Felicity Solar Hybrid Inverters 75-100 kW IVGM100/IVGM75/IVGM80KHP3G1

A three-phase hybrid inverter rated 100kW and 100kVA, the IVGM100KHP3G1 peaks at 110kVA and harvests up to 200kW of PV through 8 MPPT trackers.

Models Covered: IVGM100KHP3G1, IVGM75KHP3G1, IVGM80KHP3G1

Manufacturer: Felicity Solar

Application: The Felicity Solar IVGM100KHP3G1 is a three-phase hybrid solar inverter rated at 100kW and 100kVA, with 110kVA maximum apparent power, 200kW of maximum PV input across 8 MPPT trackers, a 160-1000V battery voltage range, 97.6% maximum efficiency and a 2 Years warranty. Each tracker accepts 45A and up to 1000V, tracking from 150V to 850V after a 180V start-up. The AC side wires as 3L+N+PE at 220-230V per phase and 380-400V line to line, draws up to 159.4A and delivers up to 159.4A behind 270A output overcurrent protection, with harmonic distortion below 3% and a power factor adjustable from 0.8 leading to 0.8 lagging. Two battery inputs charge and discharge LFP packs at 120+120A, and transfer to the 100kW backup output takes 0ms. The IP66 wall-mounted cabinet measures 1271 x 814.5 x 379.5 mm, weighs 156kg net and 200kg gross, runs from -40 to 60°C and up to 4000m, and takes up to 12 units in parallel. We are an authorised Felicity Solar distributor.

Models and prices

Technical Specifications

Technical Specifications
ParameterIVGM100KHP3G1IVGM75KHP3G1IVGM80KHP3G1
Performance & Electrical
AC Output Line Voltage380-400 V
AC Output Voltage220-230 V
AC Rated Output Current145 A108.7 A116 A
AC Wiring Mode3L+N+PE
Backup Rated Output Power100 kW75 kW80 kW
Battery Inputs2
Battery TypeLFP
Battery Voltage Range160-1000 V
Charge AlgorithmSelf-Adaption to BMS
Grid Frequency Range (50 Hz)45-55 Hz
Grid Frequency Range (60 Hz)55-65 Hz
Grid RegulationIEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4110
Ground Fault Current MonitoringYes
Input Voltage Range184-264.5 V
MPPT Full-Load Voltage Range444-850 V416-850 V444-850 V
MPPT Trackers8
MPPT Voltage Range150-850 V
Max AC Input Current159.4 A119.6 A127.5 A
Max AC Pass-Through Current270 A
Max Apparent Power110 kVA82.5 kVA88 kVA
Max Charging Current120+120 A
Max Discharging Current120+120 A
Max Efficiency97.6%
Max Output Current159.4 A119.6 A127.5 A
Max Output Overcurrent Protection270 A218 A218 A
Max PV Input Current45+45+45+45+45+45+45+45 A
Max PV Input Power200 kW150 kW160 kW
Max PV Voltage1000 V
Max Short-Circuit Current68+68+68+68+68+68+68+68 A
Nominal AC Input Line Voltage380-400 V
Nominal AC Input Voltage220-230 V
Nominal Input Frequency50/60 Hz
Output Frequency50/60 Hz
Output Short-Circuit ProtectionYes
Overload ProtectionYes
Overvoltage Category (AC)III
Overvoltage Category (DC)II
PhaseThree Phase
Power Factor Adjustment Range0.8 leading to 0.8 lagging
ProtectionPV Input Lightning Protection, PV String Input Reverse Polarity Protection, Battery Input Lightning Protection, Battery Input Reverse Polarity Protection, DC Component Detection, Insulation Resistor Detection, Residual Current Monitoring Unit, Arc Fault Monitoring (optional), Output Over Current Protection, Output Shorted Protection, Output Over Voltage Protection, Remaining Current (RCD) Monitoring, Overheat Protection, Anti-islanding Protection, AC Output Lightning Protection
Rated Apparent Output Power100 kVA75 kVA80 kVA
Rated Output Power100 kW75 kW80 kW
Rated PV Input Voltage600 V
Start-Up Voltage180 V
Strings per MPPT2
Surge Protection Level (AC)III
Surge Protection Level (DC)III
Surge Rating1.5*rated (10s)
Total Harmonic Distortion<3%
Transfer Time0 ms
Build & Interfaces
BMS CommunicationRS485, CAN
Communication InterfaceRS232, RS485
DisplayLCD, LED
Gross Weight200 kg
Installation StyleWall-Mounted
Monitoring ModuleWiFi/Bluetooth/4G/LAN
Net Weight156 kg
Package Dimensions1410 x 960 x 646 mm
Parallel Capability12
Safety StandardIEC/EN 62109-1, IEC/EN 62109-2
TopologyNon-Isolated
Operating Environment
CoolingSmart Cooling
IP RatingIP66
Operating Altitude4000 m
Operating Temperature Range-40 to 60 (>45 derating) °C
Relative Humidity0-100 (non-condensing)%

Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.

Availability & grid compliance in the UAE

MarketUAE
Grid authority / regulatorDEWA, ADDC, SEWA
Quotation currencyAED
Support hours timezoneAsia/Dubai
Main citiesDubai, Abu Dhabi, Sharjah, Ajman, Ras Al Khaimah

Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in the UAE that rests with the local authorities (DEWA, ADDC, SEWA). Confirm the grid code, import requirements and any local certification with them, or with us, before you order.

For prices, see Felicity Solar Systems: Prices in UAE. Store pickup — collect your order from our store in Dubai or Riyadh.

Key Features & Technical Highlights

  • 100kW rated output and 110kVA maximum apparent power: the IVGM100KHP3G1 is rated 100kVA apparent and withstands a 1.5*rated surge for 10s
  • 200kW of maximum PV input across 8 MPPT trackers: each tracker takes 45A, at up to 1000V PV inside a 150-850V tracking window
  • Two battery inputs over a 160-1000V LFP range: charging and discharging at 120+120A, with BMS communication on RS485 and CAN
  • 97.6% maximum efficiency and harmonic distortion below 3%: transfer to the 100kW backup output takes 0ms at 220-230V per phase
  • IP66 wall-mounted cabinet of 156kg net and 200kg gross: measuring 1271 x 814.5 x 379.5 mm and rated from -40 to 60°C up to 4000m
  • Up to 12 units in parallel, monitored over WiFi, Bluetooth, 4G or LAN: the IVGM100KHP3G1 carries a 2 Years warranty and reports on RS232 and RS485
  • 75kW rated output and 82.5kVA of maximum apparent power: apparent rating is 75kVA on the IVGM75KHP3G1, which stands 1.5 times rated power for 10s
  • 150kW of PV input shared over 8 MPPT trackers: two strings, 45A and up to 1000V per input, tracked 416-850V at full load and 150-850V in service
  • 119.6A of output current behind 218A overcurrent protection: rated output current is 108.7A and the AC pass-through carries 270A on a 3L+N+PE connection
  • Two LFP battery inputs spanning 160V to 1000V: charge and discharge both run at 120+120A, with the charge algorithm keyed to the BMS over RS485 and CAN
  • 0ms transfer to a 75kW backup output: peak efficiency is 97.6%, harmonic distortion below 3%, and power factor adjusts 0.8 leading to 0.8 lagging
  • Smart-cooled IP66 enclosure weighing 156kg net: 200kg gross, wall-mounted, working from -40 to 60°C with derating above 45°C and up to 4000m of altitude

Frequently Asked Questions

What is the rated output power of the IVGM100KHP3G1?

100kW rated output power, rated at 100kVA apparent, with 110kVA maximum apparent power and a 1.5*rated surge for 10s. Backup rated output power is also 100kW, delivered at 220-230V per phase and 380-400V line to line.

How much solar can the IVGM100KHP3G1 take?

200kW of maximum PV input power across 8 MPPT trackers, each accepting 45A, at a maximum PV voltage of 1000V. Tracking runs from 150V to 850V, begins at a 180V start-up voltage, and peak efficiency is 97.6%.

Which batteries work with the IVGM100KHP3G1?

LFP batteries across a 160-1000V range, on two battery inputs charging and discharging at 120+120A. The charge algorithm self-adapts to the BMS, which communicates over RS485 and CAN.

What warranty and standards does the IVGM100KHP3G1 carry?

2 Years warranty. Safety follows IEC 62109-1, EN 62109-1, IEC 62109-2 and EN 62109-2, and grid connection follows IEC 61727, IEC 62116, EN 50549, CEI 0-21, NRS 097, UNE 217002, G99 and VDE-AR-N 4110.

How much power does the IVGM75KHP3G1 deliver?

75kW of rated output power, rated 75kVA apparent, rising to 82.5kVA of maximum apparent power and 1.5 times rated power for 10s. The backup output is 75kW as well, presented as 380-400V between lines and 220-230V per phase on a 3L+N+PE connection.

What size PV array fits the IVGM75KHP3G1?

150kW is the maximum PV input power, split over 8 MPPT trackers of two strings each at 45A and up to 1000V. Tracking covers 150-850V, narrows to 416-850V at full load, opens from 180V, and maximum efficiency reads 97.6%.

Which grid codes can the IVGM75KHP3G1 be commissioned to?

IEC 61727 and IEC 62116 first, alongside CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99 and VDE-AR-N 4110. Its AC input takes 184-264.5V, at 45-55Hz on a 50Hz grid and 55-65Hz on a 60Hz grid.

What batteries does the IVGM75KHP3G1 take, and how long is the warranty?

LFP batteries from 160V to 1000V across two inputs rated 120+120A for charge and for discharge, the charge algorithm adapting itself to the BMS over RS485 and CAN. The warranty is 2 Years, and safety approval covers IEC 62109-1, EN 62109-1, IEC 62109-2 and EN 62109-2.

What is the maximum PV input of the IVGM80KHP3G1?

160kW of maximum PV input power, divided over 8 MPPT trackers that each carry two strings at 45A and up to 1000V. The full-load tracking window is 444-850V inside a wider 150-850V range, opening at a 180V start-up, at a 600V rated PV input voltage.

How much output current does the IVGM80KHP3G1 supply?

127.5A of maximum output current against 116A rated, behind 218A of output overcurrent protection and with 270A of AC pass-through. Output power is 80kW and 80kVA rated, 88kVA at maximum apparent power, under 380-400V of line voltage and 220-230V per phase.