FLS-ES232LC-S

Energy storage system140 codes
36 Critical 65 Fault 39 Warning
0x10A1Cell voltage accumulation overvoltage alarm in battery cluster (level 1).Warninglevel 1
Cause

Vsum > 3.65V × N (N = number of battery strings).

Recommended fix

Send faults externally. Recovers when Vsum < 3.6V × N.

Source:FLS-ES232LC-S.pdf
0x10A2Cell voltage accumulation overvoltage alarm in battery cluster (level 2).Faultlevel 2
Cause

Vsum > 3.7V × N.

Recommended fix

Send faults externally and limit power. Recovers when Vsum < 3.65V × N.

Source:FLS-ES232LC-S.pdf
0x10A3Cell voltage accumulation overvoltage alarm in battery cluster (level 3).Criticallevel 3
Cause

Vsum > 3.8V × N.

Recommended fix

Send faults externally, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay. Recovers when Vsum < 3.7V × N.

Source:FLS-ES232LC-S.pdf
0x10B1Cell voltage accumulation undervoltage alarm in battery cluster (level 1).Warninglevel 1
Cause

Vsum < 2.50V × N.

Recommended fix

Send faults externally. Recovers when Vsum > 2.60V × N.

Source:FLS-ES232LC-S.pdf
0x10B2Cell voltage accumulation undervoltage alarm in battery cluster (level 2).Faultlevel 2
Cause

Vsum < 2.40V × N.

Recommended fix

Send faults externally and limit power. Recovers when Vsum > 2.50V × N.

Source:FLS-ES232LC-S.pdf
0x10B3Cell voltage accumulation undervoltage alarm in battery cluster (level 3).Criticallevel 3
Cause

Vsum < 2.30V × N.

Recommended fix

Send faults externally, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay. Recovers when Vsum > 2.40V × N.

Source:FLS-ES232LC-S.pdf
0x10C1Low insulation fault (level 1).Warninglevel 1
Cause

Insulation resistance ≤ 1000 Ω/V.

Recommended fix

Send faults to EMS. Recovers when > 1100 Ω/V.

Source:FLS-ES232LC-S.pdf
0x10C2Low insulation fault (level 2).Faultlevel 2
Cause

Insulation resistance ≤ 500 Ω/V.

Recommended fix

Send faults to EMS and limit power. Recovers when > 600 Ω/V.

Source:FLS-ES232LC-S.pdf
0x10C3Low insulation fault, single cabinet with no MBCU (level 3).Criticallevel 3
Cause

Insulation resistance ≤ 100 Ω/V.

Recommended fix

Send faults to EMS, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay.

Source:FLS-ES232LC-S.pdf
0x10D1Battery cluster excessive temperature difference alarm (level 1).Warninglevel 1
Cause

Cell temperature spread > 8°C.

Recommended fix

Send faults externally. Recovers when < 6°C.

Source:FLS-ES232LC-S.pdf
0x10D2Battery cluster excessive temperature difference alarm (level 2).Faultlevel 2
Cause

Cell temperature spread > 13°C.

Recommended fix

Send faults externally and limit power. Recovers when < 8°C.

Source:FLS-ES232LC-S.pdf
0x10D3Battery cluster excessive temperature difference alarm (level 3).Criticallevel 3
Cause

Cell temperature spread > 15°C.

Recommended fix

Send faults externally, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay. Recovers when < 13°C.

Source:FLS-ES232LC-S.pdf
0x10E1Battery cluster cell excessive voltage difference alarm (level 1).Warninglevel 1
Cause

Cell voltage spread > 500 mV.

Recommended fix

Send faults externally. Recovers when < 300 mV.

Source:FLS-ES232LC-S.pdf
0x10E2Battery cluster cell excessive voltage difference alarm (level 2).Faultlevel 2
Cause

Cell voltage spread > 3600 mV.

Recommended fix

Send faults externally and limit power. Recovers when < 500 mV.

Source:FLS-ES232LC-S.pdf
0x10E3Battery cluster cell excessive voltage difference alarm (level 3).Criticallevel 3
Cause

Cell voltage spread > 4000 mV.

Recommended fix

Send faults externally, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay. Recovers when < 3600 mV.

Source:FLS-ES232LC-S.pdf
0x10F1Low battery cluster SOC alarm.Warninglevel 1
Cause

SOC < 3%.

Recommended fix

Send faults externally. Recovers when SOC > 5% (threshold subject to actual operating conditions).

Source:FLS-ES232LC-S.pdf
0x20B1Battery cluster SBCU internal bus voltage sampling fault (after applying high voltage).Warninglevel 1
Cause

Invalid internal bus voltage sampling.

Recommended fix

Send faults externally, cluster disables insulation detection function. Recovers on normal sampling.

Source:FLS-ES232LC-S.pdf
0x20B3Battery cluster SBCU internal bus voltage sampling fault (before applying high voltage).Criticallevel 3
Cause

Invalid internal bus voltage sampling.

Recommended fix

Send faults externally, cluster disables insulation detection function with high voltage prohibited. Recovers on normal sampling.

Source:FLS-ES232LC-S.pdf
0x20C3Battery cluster SBCU external bus voltage sampling fault.Criticallevel 3
Cause

Invalid external bus voltage sampling.

Recommended fix

Send faults externally, limit power and request to lower high voltage; if command not received within 5s, cut off the main circuit relay.

Source:FLS-ES232LC-S.pdf
0x20D3Battery cluster SBCU insulation sampling circuit fault (before applying high voltage).Criticallevel 3
Cause

Invalid insulation sampling partial voltage value.

Recommended fix

Send faults externally, cluster disables insulation detection function with high voltage prohibited. Recovers on normal sampling.

Source:FLS-ES232LC-S.pdf
0x20E3Battery cluster high-voltage box current sampling module fault.Criticallevel 3
Cause

Current sampling value reading fails.

Recommended fix

Send faults externally, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay. Recovers on successful current sampling read.

Source:FLS-ES232LC-S.pdf
0x20F1SBCU-EE storage failure.Warninglevel 1
Cause

Communication of EE fails while reading or writing.

Recommended fix

Send faults externally. Recovers when EE communication succeeds.

Source:FLS-ES232LC-S.pdf
0x30B3Battery cluster high-voltage box NTC failure.Warninglevel 1
Cause

SBCU detects BJB_NTC sampling value as invalid.

Recommended fix

Send faults externally. Recovers when BJB_NTC sampling value valid.

Source:FLS-ES232LC-S.pdf
0x40F2Failure to disconnect the main positive circuit relay in the battery cluster high-voltage box.Criticallevel 3
Cause

Sticking failure - main positive relay cannot open.

Recommended fix

Send faults externally, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay.

Source:FLS-ES232LC-S.pdf
0x90A3PACK high-voltage connector overtemperature.Criticallevel 3
Cause

Temp21 or Temp22 on any BMU as judged by SBCU: T > 90°C.

Recommended fix

Send faults to EMS, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay. Latch - manual troubleshooting is required.

Source:FLS-ES232LC-S.pdf
0x1011Battery cluster cell overtemperature alarm (level 1).Warninglevel 1
Cause

Cell maximum temperature > 50°C.

Recommended fix

Send faults externally. Recovers when Temp_max < 45°C.

Source:FLS-ES232LC-S.pdf
0x1012Battery cluster cell overtemperature alarm (level 2).Faultlevel 2
Cause

Cell maximum temperature > 55°C.

Recommended fix

Send faults externally and limit power. Recovers when Temp_max < 50°C.

Source:FLS-ES232LC-S.pdf
0x1013Battery cluster cell overtemperature alarm (level 3).Criticallevel 3
Cause

Cell maximum temperature > 60°C.

Recommended fix

Send faults externally, limit power and request to lower high voltage; if command not received within 5s, cut off the main circuit relay. Recovers when Temp_max < 55°C.

Source:FLS-ES232LC-S.pdf
0x1021Battery cluster cell undertemperature alarm (level 1).Warninglevel 1
Cause

Cell minimum temperature < 5°C.

Recommended fix

Send faults externally. Recovers when Temp_min > 10°C.

Source:FLS-ES232LC-S.pdf
0x1022Battery cluster cell undertemperature alarm (level 2).Faultlevel 2
Cause

Cell minimum temperature < 0°C.

Recommended fix

Send faults externally and limit power. Recovers when Temp_min > 5°C.

Source:FLS-ES232LC-S.pdf
0x1023Battery cluster cell undertemperature alarm (level 3).Criticallevel 3
Cause

Cell minimum temperature < -30°C.

Recommended fix

Send faults externally, limit power and request to lower high voltage; if command not received within 5s, cut off the main circuit relay. Recovers when Temp_min > 0°C.

Source:FLS-ES232LC-S.pdf
0x1031Battery cluster cell overvoltage alarm (level 1).Warninglevel 1
Cause

Cell voltage > 3,650 mV.

Recommended fix

Send faults externally. Recovers when < 3,600 mV.

Source:FLS-ES232LC-S.pdf
0x1032Battery cluster cell overvoltage alarm (level 2).Faultlevel 2
Cause

Cell voltage > 3,700 mV.

Recommended fix

Send faults externally and limit power. Recovers when < 3,650 mV.

Source:FLS-ES232LC-S.pdf
0x1033Battery cluster cell overvoltage alarm (level 3).Criticallevel 3
Cause

Cell voltage > 3,800 mV.

Recommended fix

Send faults externally, limit power and request lower high voltage; immediately cut off the main circuit relay. Recovers when < 3,700 mV.

Source:FLS-ES232LC-S.pdf
0x1041Battery cluster cell undervoltage alarm (level 1).Warninglevel 1
Cause

Cell voltage < 2,500 mV.

Recommended fix

Send faults externally. Recovers when > 2,600 mV.

Source:FLS-ES232LC-S.pdf
0x1042Battery cluster cell undervoltage alarm (level 2).Faultlevel 2
Cause

Cell voltage < 2,400 mV.

Recommended fix

Send faults externally and limit power. Recovers when > 2,500 mV.

Source:FLS-ES232LC-S.pdf
0x1043Battery cluster cell undervoltage alarm (level 3).Criticallevel 3
Cause

Cell voltage < 2,300 mV.

Recommended fix

Send faults externally, limit power and request lower high voltage; immediately cut off the main circuit relay. Recovers when > 2,400 mV.

Source:FLS-ES232LC-S.pdf
0x1051Battery cluster charging current exceeding limit alarm (level 1).Warninglevel 1
Cause

Charging current > 105% × allowable current.

Recommended fix

Send faults externally. Recovers when < 100% allowable current.

Source:FLS-ES232LC-S.pdf
0x1052Battery cluster charging current exceeding limit alarm (level 2).Faultlevel 2
Cause

Charging current > 110% × allowable current.

Recommended fix

Send faults externally and limit power. Recovers when < 105% allowable current.

Source:FLS-ES232LC-S.pdf
0x1053Battery cluster charging current exceeding limit alarm (level 3).Criticallevel 3
Cause

Charging current > 130% × allowable current.

Recommended fix

Send faults externally, limit power and request lower high voltage; if command not received within 5s, cut off the main circuit relay.

Source:FLS-ES232LC-S.pdf
0x1061Battery cluster discharging current exceeding limit alarm (level 1).Warninglevel 1
Cause

Discharging current > 105% × allowable current.

Recommended fix

Send faults externally. Recovers when < 100% allowable current.

Source:FLS-ES232LC-S.pdf
0x1062Battery cluster discharging current exceeding limit alarm (level 2).Faultlevel 2
Cause

Discharging current > 110% × allowable current.

Recommended fix

Send faults externally and limit power. Recovers when < 105% allowable current.

Source:FLS-ES232LC-S.pdf
0x1063Battery cluster discharging current exceeding limit alarm (level 3).Criticallevel 3
Cause

Discharging current > 130% × allowable current.

Recommended fix

Send faults externally, limit power and request lower high voltage; if command not received within 5s, cut off the main circuit relay.

Source:FLS-ES232LC-S.pdf
0x1103Battery cluster voltage mismatch fault.Criticallevel 3
Cause

|Slave plate voltage sum - internal bus voltage| > 40V.

Recommended fix

Send faults externally, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay.

Source:FLS-ES232LC-S.pdf
0x1183Low battery cluster SOH alarm.Criticallevel 3
Cause

SOH < 60%.

Recommended fix

Send faults externally, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay. Latch - Administrator permissions are required to troubleshoot.

Source:FLS-ES232LC-S.pdf
0x2013Loss of communication between battery cluster SBCU and BMU.Criticallevel 3
Cause

No signal received or life signal unchanged.

Recommended fix

Send faults externally, limit power and request to lower high voltage; if command not received within 5s, cut off the main circuit relay. Recovers when life signal changed.

Source:FLS-ES232LC-S.pdf
0x2083Loss of communication between battery cluster SBCU and BMCU.Criticallevel 3
Cause

No signal received or life signal unchanged.

Recommended fix

Send faults externally, limit power and request to lower high voltage; if command not received within 5s, cut off the main circuit relay. Recovers when life signal changed.

Source:FLS-ES232LC-S.pdf
0x2133Fire system communication loss.Criticallevel 3
Cause

No signal received or life signal unchanged from fire system.

Recommended fix

Send faults to EMS, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay.

Source:FLS-ES232LC-S.pdf
0x2153Communication loss between SBCU and EMS (for liquid-cooled single cabinet).Criticallevel 3
Cause

No signal received or life signal unchanged.

Recommended fix

Send faults to EMS, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay.

Source:FLS-ES232LC-S.pdf
0x2163PCS communication loss.Criticallevel 3
Cause

No signal received or life signal unchanged from PCS.

Recommended fix

Send faults to EMS, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay.

Source:FLS-ES232LC-S.pdf
0x317333772 communication loss.Criticallevel 3
Cause

Unsuccessful reboot of 33772 chip 10 times within 1s.

Recommended fix

Send faults to EMS, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay. Recovers on communication recovered.

Source:FLS-ES232LC-S.pdf
0x4013Failure to connect the main positive circuit relay in the battery cluster high-voltage box.Criticallevel 3
Cause

Open-circuit fault detected on main positive relay.

Recommended fix

Send faults externally, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay.

Source:FLS-ES232LC-S.pdf
0x4143Battery cluster relay sticking detection circuit failure.Criticallevel 3
Cause

After low voltage applied without enabling relay: DO4 input voltage not 20-32V or DI1/2 feedback state is 0; after enabling relay: DO4 input voltage not 20-32V or DI1/2 feedback state is 1.

Recommended fix

Send faults externally, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay.

Source:FLS-ES232LC-S.pdf
0x5182Battery cluster SBCU wakeup loss.Criticallevel 3
Cause

Anomalous high-voltage state (wakeup loss & EMS communication loss); cut-off with 5s delay and dormant. Trigger: < 9V.

Recommended fix

Send faults externally. (1) Non-high-voltage state dormant; (2) Normal high-voltage state hold; (3) Anomalous high-voltage state cut-off. Recovers when ≥ 9V.

Source:FLS-ES232LC-S.pdf
0x5192Battery cluster system voltage mismatch fault.Criticallevel 3
Cause

Actual voltage quantity does not match software configuration.

Recommended fix

Send faults externally, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay. Detection starts 10s after Device powered on.

Source:FLS-ES232LC-S.pdf
0x8023Battery cluster thermal runaway alarm.Criticallevel 3
Cause

Thermal runaway detected by any of: 1) Vmin<0.5V & Tmax>65°C; 2) Vmin<0.5V & Tmax-Tmin>30°C; 3) Vmin<0.5V & dT/dt>1°C/s; 4) Voltage sampling disconnection fault & Tmax>65°C; 5) Voltage sampling disconnection fault & Tmax-Tmin>30°C; 6) Voltage sampling disconnection fault & dT/dt>1°C/s; Vmin<0.5V & NTC sampling break or short circuit; Aerosol operation (AI1>9V on any BMU as judged by SBCU) & Tmax>65°C; Any BMU air pressure change rate ≥ 0.1 kPa/s.

Recommended fix

Send faults externally, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay. Latch - manual troubleshooting is required.

Source:FLS-ES232LC-S.pdf
0x8051Aerosol operation alarm in battery pack.Criticallevel 3
Cause

Aerosol operation (AI1 > 9V on any BMU as judged by SBCU).

Recommended fix

Send faults externally, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay.

Source:FLS-ES232LC-S.pdf
0x9012Manual disconnect switch (QS) in the battery cluster high-voltage box is disconnected.Criticallevel 3
Cause

QS feedback signal anomaly detected inside SBCU (judgment made only after receiving applying high voltage command).

Recommended fix

Send faults externally, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay.

Source:FLS-ES232LC-S.pdf
0x9022Fuse (FU1) in the battery cluster high-voltage box is disconnected.Criticallevel 3
Cause

FU1 feedback signal anomaly detected inside SBCU.

Recommended fix

Send faults externally, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay.

Source:FLS-ES232LC-S.pdf
0x9052Excessive temperature in the high-voltage box of the battery cluster.Criticallevel 3
Cause

SBCU detects BJB_NTC > 60°C.

Recommended fix

Send faults externally, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay. Recovers when BJB_NTC < 50°C.

Source:FLS-ES232LC-S.pdf
0x9062Battery cluster SBCU relay drive supply voltage differences.Criticallevel 3
Cause

Relay drive supply voltage < 22V.

Recommended fix

Send faults externally, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay. Recovers at ≥ 22V.

Source:FLS-ES232LC-S.pdf
HVAC-COMP-NOSTARTCompressor does not start.Fault
Cause

Power off, loose circuit connection, or compressor damaged.

Recommended fix

Check main power switch and operation display screen; tighten circuit connector; check compressor and replace if damaged.

Source:FLS-ES232LC-S.pdf
HVAC-COMP-NOWORKCompressor does not work.Fault
Cause

Water temperature set too high (no cooling required) or shutdown delay (compressor minimum shutdown time).

Recommended fix

Check inlet/outlet temperature display and reset control temperature. The compressor will restart with delay if temperature rises again.

Source:FLS-ES232LC-S.pdf
HVAC-COOL-POORPoor cooling effect.Fault
Cause

Insufficient refrigerant; insufficient water flow; serious dust accumulation in condenser; refrigeration system clogged.

Recommended fix

Replenish refrigerant; clean water filter and check water pump; clean condenser; check or replace filter drier.

Source:FLS-ES232LC-S.pdf
HVAC-FAN-NOISEAbnormal noise of fan.Fault
Cause

Worn fan bearings or fan blades scrape against other objects.

Recommended fix

Replace the fan. Check whether any cables interfere with the fan blades.

Source:FLS-ES232LC-S.pdf
HVAC-FAN-NORUNFan does not run.Fault
Cause

Fan failure or fan stuck.

Recommended fix

Check the motor and replace it immediately if defects are found. Check whether any foreign matters are stuck in the fan.

Source:FLS-ES232LC-S.pdf
HVAC-HEAT-NOWORKElectric heating tube does not work.Fault
Cause

Water temperature set too low (no heating required), loose circuit connection, or electric heating tube burnout.

Recommended fix

Check outlet temperature and heating set point; tighten circuit connector; replace burnt-out heating tube.

Source:FLS-ES232LC-S.pdf
HVAC-HV-PROTHigh voltage protection fault.Fault
Cause

Condenser dirty plugging or external circulation fan does not operate.

Recommended fix

Clean the condenser. Check the fan.

Source:FLS-ES232LC-S.pdf
HVAC-LV-PROTLow voltage protection fault.Fault
Cause

Leakage of fluorine or insufficient refrigerant; filter drier clogging; thermal expansion valve failure; water flow rate too low.

Recommended fix

Leak check and replenish refrigerant; replace filter drier; check expansion valve and temperature sensing package; fix water system.

Source:FLS-ES232LC-S.pdf
HVAC-PUMP-FAILCirculating water pump does not start or operates improperly.Fault
Cause

Power off, loose circuit connection, damaged water pump, or air in cooling medium / no cooling medium.

Recommended fix

Check main power switch; tighten circuit connector; replace damaged water pump; evacuate air or replenish cooling medium.

Source:FLS-ES232LC-S.pdf
PCS-ARM-01ARM software fault - phase A output overcurrent.Faultlevel 2
Cause

Phase A output overcurrent.

Recommended fix

Reset to restart. Manual intervention required if fault cannot be rectified. More than 3 faults in one day require manual intervention to confirm grid quality on site.

Source:FLS-ES232LC-S.pdf
PCS-ARM-02ARM software fault - phase A output quick disconnection.Faultlevel 2
Cause

Phase A output quick disconnection.

Recommended fix

Reset to restart. Manual intervention required if fault cannot be rectified.

Source:FLS-ES232LC-S.pdf
PCS-ARM-03ARM software fault - phase B output overcurrent.Faultlevel 2
Cause

Phase B output overcurrent.

Recommended fix

Reset to restart. Manual intervention required if fault cannot be rectified.

Source:FLS-ES232LC-S.pdf
PCS-ARM-04ARM software fault - phase B output quick disconnection.Faultlevel 2
Cause

Phase B output quick disconnection.

Recommended fix

Reset to restart. Manual intervention required if fault cannot be rectified.

Source:FLS-ES232LC-S.pdf
PCS-ARM-05ARM software fault - phase C output overcurrent.Faultlevel 2
Cause

Phase C output overcurrent.

Recommended fix

Reset to restart. Manual intervention required if fault cannot be rectified.

Source:FLS-ES232LC-S.pdf
PCS-ARM-06ARM software fault - phase C output quick disconnection.Faultlevel 2
Cause

Phase C output quick disconnection.

Recommended fix

Reset to restart. Manual intervention required if fault cannot be rectified.

Source:FLS-ES232LC-S.pdf
PCS-ARM-07ARM software fault - phase N output quick disconnection.Faultlevel 2
Cause

Phase N output quick disconnection.

Recommended fix

Reset to restart.

Source:FLS-ES232LC-S.pdf
PCS-ARM-08ARM software fault - phase N output quick disconnection (2).Faultlevel 2
Cause

Phase N output quick disconnection (duplicate entry).

Recommended fix

Reset to restart.

Source:FLS-ES232LC-S.pdf
PCS-ARM-09ARM software fault - AC overvoltage.Warninglevel 1
Cause

AC bus overvoltage.

Recommended fix

Reset to restart. When AC undervoltage cannot be recovered: 1) Check whether AC switch is disconnected or grid is blacked out; 2) Where there is no disconnection, confirm whether the AC insurance is blown.

Source:FLS-ES232LC-S.pdf
PCS-ARM-10ARM software fault - AC undervoltage.Warninglevel 1
Cause

AC bus undervoltage.

Recommended fix

Reset to restart. Check AC switch and AC fuse.

Source:FLS-ES232LC-S.pdf
PCS-ARM-11ARM software fault - output overvoltage.Warninglevel 1
Cause

Output side overvoltage (off-grid).

Recommended fix

Cannot reset to restart. Off-grid output AC overvoltage. Check whether the Device can work with no load.

Source:FLS-ES232LC-S.pdf
PCS-ARM-12ARM software fault - output undervoltage.Warninglevel 1
Cause

Output side undervoltage (off-grid).

Recommended fix

Reset to restart. Off-grid output AC undervoltage. Check whether the device is in an overload state.

Source:FLS-ES232LC-S.pdf
PCS-ARM-13ARM software fault - voltage THDU exceeds the limit.Warninglevel 1
Cause

Voltage total harmonic distortion exceeds limit.

Recommended fix

Reset to restart. Check whether THDU of the power grid exceeds 15%; confirm instantaneous power of load is within design range of system distribution.

Source:FLS-ES232LC-S.pdf
PCS-ARM-14ARM software fault - system phase loss.Warninglevel 1
Cause

Loss of one or more grid phases.

Recommended fix

PCS shall be automatically reset and restarted after the fault is rectified on the site. Check whether the wiring misses a phase.

Source:FLS-ES232LC-S.pdf
PCS-ARM-15ARM software fault - system phase sequence error.Warninglevel 1
Cause

Phase sequence reversed/incorrect.

Recommended fix

PCS shall be automatically reset and restarted after the fault is rectified on the site. Check correspondence between ABCN phase sequence and the modules.

Source:FLS-ES232LC-S.pdf
PCS-ARM-16ARM software fault - DC polarity reverse connection.Warninglevel 1
Cause

DC terminals connected with reversed polarity.

Recommended fix

PCS shall be automatically reset and restarted after the fault is rectified on the site. Check the voltage polarity of the PCS DC terminal.

Source:FLS-ES232LC-S.pdf
PCS-ARM-17ARM software fault - DC bus software overvoltage.Warninglevel 1
Cause

DC bus overvoltage detected by software.

Recommended fix

Reset to restart. Measure battery voltage of PCS DC terminal within allowable range; check contactor of high-voltage box, DC fuse, DC soft start. More than 3 faults in one day require manual intervention.

Source:FLS-ES232LC-S.pdf
PCS-ARM-18ARM software fault - DC busbar software undervoltage.Warninglevel 1
Cause

DC busbar undervoltage detected by software.

Recommended fix

Reset to restart. Measure battery voltage; check contactor and DC fuse. More than 3 faults in one day require manual intervention.

Source:FLS-ES232LC-S.pdf
PCS-ARM-19ARM software fault - system overfrequency.Faultlevel 2
Cause

Grid frequency too high.

Recommended fix

Reset to restart. Check whether grid frequency is beyond range of frequency protection action. Check for AC disconnection or islanding.

Source:FLS-ES232LC-S.pdf
PCS-ARM-20ARM software fault - system underfrequency.Faultlevel 2
Cause

Grid frequency too low.

Recommended fix

Reset to restart. Check whether grid frequency is beyond range of frequency protection action. Check for AC disconnection or islanding.

Source:FLS-ES232LC-S.pdf
PCS-ARM-21ARM software fault - DC charging overcurrent.Faultlevel 2
Cause

DC charging current exceeded threshold.

Recommended fix

Reset to restart. Check system power settings do not exceed rated capacity; check actual battery voltage range. More than 3 faults in one day require manual intervention.

Source:FLS-ES232LC-S.pdf
PCS-ARM-22ARM software fault - DC discharging overcurrent.Faultlevel 2
Cause

DC discharging current exceeded threshold.

Recommended fix

Reset to restart. Check system power settings do not exceed rated capacity; check actual battery voltage range. More than 3 faults in one day require manual intervention.

Source:FLS-ES232LC-S.pdf
PCS-ARM-23ARM software fault - islanding protection.Faultlevel 2
Cause

Islanding condition detected.

Recommended fix

Reset to restart. Where an islanding is detected, the device is shut down from the on-grid state.

Source:FLS-ES232LC-S.pdf
PCS-ARM-24ARM software fault - DC component exceedance.Warninglevel 1
Cause

DC component exceeds limit.

Recommended fix

Reset to restart. 1) Report fault to manufacturer. 2) Contact manufacturer if it occurs 2 times in one day.

Source:FLS-ES232LC-S.pdf
PCS-ARM-25ARM software fault - AC main connection switching-on failure.Faultlevel 2
Cause

AC main contactor failed to close.

Recommended fix

Reset to restart. Does not occur on domestic version. if foreign version reports during startup three consecutive times, contact manufacturer to confirm insulation detection logic and contactor sticking.

Source:FLS-ES232LC-S.pdf
PCS-ARM-26ARM software fault - AC main connection switching-off failure.Faultlevel 2
Cause

AC main contactor failed to open.

Recommended fix

No alarm is generated for the current device.

Source:FLS-ES232LC-S.pdf
PCS-ARM-27ARM software fault - AC soft start switching-on failure.Faultlevel 2
Cause

AC soft start failed to close.

Recommended fix

No alarm is generated for the current device.

Source:FLS-ES232LC-S.pdf
PCS-ARM-28ARM software fault - AC soft start switching-off failure.Faultlevel 2
Cause

AC soft start failed to open.

Recommended fix

No alarm is generated for the current device.

Source:FLS-ES232LC-S.pdf
PCS-ARM-29ARM software fault - DC main connection switching-on failure.Faultlevel 2
Cause

DC main contactor failed to close.

Recommended fix

Reset to restart. Does not occur on device adopting 'One Cluster, One Management' approach.

Source:FLS-ES232LC-S.pdf
PCS-ARM-30ARM software fault - DC main connection switching-off failure.Faultlevel 2
Cause

DC main contactor failed to open.

Recommended fix

Reset to restart. Does not occur on device adopting 'One Cluster, One Management' approach.

Source:FLS-ES232LC-S.pdf
PCS-ARM-31ARM software fault - DC soft start switching-on failure.Warninglevel 1
Cause

DC soft start failed to close.

Recommended fix

Cannot reset to restart, manual confirmation required. 1) Check DC voltage sampling and calibration deviation. 2) Check whether DC soft start resistance is damaged.

Source:FLS-ES232LC-S.pdf
PCS-ARM-32ARM software fault - DC soft start switching-off failure.Fault
Cause

DC soft start failed to open.

Recommended fix

No alarm is generated for the current device.

Source:FLS-ES232LC-S.pdf
PCS-ARM-33ARM software fault - ferroelectric parameter storage error.Warninglevel 1
Cause

Ferroelectric memory parameter storage error.

Recommended fix

Cannot reset to restart. Where PCS internal memory is faulty, contact the manufacturer.

Source:FLS-ES232LC-S.pdf
PCS-ARM-34ARM software fault - DC soft start failure.Warninglevel 1
Cause

DC soft start failure (general).

Recommended fix

Reset to restart. Report to manufacturer if it occurs three consecutive times during startup. 1) DC contactor switching-on under judgment, DC voltage difference too large. 2) When running with DCDC, DCDC startup not correct.

Source:FLS-ES232LC-S.pdf
PCS-ARM-35ARM software fault - reserved.Fault
Recommended fix

No alarm is generated for the current device.

Source:FLS-ES232LC-S.pdf
PCS-ARM-36ARM software fault - reserved.Fault
Recommended fix

No alarm is generated for the current device.

Source:FLS-ES232LC-S.pdf
PCS-ARM-37ARM software fault - start-up conditions are not met.Faultlevel 2
Cause

Start-up preconditions failed.

Recommended fix

Reset to restart. Check whether off-grid and on-grid setting matches actual wiring; after disconnecting from grid with no load, wait for AC terminal voltage to drop to near 0 before starting again.

Source:FLS-ES232LC-S.pdf
PCS-ARM-38ARM software fault - switch fault in operation.Faultlevel 2
Cause

Switch fault during operation.

Recommended fix

No alarm is generated for the current device.

Source:FLS-ES232LC-S.pdf
PCS-ARM-39ARM software fault - inverter startup timeout.Faultlevel 2
Cause

Inverter did not start within timeout.

Recommended fix

Reset to restart.

Source:FLS-ES232LC-S.pdf
PCS-ARM-40ARM software fault - parameter delivery setting error.Faultlevel 2
Cause

Parameter setting error.

Recommended fix

Reset to restart.

Source:FLS-ES232LC-S.pdf
PCS-ARM-41ARM software fault - BMS communication failure.Faultlevel 2
Cause

Communication with BMS lost.

Recommended fix

Reset to restart. Automatic reset after communication is restored.

Source:FLS-ES232LC-S.pdf
PCS-ARM-42ARM software fault - abnormal BMS temperature.Faultlevel 2
Cause

BMS reported abnormal temperature.

Recommended fix

No alarm is generated for the current device.

Source:FLS-ES232LC-S.pdf
PCS-ARM-43ARM software fault - BMS abort.Warninglevel 1
Cause

BMS abort signal received.

Recommended fix

Reset to restart.

Source:FLS-ES232LC-S.pdf
PCS-ARM-44ARM software fault - BMS battery alarm.Criticallevel 3
Cause

BMS battery alarm received.

Recommended fix

Alarm only, the device does not stop.

Source:FLS-ES232LC-S.pdf
PCS-ARM-45ARM software fault - DCDC communication failure.Faultlevel 2
Cause

Communication with DCDC lost.

Recommended fix

PCS and DCDC communication timeout.

Source:FLS-ES232LC-S.pdf
PCS-ARM-46ARM software fault - EMS communication failure.Warninglevel 1
Cause

Communication with EMS lost.

Recommended fix

Reset to restart.

Source:FLS-ES232LC-S.pdf
PCS-ARM-47ARM software fault - emergency stop or core failure.Warninglevel 1
Cause

External emergency stop signal or internal core failure.

Recommended fix

Reset to restart, external dry node signal shall disappear.

Source:FLS-ES232LC-S.pdf
PCS-ARM-48ARM software fault - reserved.Fault
Source:FLS-ES232LC-S.pdf
PCS-ARM-49ARM software fault - reserved.Fault
Source:FLS-ES232LC-S.pdf
PCS-ARM-50ARM software fault - battery software overvoltage.Warninglevel 1
Cause

Battery overvoltage detected by software.

Recommended fix

Reset to restart. Measure battery voltage; check contactor of high-voltage box, DC fuse. More than 3 faults in one day require manual intervention.

Source:FLS-ES232LC-S.pdf
PCS-ARM-51ARM software fault - battery software undervoltage.Warninglevel 1
Cause

Battery undervoltage detected by software.

Recommended fix

Reset to restart. Measure battery voltage; check contactor of high-voltage box, DC fuse. More than 3 faults in one day require manual intervention.

Source:FLS-ES232LC-S.pdf
PCS-ARM-52ARM software fault - abnormal busbar imbalance.Warninglevel 1
Cause

Bus imbalance detected.

Recommended fix

Reset to restart. 1) Fault elimination lasts about 1h after DC cut off. 2) if cannot be reset, contact manufacturer for voltage sampling and capacitor aging issues. 3) if reset works but repeatedly reports after startup, contact manufacturer.

Source:FLS-ES232LC-S.pdf
PCS-ARM-53ARM software fault - busbar semi-direct voltage overvoltage.Warninglevel 1
Cause

Half-bus voltage overvoltage.

Recommended fix

Reset to restart. Measure battery voltage; check contactor and DC fuse. More than 3 faults in one day require manual intervention.

Source:FLS-ES232LC-S.pdf
PCS-ARM-54ARM software fault - DCDC startup timeout.Faultlevel 2
Cause

DCDC did not start within timeout.

Recommended fix

Reset to restart. Check communication cables between PCS and DCDC and the baud rate.

Source:FLS-ES232LC-S.pdf
PCS-FPGA-01FPGA hardware fault - phase A hardware overcurrent.Faultlevel 2
Cause

Phase A hardware overcurrent detected by FPGA.

Recommended fix

Reset to restart. More than 3 faults in one day require manual intervention to confirm the grid quality on site.

Source:FLS-ES232LC-S.pdf
PCS-FPGA-02FPGA hardware fault - phase B hardware overcurrent.Faultlevel 2
Cause

Phase B hardware overcurrent detected by FPGA.

Recommended fix

Reset to restart. More than 3 faults in one day require manual intervention to confirm the grid quality on site.

Source:FLS-ES232LC-S.pdf
PCS-FPGA-03FPGA hardware fault - phase C hardware overcurrent.Faultlevel 2
Cause

Phase C hardware overcurrent detected by FPGA.

Recommended fix

Reset to restart. More than 3 faults in one day require manual intervention to confirm the grid quality on site.

Source:FLS-ES232LC-S.pdf
PCS-FPGA-04FPGA hardware fault - phase N hardware overcurrent.Faultlevel 2
Cause

Phase N hardware overcurrent detected by FPGA.

Recommended fix

Reset to restart. More than 3 faults in one day require manual intervention to confirm the grid quality on site.

Source:FLS-ES232LC-S.pdf
PCS-FPGA-05FPGA hardware fault - reserved.Fault
Source:FLS-ES232LC-S.pdf
PCS-FPGA-06FPGA hardware fault - reserved.Fault
Source:FLS-ES232LC-S.pdf
PCS-FPGA-07FPGA hardware fault - unit direct voltage fault.Warninglevel 1
Cause

Unit DC voltage abnormal.

Recommended fix

Reset to restart. Check whether the contactor of the high-voltage box has been disconnected. if the device fails to start after reset, manual intervention is required to check whether the DC fuse is blown.

Source:FLS-ES232LC-S.pdf
PCS-FPGA-08FPGA hardware fault - reserved.Fault
Source:FLS-ES232LC-S.pdf
PCS-FPGA-09FPGA hardware fault - reserved.Fault
Source:FLS-ES232LC-S.pdf
PCS-FPGA-10FPGA hardware fault - switching power supply undervoltage.Warninglevel 1
Cause

Switching power supply undervoltage.

Recommended fix

Reset to restart. Check whether the contactor of the high-voltage box has been disconnected.

Source:FLS-ES232LC-S.pdf
PCS-FPGA-11FPGA software fault - phase A IGBT failure.Fault
Cause

Phase A IGBT failure.

Recommended fix

No alarm is generated for the current device.

Source:FLS-ES232LC-S.pdf
PCS-FPGA-12FPGA hardware fault - phase B IGBT failure.Fault
Cause

Phase B IGBT failure.

Recommended fix

No alarm is generated for the current device.

Source:FLS-ES232LC-S.pdf
PCS-FPGA-13FPGA hardware fault - phase C IGBT failure.Fault
Cause

Phase C IGBT failure.

Recommended fix

No alarm is generated for the current device.

Source:FLS-ES232LC-S.pdf
PCS-FPGA-14FPGA hardware fault - phase N IGBT failure.Fault
Cause

Phase N IGBT failure.

Source:FLS-ES232LC-S.pdf
PCS-FPGA-15FPGA hardware fault - overtemperature failure.Warninglevel 1
Cause

Internal overtemperature.

Recommended fix

Reset to restart. if over-temperature persists, consider derating depending on ambient temperature: derate 6kW per degree for ambient temperature over 45 degrees. Check fan operation, over-temperature protection threshold, and whether the container is exposed to sunlight without shade.

Source:FLS-ES232LC-S.pdf
PCS-FPGA-16FPGA hardware fault - reserved.Fault
Source:FLS-ES232LC-S.pdf

Compiled from official FelicityESS user manuals. Always consult your device manual and a qualified technician before performing repairs.