Ten MPPT trackers feed the IVGM125KHP3G1 with 250 kW of array, which it turns into 125 kW of three-phase output, 137 kVA at its apparent-power ceiling and 198.6 A of current, drawn against a 160-950 V LFP bank on two inputs.

  • Rated Output Power: 125 kW
  • Max Apparent Power: 137 kVA
  • Max Efficiency: 97.6 %
  • Max PV Input Power: 250 kW

Models in the IVGM25KHP3G2 – IVGM125KHP3G1 family

What sets the IVGM125KHP3G1 apart from the other 8 models in the family: AC Output Line Voltage 380-400 V; AC Output Voltage 220-230 V; AC Rated Output Current 181.2 A; Backup Rated Output Power 125 kW; Battery Voltage Range 160-950 V; Grid Regulation IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4110; MPPT Full-Load Voltage Range 555-950 V; MPPT Trackers 10.

AED 1incl. VAT

In stock

  • Delivered within 3 business days, door to door, to every market we serve.
  • Dispatched the same business day for an order placed before 21:00 (Dubai time), or the next business day after.
  • Delivery charge: AED 990
  • 2-year warranty

Felicity Solar IVGM125KHP3G1 125kW Three-Phase Hybrid Solar Inverter features

  • 125 kW rated output and 137 kVA of maximum apparent power

    Rated output power is 125 kW and rated apparent output power 125 kVA, rising to 137 kVA at maximum, with a 125 kW backup output that transfers in 0 ms and surge capacity of 1.5 times rated power for 10 seconds.

  • 250 kW of PV input across 10 MPPT trackers

    Maximum PV input power is 250 kW over 10 MPPT trackers carrying two strings each, 45 A of input current and 68 A of short-circuit current per tracker, up to a 1000 V maximum PV voltage, tracking 150-950 V from a 180 V start-up and 555-950 V at full load.

  • Two battery inputs moving 120+120 A across 160-950 V

    Two battery inputs charge and discharge LFP packs at 120+120 A anywhere between 160 V and 950 V, with a charge algorithm that self-adapts to the BMS over RS485 and CAN.

  • 3L+N+PE output rated 181.2 A and 198.6 A at maximum

    AC wiring is 3L+N+PE at 380-400 V line to line and 220-230 V per phase, rated 181.2 A, maximum 198.6 A in and out, protected at 270 A with 270 A of pass-through, THD below 3% and a power factor adjustable from 0.8 leading to 0.8 lagging.

  • 97.6% maximum efficiency with overvoltage category III

    Maximum efficiency is 97.6%; the non-isolated design carries overvoltage category III on the AC side and II on the DC side, surge protection level III on both, ground fault current monitoring, and certification to IEC 62109-1, EN 62109-1, IEC 62109-2 and EN 62109-2.

  • 1271 x 810 x 364 mm IP66 cabinet, 155.5 kg net, 12 in parallel

    The smart-cooled, wall-mounted IP66 cabinet measures 1271 x 810 x 364 mm and weighs 155.5 kg net and 198 kg gross in a 1410 x 960 x 646 mm carton, works from -40 to 60 °C with derating above 45 °C, to 4000 m and 0-100% non-condensing humidity, and parallels up to 12 units. Warranty: 2 Years.

About the Felicity Solar IVGM125KHP3G1 125kW Three-Phase Hybrid Solar Inverter

The Felicity Solar IVGM125KHP3G1 is a three-phase hybrid solar inverter rated 125 kW and 125 kVA, with 137 kVA of maximum apparent power, 250 kW of PV input spread over 10 MPPT trackers, a 160-950 V battery window, 97.6% maximum efficiency and a 2 Years warranty. Every tracker carries two strings at 45 A and 68 A of short-circuit current, tolerates 1000 V, and tracks from 150 V after a 180 V start-up, tightening to 555-950 V at full load around a 600 V rated PV input voltage. AC wiring is 3L+N+PE, 380-400 V line to line and 220-230 V per phase, rated 181.2 A, drawing and delivering up to 198.6 A behind 270 A of output overcurrent protection and 270 A of pass-through, with harmonic distortion under 3%. Two inputs charge and discharge LFP packs at 120+120 A, the 125 kW backup output picks up in 0 ms, and surge capacity is 1.5 times rated power for 10 seconds. The smart-cooled IP66 cabinet measures 1271 x 810 x 364 mm, weighs 155.5 kg net, works to 4000 m and parallels to 12 units. We are an authorised Felicity Solar distributor and supply the IVGM125KHP3G1 from our own stock.

Specifications last updated 17 August 2026

Felicity Solar IVGM125KHP3G1 125kW Three-Phase Hybrid Solar Inverter full specifications

Electrical(49)

AC Output Line Voltage380-400 V
AC Output Voltage220-230 V
AC Rated Output Current181.2 A
AC Wiring Mode3L+N+PE
Backup Rated Output Power125 kW
Battery Inputs2
Battery TypeLFP
Battery Voltage Range160-950 V
Charge AlgorithmSelf-Adaption to BMS
Grid Frequency Range (50 Hz)45-55 Hz
Grid Frequency Range (60 Hz)55-65 Hz
Grid RegulationIEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4110
Ground Fault Current MonitoringYes
Input Voltage Range184-264.5 V
MPPT Full-Load Voltage Range555-950 V
MPPT Trackers10
MPPT Voltage Range150-950 V
Max AC Input Current198.6 A
Max AC Pass-Through Current270 A
Max Apparent Power137 kVA
Max Charging Current120+120 A
Max Discharging Current120+120 A
Max Efficiency97.6 %
Max Output Current198.6 A
Max Output Overcurrent Protection270 A
Max PV Input Current45+45+45+45+45+45+45+45+45+45 A
Max PV Input Power250 kW
Max PV Voltage1000 V
Max Short-Circuit Current68+68+68+68+68+68+68+68+68+68 A
Nominal AC Input Line Voltage380-400 V
Nominal AC Input Voltage220-230 V
Nominal Input Frequency50/60 Hz
Output Frequency50/60 Hz
Output Short-Circuit ProtectionYes
Overload ProtectionYes
Overvoltage Category (AC)III
Overvoltage Category (DC)II
PhaseThree Phase
Power Factor Adjustment Range0.8 leading to 0.8 lagging
ProtectionPV Input Lightning Protection, PV String Input Reverse Polarity Protection, Battery Input Lightning Protection, Battery Input Reverse Polarity Protection, DC Component Detection, Insulation Resistor Detection, Residual Current Monitoring Unit, Arc Fault Monitoring (optional), Output Over Current Protection, Output Shorted Protection, Output Over Voltage Protection, Remaining Current (RCD) Monitoring, Overheat Protection, Anti-islanding Protection, AC Output Lightning Protection
Rated Apparent Output Power125 kVA
Rated Output Power125 kW
Rated PV Input Voltage600 V
Start-Up Voltage180 V
Strings per MPPT2
Surge Protection Level (AC)III
Surge Rating1.5*rated (10s)
Total Harmonic Distortion<3 %
Transfer Time0 ms

Mechanical(11)

BMS CommunicationRS485, CAN
Communication InterfaceRS232, RS485
DisplayLCD, LED
Gross Weight198 kg
Installation StyleWall-Mounted
Monitoring ModuleWiFi/Bluetooth/4G/LAN (optional)
Net Weight155.5 kg
Package Dimensions1410 x 960 x 646 mm
Parallel Capability12
Safety StandardIEC/EN 62109-1, IEC/EN 62109-2
TopologyNon-Isolated

Environmental(5)

CoolingSmart Cooling
IP RatingIP66
Operating Altitude4000 m
Operating Temperature Range-40 to 60 (>45 derating) °C
Relative Humidity0-100 (non-condensing) %

Certifications(4)

  • IEC 62109-1
  • EN 62109-1
  • IEC 62109-2
  • EN 62109-2

Downloads & support

Frequently Asked Questions

How much solar can the IVGM125KHP3G1 take?

250 kW is the maximum PV input power, spread over 10 MPPT trackers with two strings each. Every tracker takes 45 A of input current and 68 A of short-circuit current, tracks from 150 V to 950 V after a 180 V start-up and narrows to 555-950 V at full load, around a 600 V rated PV input voltage and a 1000 V maximum PV voltage.

What battery does the IVGM125KHP3G1 work with?

LFP packs between 160 V and 950 V, on two battery inputs that charge and discharge at 120+120 A. The charge algorithm self-adapts to the BMS over RS485 and CAN, and the 125 kW backup output takes over in 0 ms.

What does the IVGM125KHP3G1 deliver on the AC side?

125 kW rated output power and 125 kVA rated apparent output power, three phase, rising to 137 kVA at maximum. Rated output current is 181.2 A and both maximum AC input current and maximum output current are 198.6 A, behind 270 A of output overcurrent protection and 270 A of pass-through, at 380-400 V line to line and 220-230 V per phase on 3L+N+PE wiring, 50/60 Hz across 45-55 Hz and 55-65 Hz windows, with THD under 3%. Grid settings cover IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99 and VDE-AR-N 4110.

Where can the IVGM125KHP3G1 be installed and what warranty does it carry?

The IP66 wall-mounted cabinet runs from -40 to 60 °C with derating above 45 °C, to 4000 m of altitude and 0-100% non-condensing humidity. It measures 1271 x 810 x 364 mm, weighs 155.5 kg net and 198 kg gross, is monitored by optional WiFi, Bluetooth, 4G or LAN behind an LCD and LED panel, parallels to 12 units, and carries a 2 Years warranty.