0x90A3

PACK high-voltage connector overtemperature.

1 Devices that report this code
FLS-ES232LC-SEnergy storage system↗ view on device
0x90A3PACK high-voltage connector overtemperature.Criticallevel 3
Cause

Temp21 or Temp22 on any BMU as judged by SBCU: T > 90°C.

Recommended fix

Send faults to EMS, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay. Latch - manual troubleshooting is required.

Source:FLS-ES232LC-S.pdf