Critical
1 Devices that report this code0x90A3
PACK high-voltage connector overtemperature.
0x90A3PACK high-voltage connector overtemperature.Critical— level 3
Cause
Temp21 or Temp22 on any BMU as judged by SBCU: T > 90°C.
Recommended fix
Send faults to EMS, limit power, request lower high voltage; if command not received within 5s, cut off the main circuit relay. Latch - manual troubleshooting is required.
Source:
FLS-ES232LC-S.pdfCompiled from official FelicityESS user manuals. Always consult your device manual and a qualified technician before performing repairs.