Felicity FLA48250-EU Error Codes: Causes & Fixes (14 codes)

This is the complete fault table for the Felicity FLA48250-EU Battery — all 14 codes from the official manual on one page. On this Felicity device, a fault code means the unit has entered protection and stopped normal operation; a warning leaves it running. The exact indication (LED pattern or display code) is listed per code below.

Last checked against the official manuals on July 10, 2026.

How to read the severity labels

  • Fault(14)operation stops until cleared

Fault codes (14)operation stops until cleared

C01Fault

C01

Fault

Battery overvoltage.

CauseThe total battery pack voltage rose above its rated protection value during charging, so the BMS stopped charging. The protection releases once the pack voltage returns to the rated range.

Recommended fixRestart the unit. if the error persists, contact the repair center.

Source:FLA48250-EU_Manual.pdf· page 8

C02Fault

C02

Fault

Battery undervoltage.

CauseThe total pack voltage fell below its rated protection value during discharging (over-discharge), so the BMS stopped supplying power. The protection releases once the voltage returns to the rated range.

Recommended fixRestart the unit. if the error persists, contact the repair center.

Source:FLA48250-EU_Manual.pdf· page 8

C03Fault

C03

Fault

Cell overvoltage.

CauseAn individual cell reached its over-voltage protection value during charging, typically from cell imbalance letting one cell run ahead of the pack, so the BMS stopped charging.

Recommended fixRestart the unit. if the error persists, contact the repair center.

Source:FLA48250-EU_Manual.pdf· page 8

C04Fault

C04

Fault

Cell undervoltage.

CauseAn individual cell fell below its under-voltage protection value during discharging, usually deep discharge or a weak, imbalanced cell, so the BMS stopped supplying power.

Recommended fixRestart the unit. if the error persists, contact the repair center.

Source:FLA48250-EU_Manual.pdf· page 8

C05Fault

C05

Fault

Charge overcurrent.

CauseThe charging current reached the BMS trigger value and stayed there for 15 seconds, activating charge overcurrent protection: the charger or inverter is pushing more current than the pack accepts. The battery disables both charging input and discharging output while in fault mode.

Recommended fixRestart the unit. if the error persists, contact the repair center. When the charging current reaches the trigger value and lasts for 15 seconds, charging overcurrent protection is activated, entering fault mode. The battery disables both charging input and discharging output. The fault is automatically cleared after 1 minute. After 10 occurrences, the fault can no longer clear automatically, requiring a manual battery restart.

Source:FLA48250-EU_Manual.pdf

C06Fault

C06

Fault

Discharge overcurrent.

CauseThe discharging current reached the BMS trigger value and stayed there for 15 seconds, activating discharge overcurrent protection: the load or inverter is drawing more current than the pack's discharge limit. The battery disables both charging input and discharging output while in fault mode.

Recommended fixRestart the unit. if the error persists, contact the repair center. When the discharging current reaches the trigger value and lasts for 15 seconds, discharging overcurrent protection is activated, entering fault mode. The battery disables both charging input and discharging output. The fault is automatically cleared after 1 minute. After 10 occurrences, the fault can no longer clear automatically, requiring a manual battery restart.

Source:FLA48250-EU_Manual.pdf

C07Fault

C07

Fault

MOS overtemperature.

CauseInverter internal temperature has exceeded the safe operating threshold. Causes include high ambient temperature, blocked cooling vents, failed cooling fan, or installation in direct sunlight.

Recommended fix1. The inner temperature is over the limitation. 2. Check whether the ambient temperature is too high.

Source:FLA48250-EU_Manual.pdf· page 8

C08Fault

C08

Fault

MOS undertemperature.

CauseInverter ambient temperature is below the minimum operating range. Most common in unheated outdoor installs in winter.

Recommended fix1. The internal temperature is lower than the limit range. 2. Check whether the ambient temperature is too low.

Source:FLA48250-EU_Manual.pdf· page 8

C09Fault

C09

Fault

Cell overtemperature.

CauseInverter internal temperature has exceeded the safe operating threshold. Causes include high ambient temperature, blocked cooling vents, failed cooling fan, or installation in direct sunlight.

Recommended fixRestart the unit. if the error persists, contact the repair center.

Source:FLA48250-EU_Manual.pdf· page 8

C10Fault

C10

Fault

Cell undertemperature.

CauseInverter ambient temperature is below the minimum operating range. Most common in unheated outdoor installs in winter.

Recommended fixRestart the unit. if the error persists, contact the repair center.

Source:FLA48250-EU_Manual.pdf· page 8

C11Fault

C11

Fault

Abnormal current sampling.

CauseThe BMS current sensor or its sampling circuit returned an abnormal reading. This is an internal hardware fault in the current-measurement path, not an installation issue.

Recommended fixRestart the unit. if the error persists, contact the repair center.

Source:FLA48250-EU_Manual.pdf· page 8

C12Fault

C12

Fault

Abnormal output impedance.

CauseThe BMS measured abnormal impedance on the battery's output path, commonly a loose or corroded output terminal connection, or a contactor or wiring issue.

Recommended fixRestart the unit. if the error persists, contact the repair center.

Source:FLA48250-EU_Manual.pdf· page 8

C13Fault

C13

Fault

Parallel failed.

CauseA single unit may be installed to a parallel system, or the wiring connection between parallel units is incorrect or incomplete.

Recommended fix1. Please check if single unit is installed to parallel system. 2. if this error happens during parallel installation, please check wires connection. if they are connected correctly, please finish parallel installation first, and then restart the unit. 3. if the problem remains, please contact your installer.

Source:FLA48250-EU_Manual.pdf· page 8

C14Fault

C14

Fault

Output loss.

CauseThe battery's output path is interrupted: the circuit breaker is open or the fuse has blown.

Recommended fix1. Please check whether the circuit breaker is closed. 2. Please check whether the fuse is normal. 3. Restart the unit. if the error persists, contact the repair center.

Source:FLA48250-EU_Manual.pdf· page 8

Still seeing a code on your FLA48250-EU?

Send us the code on your screen and a Felicity technician will reply with the exact steps for your unit. Support is free for life — a first diagnosis never needs a callout.

Keep troubleshooting

Related devices

Common questions about FLA48250-EU error codes

What is the difference between a fault and a warning on the FLA48250-EU?
A fault puts the unit into protection and stops normal operation — this page lists 14 of them for the FLA48250-EU. The FLA48250-EU manual defines no separate warning table — every listed code stops operation. Resolve the cause of a fault before restarting; warnings can usually be cleared while the unit runs.
Does this page apply to other Felicity models?
No — this table was transcribed specifically from the FLA48250-EU manual. Other Felicity devices have their own pages; start from the error-code hub to find the one matching the model number on your unit's label.
Where do these codes come from?
Every entry was transcribed from FLA48250-EU_Manual.pdf — Felicity's official documentation. Each row cites its source manual (and page where printed), so you can verify the wording before acting on it.

Compiled from official Felicity user manuals. Always consult your device manual and a qualified technician before performing repairs.