |
| Total Harmonic Distortion | <3 % |
| Transfer Time | 0 ms |
| BMS Communication | RS485, CAN |
|---|---|
| Communication Interface | RS232, RS485 |
| Display | LCD, LED |
| Gross Weight | 200 kg |
| Installation Style | Wall-Mounted |
| Monitoring Module | WiFi/Bluetooth/4G/LAN |
| Net Weight | 156 kg |
|---|---|
| Package Dimensions | 1410 x 960 x 646 mm |
| Parallel Capability | 12 |
| Safety Standard | IEC/EN 62109-1, IEC/EN 62109-2 |
| Topology | Non-Isolated |
| Cooling | Smart Cooling |
|---|---|
| IP Rating | IP66 |
| Operating Altitude | 4000 m |
| Operating Temperature Range | -40 to 60 (>45 derating) °C |
| Relative Humidity | 0-100 (non-condensing) % |
160kW of maximum PV input power, divided over 8 MPPT trackers that each carry two strings at 45A and up to 1000V. The full-load tracking window is 444-850V inside a wider 150-850V range, opening at a 180V start-up, at a 600V rated PV input voltage.
127.5A of maximum output current against 116A rated, behind 218A of output overcurrent protection and with 270A of AC pass-through. Output power is 80kW and 80kVA rated, 88kVA at maximum apparent power, under 380-400V of line voltage and 220-230V per phase.
12 units can be paralleled. Monitoring runs over WiFi, Bluetooth, 4G or LAN, with RS232 and RS485 interfaces, an LCD and LED display, and BMS links on RS485 and CAN. The IP66 cabinet works from -40 to 60°C, derating past 45°C, and to 4000m of altitude.
2 Years of warranty. Approvals are IEC 62109-1, EN 62109-1, IEC 62109-2 and EN 62109-2 for safety, plus the grid codes IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99 and VDE-AR-N 4110.