100kW rated output and 110kVA maximum apparent power
the IVGM100KHP3G1 is rated 100kVA apparent and withstands a 1.5*rated surge for 10s

InvertersModel IVGM100KHP3G1
A three-phase hybrid inverter rated 100kW and 100kVA, the IVGM100KHP3G1 peaks at 110kVA and harvests up to 200kW of PV through 8 MPPT trackers.
What sets the IVGM100KHP3G1 apart from the other 8 models in the family: AC Output Line Voltage 380-400 V; AC Output Voltage 220-230 V; AC Rated Output Current 145 A; Backup Rated Output Power 100 kW; Battery Voltage Range 160-1000 V; Grid Regulation IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4110; MPPT Full-Load Voltage Range 444-850 V; MPPT Trackers 8.
In stock
the IVGM100KHP3G1 is rated 100kVA apparent and withstands a 1.5*rated surge for 10s
each tracker takes 45A, at up to 1000V PV inside a 150-850V tracking window
charging and discharging at 120+120A, with BMS communication on RS485 and CAN
transfer to the 100kW backup output takes 0ms at 220-230V per phase
measuring 1271 x 814.5 x 379.5 mm and rated from -40 to 60°C up to 4000m
the IVGM100KHP3G1 carries a 2 Years warranty and reports on RS232 and RS485
The Felicity Solar IVGM100KHP3G1 is a three-phase hybrid solar inverter rated at 100kW and 100kVA, with 110kVA maximum apparent power, 200kW of maximum PV input across 8 MPPT trackers, a 160-1000V battery voltage range, 97.6% maximum efficiency and a 2 Years warranty. Each tracker accepts 45A and up to 1000V, tracking from 150V to 850V after a 180V start-up. The AC side wires as 3L+N+PE at 220-230V per phase and 380-400V line to line, draws up to 159.4A and delivers up to 159.4A behind 270A output overcurrent protection, with harmonic distortion below 3% and a power factor adjustable from 0.8 leading to 0.8 lagging. Two battery inputs charge and discharge LFP packs at 120+120A, and transfer to the 100kW backup output takes 0ms. The IP66 wall-mounted cabinet measures 1271 x 814.5 x 379.5 mm, weighs 156kg net and 200kg gross, runs from -40 to 60°C and up to 4000m, and takes up to 12 units in parallel. We are an authorised Felicity Solar distributor.
Specifications last updated 17 August 2026
| AC Output Line Voltage | 380-400 V |
|---|---|
| AC Output Voltage | 220-230 V |
| AC Rated Output Current | 145 A |
| AC Wiring Mode | 3L+N+PE |
| Backup Rated Output Power | 100 kW |
| Battery Inputs | 2 |
| Battery Type | LFP |
| Battery Voltage Range | 160-1000 V |
| Charge Algorithm | Self-Adaption to BMS |
| Grid Frequency Range (50 Hz) | 45-55 Hz |
| Grid Frequency Range (60 Hz) | 55-65 Hz |
| Grid Regulation | IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4110 |
| Ground Fault Current Monitoring | Yes |
| Input Voltage Range | 184-264.5 V |
| MPPT Full-Load Voltage Range | 444-850 V |
| MPPT Trackers | 8 |
| MPPT Voltage Range | 150-850 V |
| Max AC Input Current | 159.4 A |
| Max AC Pass-Through Current | 270 A |
| Max Apparent Power | 110 kVA |
| Max Charging Current | 120+120 A |
| Max Discharging Current | 120+120 A |
| Max Efficiency | 97.6 % |
| Max Output Current | 159.4 A |
| Max Output Overcurrent Protection | 270 A |
| Max PV Input Current | 45+45+45+45+45+45+45+45 A |
|---|---|
| Max PV Input Power | 200 kW |
| Max PV Voltage | 1000 V |
| Max Short-Circuit Current | 68+68+68+68+68+68+68+68 A |
| Nominal AC Input Line Voltage | 380-400 V |
| Nominal AC Input Voltage | 220-230 V |
| Nominal Input Frequency | 50/60 Hz |
| Output Frequency | 50/60 Hz |
| Output Short-Circuit Protection | Yes |
| Overload Protection | Yes |
| Overvoltage Category (AC) | III |
| Overvoltage Category (DC) | II |
| Phase | Three Phase |
| Power Factor Adjustment Range | 0.8 leading to 0.8 lagging |
| Protection | PV Input Lightning Protection, PV String Input Reverse Polarity Protection, Battery Input Lightning Protection, Battery Input Reverse Polarity Protection, DC Component Detection, Insulation Resistor Detection, Residual Current Monitoring Unit, Arc Fault Monitoring (optional), Output Over Current Protection, Output Shorted Protection, Output Over Voltage Protection, Remaining Current (RCD) Monitoring, Overheat Protection, Anti-islanding Protection, AC Output Lightning Protection |
| Rated Apparent Output Power | 100 kVA |
| Rated Output Power | 100 kW |
| Rated PV Input Voltage | 600 V |
| Start-Up Voltage | 180 V |
| Strings per MPPT | 2 |
| Surge Protection Level (AC) | III |
| Surge Rating | 1.5*rated (10s) |
| Total Harmonic Distortion | <3 % |
| Transfer Time | 0 ms |
| BMS Communication | RS485, CAN |
|---|---|
| Communication Interface | RS232, RS485 |
| Display | LCD, LED |
| Gross Weight | 200 kg |
| Installation Style | Wall-Mounted |
| Monitoring Module | WiFi/Bluetooth/4G/LAN |
| Net Weight | 156 kg |
|---|---|
| Package Dimensions | 1410 x 960 x 646 mm |
| Parallel Capability | 12 |
| Safety Standard | IEC/EN 62109-1, IEC/EN 62109-2 |
| Topology | Non-Isolated |
| Cooling | Smart Cooling |
|---|---|
| IP Rating | IP66 |
| Operating Altitude | 4000 m |
| Operating Temperature Range | -40 to 60 (>45 derating) °C |
| Relative Humidity | 0-100 (non-condensing) % |
100kW rated output power, rated at 100kVA apparent, with 110kVA maximum apparent power and a 1.5*rated surge for 10s. Backup rated output power is also 100kW, delivered at 220-230V per phase and 380-400V line to line.
200kW of maximum PV input power across 8 MPPT trackers, each accepting 45A, at a maximum PV voltage of 1000V. Tracking runs from 150V to 850V, begins at a 180V start-up voltage, and peak efficiency is 97.6%.
LFP batteries across a 160-1000V range, on two battery inputs charging and discharging at 120+120A. The charge algorithm self-adapts to the BMS, which communicates over RS485 and CAN.
2 Years warranty. Safety follows IEC 62109-1, EN 62109-1, IEC 62109-2 and EN 62109-2, and grid connection follows IEC 61727, IEC 62116, EN 50549, CEI 0-21, NRS 097, UNE 217002, G99 and VDE-AR-N 4110.