Critical

0x10E3

Battery cluster cell excessive voltage difference alarm (level 3).

1 Devices that report this code
FLS-ES232LC-SEnergy storage system↗ view on device
0x10E3Battery cluster cell excessive voltage difference alarm (level 3).Criticallevel 3
Cause

Cell voltage spread > 4000 mV.

Recommended fix

Send faults externally, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay. Recovers when < 3600 mV.

Source:FLS-ES232LC-S.pdf