2 kW rated and 2 kW backup output at 220 V
single phase on an L+N+PE connection, with output voltage regulation held to 5%

A single-phase 2 kW inverter-charger built around a 24 V battery bank of 21-31.5 V, with a 40 A charger, 15 ms transfer and a low-frequency transformer-based build.
In stock
The Felicity Solar IVPS2524 is a single-phase off-grid inverter-charger rated 2 kW at 220 V and built around a 24 V battery bank working between 21 and 31.5 V. Its charger reaches 40 A, transfer between utility and battery takes 15 ms, and the unit weighs 20.7 kg net. Charging follows that 24 V bank exactly: 23 V start-up, 28.8 V boost, 27.2 V float and a 31.5 V ceiling, across AGM, Flooded, Li-Ion and Self-Defined batteries. The low-frequency transformer-based build carries 2x rated power for 5 seconds, holds output regulation to 5% and backs 2 kW of backup output. A 30 A output overcurrent limit joins Air Switch overload protection and over-charge, over-discharge, short-circuit and over-temperature protection. Utility is accepted from 90 V to 280 V at 50/60 Hz on an L+N+PE connection, with line-mode efficiency above 95% against 90% maximum in inverter mode. RS485 carries BMS data, RS232 is the communication interface, an LCD and LED display reports status, and 6 units run in parallel. It ships at 24.1 kg gross in a 552 x 408 x 290 mm carton, IP21, with intelligent air cooling for 0-40 °C. Warranty 2 Years. We are an authorised Felicity Solar distributor.
Specifications last updated 7 August 2026
| AC Output Voltage | 220 V |
|---|---|
| AC Wiring Mode | L+N+PE |
| Backup Rated Output Power | 2 kW |
| Battery Inputs | 1 |
| Battery Type | AGM, Flooded, Li-Ion, Self-Defined |
| Battery Voltage Range | 21-31.5 V |
| Bulk Charging Voltage | 28.8 V |
| Charge Algorithm | Three-Stage: Boost CC, Boost CV, Float |
| Float Charging Voltage | 27.2 V |
| High DC Input Recovery Voltage | 31 V |
| High Frequency Disconnect | 65 Hz |
| High Frequency Reconnect | 63 Hz |
| High Line Disconnect Voltage | 280 V |
| High Line Reconnect Voltage | 270 V |
| Input Voltage Range | 90-280 V |
| Input Voltage Range (UPS Mode) | 170-280 V |
| Input Voltage Waveform | Sinusoidal (utility or generator) |
| Line Mode Efficiency | >95 % |
| Line Mode Output Waveform | Same As Input Waveform |
| Low DC Shutdown (<50% Load) | 21.5 V |
| Low DC Shutdown (>50% Load) | 21 V |
| Low Frequency Disconnect | 40 Hz |
| Low Frequency Reconnect | 42 Hz |
| Low Line Disconnect (Appliance Mode) | 90 V |
| Low Line Disconnect (UPS Mode) | 170 V |
| Low Line Reconnect (Appliance Mode) | 100 V |
| Low Line Reconnect (UPS Mode) | 180 V |
| Low-Battery Recovery (<50% Load) | 23.5 V |
| Low-Battery Recovery (>50% Load) | 23 V |
| Max AC Charge Current | 40 A |
| Max AC Input Voltage | 280 V |
| Max AC Pass-Through Current | 30 A |
| Max Charging Current | 40 A |
| Max Charging Voltage | 31.5 V |
| Max Efficiency | 90 % |
| Max Output Overcurrent Protection | 30 A |
| Motor Start Capable | Yes |
| Nominal AC Input Voltage | 220 V |
| Nominal DC Input Voltage | 24 V |
| Nominal Input Frequency | 50/60 Hz |
| Output Frequency | 50/60 Hz |
| Output Short-Circuit Protection | Yes |
| Output Voltage Regulation | 5 % |
| Output Voltage Waveform | Pure Sine Wave |
| Overload Protection | Air Switch Protection |
| Overload Trip Time (>105% Load) | 10 s |
| Overload Trip Time (>150% Load) | 5 s |
| Pass-Through Without Battery | No |
| Phase | Single Phase |
| Protection | Over Charge Protection, Over Discharge Protection, Overload Protection, Output Short Circuit Protection, Over Temperature Protection |
| Rated Apparent Output Power | 2.5 kVA |
| Rated Output Power | 2 kW |
| Short-Circuit Protection (Line Mode) | Air Switch Protection |
| Start-Up Voltage | 23 V |
| Surge Rating | 2*rated (5s) |
| Transfer Time | 15 ms |
| BMS Communication | RS485 |
|---|---|
| Communication Interface | RS232 |
| Display | LCD, LED |
| Gross Weight | 24.1 kg |
| Net Weight | 20.7 kg |
| Package Dimensions | 552 x 408 x 290 mm |
| Parallel Capability | 6 |
| Topology | Low-Frequency (transformer-based) |
| Cooling | Intelligent Air Cooling |
|---|---|
| IP Rating | IP21 |
| Operating Temperature Range | 0-40 °C |
| Storage Temperature | -15 to 60 °C |
Looking up an error code on this FelicityESS IVPS/IVPM Series? Browse the full list of codes for this device, with the cause and recommended fix for each.
View error codes for this device →







Step-by-step guide to calculating daily power consumption in kWh. Includes a load audit worksheet and tips for sizing your off-grid solar system correctly.
Read: How to Calculate Your Daily Power Consumption for Off-Grid Solar →Design a portable or permanent off-grid solar system for cabins, desert camps, and remote shelters. Covers small system sizing, portability, and budget tips.
Read: Off-Grid Solar for Cabins, Camps, and Remote Shelters →Discover how off-grid solar powers rural Morocco. Covers village electrification, agricultural pumping, ONEE programs, and Felicity Solar system recommendations.
Read: Solar Energy for Rural Morocco: Off-Grid Solutions for Remote Villages →24 V nominal, over a 21-31.5 V working range. The IVPS2524 starts at 23 V and charges to a 31.5 V ceiling, so the bank has to be a 24 V bank.
40 A maximum charge current, and the same 40 A from the utility, delivered as a 28.8 V boost stage settling to a 27.2 V float across AGM, Flooded, Li-Ion and Self-Defined batteries.
20.7 kg net and 24.1 kg gross, in a 552 x 408 x 290 mm carton. The mass follows from the low-frequency transformer-based build.
6 units in parallel. Each one is single phase at 220 V and 50/60 Hz on an L+N+PE connection, with 30 A output overcurrent protection.