Felicity LPBA48100-OL Error Codes: Causes & Fixes (38 codes)

This is the complete fault table for the Felicity LPBA48100-OL Battery — all 38 codes from the official manual on one page. On this Felicity device, a fault code means the unit has entered protection and stopped normal operation; a warning leaves it running. The exact indication (LED pattern or display code) is listed per code below.

Last checked against the official manuals on July 10, 2026.

How to read the severity labels

  • Critical(3)unit trips offline — do not restart before checking
  • Fault(30)operation stops until cleared
  • Warning(5)unit keeps running · needs attention

Critical codes (3)unit trips offline — do not restart before checking

PROT-BAT-INT-SHORTCritical

Battery Internal Short Circuit protection.

Critical

Listed under 7.1 Battery System Features 'Battery Protection': protects the cells/pack against an internal short-circuit fault.

CauseThe BMS has detected a short circuit inside the battery pack — on a cell or the internal power path — and tripped the internal short-circuit protection to stop current flow.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:felicity-5.1-kwh-user-manual.pdf· page 4

PROT-INV-EXT-SHORTCritical

External Short Circuit protection.

Critical

Listed under 7.1 Battery System Features as part of the inverter-interface protection set: protects against external short circuits on the inverter/output side.

CauseA short circuit on the inverter/output side — in the DC cabling or the connected equipment — pulled a fault-level current, tripping the external short-circuit protection.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:felicity-5.1-kwh-user-manual.pdf· page 4

TROUBLE-NO-LEDCritical

Battery system cannot work / LED does not light or flash.

Critical

Per 10.2 Troubleshooting: 'Battery system cannot work, when DC switch on and POWER on, the LED doesn't light up or flash, please consider contact the local distributor.'.

CauseThe battery's control electronics are not starting even with the DC switch and power button on — either the pack is so deeply discharged it can no longer activate, or an internal failure is preventing startup.

Recommended fixContact the local distributor.

Source:felicity-5.1-kwh-user-manual.pdf· page 11

Fault codes (30)operation stops until cleared

FAULT-LED:0001Fault

Battery Voltage Low.

Fault

Fault mode indicated by red FAULT LED ON, green LED OFF, and SOC LED pattern LED1=OFF, LED2=OFF, LED3=OFF, LED4=ON.

CauseBattery voltage has fallen below the configured low-voltage cutoff. Causes: deep discharge during a long outage, undersized battery for the load, failing cells, or incorrect battery type setting.

Recommended fixAllow the battery to recharge from PV or grid. Check the battery bank voltage with a multimeter. If a single cell or block reads significantly lower than the others, that cell has failed. Verify the battery type and capacity settings in the inverter menu match the installed bank.

Source:Felicitysolar LPBA48100-OL Felicity Storage Battery User Manual.pdf· page 10

FAULT-LED:0011Fault

Cell Voltage Low.

Fault

Fault mode indicated by red FAULT LED ON, green LED OFF, and SOC LED pattern LED1=OFF, LED2=OFF, LED3=ON, LED4=ON.

CauseOne or more cells have fallen below the under-voltage protection limit — deep discharge, or a weak, aged cell sagging below the threshold under load.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:Felicitysolar LPBA48100-OL Felicity Storage Battery User Manual.pdf· page 10

FAULT-LED:0110Fault

Discharging Current High.

Fault

Fault mode indicated by red FAULT LED ON, green LED OFF, and SOC LED pattern LED1=OFF, LED2=ON, LED3=ON, LED4=OFF.

CauseThe load or inverter is drawing more current than the pack's discharge protection limit, or a short circuit is present on the output side.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:Felicitysolar LPBA48100-OL Felicity Storage Battery User Manual.pdf· page 10

FAULT-LED:1000Fault

Battery Voltage High.

Fault

Fault mode indicated by red FAULT LED ON, green LED OFF, and SOC LED pattern LED1=ON, LED2=OFF, LED3=OFF, LED4=OFF.

CauseBattery voltage has exceeded the configured high-voltage cutoff. Usually a misconfigured charge profile, a runaway charger, or a fault in the battery management system.

Recommended fixDisconnect PV input and verify resting battery voltage. If above the manufacturer's float voltage, the BMS or charge controller has failed. Recheck the inverter's battery profile settings against the battery manufacturer's spec sheet. Stop the system and have a technician inspect before continuing.

Source:Felicitysolar LPBA48100-OL Felicity Storage Battery User Manual.pdf· page 10

FAULT-LED:1001Fault

Current Sensor Abnormal.

Fault

Fault mode indicated by red FAULT LED ON, green LED OFF, and SOC LED pattern LED1=ON, LED2=OFF, LED3=OFF, LED4=ON.

CauseThe BMS current-sampling circuit is returning an abnormal reading — an internal sensor fault rather than a problem with the cells or external wiring.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:Felicitysolar LPBA48100-OL Felicity Storage Battery User Manual.pdf· page 10

FAULT-LED:1010Fault

Charging Current High.

Fault

Fault mode indicated by red FAULT LED ON, green LED OFF, and SOC LED pattern LED1=ON, LED2=OFF, LED3=ON, LED4=OFF.

CauseThe inverter or charger is requesting more charge current than the pack's protection limit — its charge-current setting is above the battery's rating.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:Felicitysolar LPBA48100-OL Felicity Storage Battery User Manual.pdf· page 10

FAULT-LED:1011Fault

Cell Temperature High.

Fault

Fault mode indicated by red FAULT LED ON, green LED OFF, and SOC LED pattern LED1=ON, LED2=OFF, LED3=ON, LED4=ON.

CauseA cell temperature reading has exceeded the protection threshold — high ambient temperature, poor ventilation, or sustained heavy charge/discharge current.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:Felicitysolar LPBA48100-OL Felicity Storage Battery User Manual.pdf· page 10

FAULT-LED:1100Fault

Cell Voltage High.

Fault

Fault mode indicated by red FAULT LED ON, green LED OFF, and SOC LED pattern LED1=ON, LED2=ON, LED3=OFF, LED4=OFF.

CauseOne or more cells have risen above the over-voltage protection limit — a charge voltage set too high on the inverter, or cell imbalance letting one cell run ahead of the rest.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:Felicitysolar LPBA48100-OL Felicity Storage Battery User Manual.pdf· page 10

FAULT-LED:1110Fault

BMS Temperature High.

Fault

Fault mode indicated by red FAULT LED ON, green LED OFF, and SOC LED pattern LED1=ON, LED2=ON, LED3=ON, LED4=OFF.

CauseThe BMS internal temperature has exceeded its limit — hot surroundings, restricted airflow around the case, or sustained current near the pack's maximum.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:Felicitysolar LPBA48100-OL Felicity Storage Battery User Manual.pdf· page 10

LED-FAULT-BMS-THFault

BMS Temperature High.

Fault

FAULT mode: Green LED OFF, Red LED ON. LED1 ON, LED2 ON, LED3 ON, LED4 OFF. Indicates the BMS internal temperature is above the protection threshold.

CauseThe BMS internal temperature is above its protection limit — the ambient is too hot, airflow around the case is restricted, or the pack has been running sustained current near its maximum.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:felicity-5.1-kwh-user-manual.pdf· page 10

LED-FAULT-BMS-TLFault

BMS Temperature Low.

Fault

FAULT mode: Green LED OFF, Red LED ON. LED1 OFF, LED2 OFF, LED3 OFF, LED4 ON (low-temp pattern per 8.9 table). Indicates the BMS internal temperature is below the protection threshold.

CauseThe BMS internal temperature has dropped below its operating range — the battery is sited in surroundings colder than its rated environment.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:felicity-5.1-kwh-user-manual.pdf· page 10

LED-FAULT-BVHFault

Battery Voltage High.

Fault

FAULT mode: Green LED OFF, Red LED ON. LED1 ON, LED2 OFF, LED3 OFF, LED4 OFF. Indicates total battery (pack) voltage above the protection threshold.

CauseBattery voltage has exceeded the configured high-voltage cutoff. Usually a misconfigured charge profile, a runaway charger, or a fault in the battery management system.

Recommended fixDisconnect PV input and verify resting battery voltage. If above the manufacturer's float voltage, the BMS or charge controller has failed. Recheck the inverter's battery profile settings against the battery manufacturer's spec sheet. Stop the system and have a technician inspect before continuing.

Source:felicity-5.1-kwh-user-manual.pdf· page 10

LED-FAULT-BVLFault

Battery Voltage Low.

Fault

FAULT mode: Green LED OFF, Red LED ON. LED1 OFF, LED2 OFF, LED3 OFF, LED4 ON. Indicates total battery (pack) voltage below the protection threshold.

CauseBattery voltage has fallen below the configured low-voltage cutoff. Causes: deep discharge during a long outage, undersized battery for the load, failing cells, or incorrect battery type setting.

Recommended fixAllow the battery to recharge from PV or grid. Check the battery bank voltage with a multimeter. If a single cell or block reads significantly lower than the others, that cell has failed. Verify the battery type and capacity settings in the inverter menu match the installed bank.

Source:felicity-5.1-kwh-user-manual.pdf· page 10

LED-FAULT-CCHFault

Charging Current High.

Fault

FAULT mode: Green LED OFF, Red LED ON. LED1 ON, LED2 OFF, LED3 ON, LED4 OFF. Indicates charge current above the protection threshold (max 50A per spec).

CauseCharge current is above the pack's protection limit — the charger or inverter is set to deliver more current than the battery's rating.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:felicity-5.1-kwh-user-manual.pdf· page 10

LED-FAULT-CSAFault

Current Sensor Abnormal.

Fault

FAULT mode: Green LED OFF, Red LED ON. LED1 ON, LED2 OFF, LED3 OFF, LED4 ON. Indicates the current sensor signal is abnormal (sensor fault).

CauseThe current sensor inside the BMS is reporting an abnormal reading — a faulty current-sampling circuit, not a problem with the cells themselves.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:felicity-5.1-kwh-user-manual.pdf· page 10

LED-FAULT-CTHFault

Cell Temperature High.

Fault

FAULT mode: Green LED OFF, Red LED ON. LED1 OFF, LED2 OFF, LED3 ON, LED4 ON. Indicates a cell temperature above the protection threshold (working range -10 to +50 C per spec).

CauseA cell temperature has risen above the protection threshold — hot ambient conditions, poor ventilation, or prolonged heavy charge/discharge current.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:felicity-5.1-kwh-user-manual.pdf· page 10

LED-FAULT-CTLFault

Cell Temperature Low.

Fault

FAULT mode: Green LED OFF, Red LED ON. LED1 OFF, LED2 ON, LED3 OFF, LED4 ON. Indicates a cell temperature below the protection threshold (working range -10 to +50 C per spec).

CauseA cell temperature is below the safe operating limit — the battery is too cold, and the protection holds until the pack warms back into range.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:felicity-5.1-kwh-user-manual.pdf· page 10

LED-FAULT-CVHFault

Cell Voltage High.

Fault

FAULT mode: Green LED OFF, Red LED ON. LED1 ON, LED2 ON, LED3 OFF, LED4 OFF. Indicates an individual cell over-voltage condition.

CauseAn individual cell has exceeded the over-voltage protection limit — usually a charger/inverter charge voltage set too high, or cell imbalance within the pack.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:felicity-5.1-kwh-user-manual.pdf· page 10

LED-FAULT-CVLFault

Cell Voltage Low.

Fault

FAULT mode: Green LED OFF, Red LED ON. LED1 OFF, LED2 OFF, LED3 ON, LED4 OFF. Indicates an individual cell under-voltage condition.

CauseAn individual cell has dropped below the under-voltage protection limit — the pack was discharged too deeply, or a weak, aged cell is pulling low under load.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:felicity-5.1-kwh-user-manual.pdf· page 10

LED-FAULT-DCHFault

Discharging Current High.

Fault

FAULT mode: Green LED OFF, Red LED ON. LED1 OFF, LED2 ON, LED3 ON, LED4 OFF. Indicates discharge current above the protection threshold (max 50A per spec).

CauseDischarge current is above the pack's protection limit — the connected load or inverter is drawing more than the battery's rating, or there is a short circuit on the output.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:felicity-5.1-kwh-user-manual.pdf· page 10

PROT-BAT-OVERCURRFault

Battery Over Current protection.

Fault

Listed under 7.1 Battery System Features 'Battery Protection': protects against over-current at the battery side (max charge/discharge current 50A per spec).

CauseCharge or discharge current at the battery terminals exceeded the pack's protection limit (50 A maximum per spec) — a load surge, or an inverter charge/discharge setting above the battery's rating.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:felicity-5.1-kwh-user-manual.pdf· page 4

PROT-BAT-OVERTEMPFault

Battery Over Temperature protection.

Fault

Listed under 7.1 Battery System Features 'Battery Protection': protects against over-temperature at the battery side (working temp -10 to +50 C per spec).

CauseInverter internal temperature has exceeded the safe operating threshold. Causes include high ambient temperature, blocked cooling vents, failed cooling fan, or installation in direct sunlight.

Recommended fixPower down the inverter and let it cool. Inspect cooling vents and fan inlets for dust, leaves, or insect nests — clean with compressed air. Confirm the inverter is installed in a shaded, ventilated location with the manufacturer's required clearances on all sides. If the fan does not spin on restart, fan replacement is required.

Source:felicity-5.1-kwh-user-manual.pdf· page 4

PROT-BAT-OVERVOLTFault

Battery Over Voltage protection.

Fault

Listed under 7.1 Battery System Features 'Battery Protection': protects against over-voltage at the battery side (max charge voltage 57.6 V per spec).

CauseBattery voltage rose above the over-voltage protection value — the charger or inverter is applying more than the pack's 57.6 V maximum charge voltage, or failed to taper off at the end of charge.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:felicity-5.1-kwh-user-manual.pdf· page 4

PROT-BAT-UNDERVOLTFault

Battery Under Voltage protection.

Fault

Listed under 7.1 Battery System Features 'Battery Protection': protects against under-voltage at the battery side (min discharge voltage 48 V per spec).

CauseBattery voltage fell below the under-voltage protection value (48 V minimum discharge voltage per spec) — the pack was discharged too deeply before the protection stepped in.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:felicity-5.1-kwh-user-manual.pdf· page 4

PROT-INV-GROUND-FAULTFault

Ground Fault protection.

Fault

Listed under 7.1 Battery System Features as part of the inverter-interface protection set: detects/protects against ground faults at the battery-inverter interface.

CauseLeakage current to ground was detected at the battery-inverter interface — damaged cable insulation or a wiring fault allowing current to flow to earth.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:felicity-5.1-kwh-user-manual.pdf· page 4

PROT-INV-INRUSHFault

In-rush Current protection.

Fault

Listed under 7.1 Battery System Features as part of the inverter-interface protection set: limits/protects against in-rush current at switch-on or fault transients.

CauseA high inrush of current at connection or switch-on — typically the inverter's DC-bus capacitors charging from the battery — exceeded the in-rush protection limit.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:felicity-5.1-kwh-user-manual.pdf· page 4

PROT-INV-OVERCURRFault

Inverter interface Over Current protection.

Fault

Listed under 7.1 Battery System Features as part of the inverter-interface protection set: protects the battery's inverter interface against over-current conditions.

CauseCurrent through the battery's inverter interface exceeded the over-current protection limit — the inverter is drawing or feeding more current than the pack is rated for.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:felicity-5.1-kwh-user-manual.pdf· page 4

PROT-INV-OVERTEMPFault

Inverter interface Over Temperature protection.

Fault

Listed under 7.1 Battery System Features as part of the inverter-interface protection set: protects against over-temperature conditions at the inverter interface.

CauseInverter internal temperature has exceeded the safe operating threshold. Causes include high ambient temperature, blocked cooling vents, failed cooling fan, or installation in direct sunlight.

Recommended fixPower down the inverter and let it cool. Inspect cooling vents and fan inlets for dust, leaves, or insect nests — clean with compressed air. Confirm the inverter is installed in a shaded, ventilated location with the manufacturer's required clearances on all sides. If the fan does not spin on restart, fan replacement is required.

Source:felicity-5.1-kwh-user-manual.pdf· page 4

PROT-INV-OVERVOLTFault

Inverter interface Over Voltage protection.

Fault

Listed under 7.1 Battery System Features as part of the inverter-interface protection set: protects the battery's inverter interface against over-voltage conditions from the inverter side.

CauseVoltage applied at the battery's inverter interface exceeded the over-voltage protection limit — the inverter's charge-voltage setting is too high for this pack.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:felicity-5.1-kwh-user-manual.pdf· page 4

PROT-INV-REVERSE-POLFault

Reverse Polarity protection.

Fault

Listed under 7.1 Battery System Features as part of the inverter-interface protection set: protects against reverse polarity connection of the inverter cables.

CauseThe inverter cables were connected with positive and negative swapped; reverse-polarity protection blocked the connection to prevent damage to the BMS and cells.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:felicity-5.1-kwh-user-manual.pdf· page 4

Warning codes (5)unit keeps running · needs attention

FAULT-LED:0111Warning

BMS Temperature Low.

Warning

Fault mode indicated by red FAULT LED ON, green LED OFF, and SOC LED pattern LED1=OFF, LED2=ON, LED3=ON, LED4=ON.

CauseThe BMS internal temperature is below its operating range — the battery is installed or operating somewhere colder than its rated environment.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:Felicitysolar LPBA48100-OL Felicity Storage Battery User Manual.pdf· page 10

FAULT-LED:1111Warning

Cell Temperature Low.

Warning

Fault mode indicated by red FAULT LED ON, green LED OFF, and SOC LED pattern LED1=ON, LED2=ON, LED3=ON, LED4=ON.

CauseA cell temperature reading is below the operating range — the pack is too cold for safe charging or discharging until it warms up.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:Felicitysolar LPBA48100-OL Felicity Storage Battery User Manual.pdf· page 10

LED-LOW-POWERWarning

Low Power.

Warning

LOW POWER mode: Green LED FLASH, Red LED OFF. SOC LED indicators show 'Running' pattern. Battery has reached low-power state.

CauseState of charge is critically low and the battery has entered its low-power state to protect the cells; output is held back until it is recharged.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:felicity-5.1-kwh-user-manual.pdf· page 10

LED-SOC-LOW-FLASHWarning

SOC < 10% (Flashing).

Warning

SOC LED indication: when state of charge falls below 10%, LED1 flashes. Also annotated as default behaviour in STANDBY, NORMAL, DISCHARGE rows of the mode table ('SOC<10%(DEFAULT): LED1 FLASH').

CauseState of charge has dropped below the 10% default threshold. This is a recharge prompt rather than a fault — LED1 flashes while the battery keeps operating in standby, normal, or discharge mode.

Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.

Source:felicity-5.1-kwh-user-manual.pdf· page 9

TROUBLE-LED-ABNORMALWarning

Red/Green LED flashing or abnormal indication (alarm or protection).

Warning

Per 10.2 Troubleshooting: when the red/green LED on the panel is flashing or normally on it may be just an alarm or protection. Check the 'LED fault message' in chapter 7 for detailed fault-shooting steps. Generally the alarm indication is normal without manual intervention; when the alarm trigger state is removed, the battery system automatically returns to normal use.

CauseAn alarm or protection has triggered and the pack is signalling it through the red/green LED pattern — usually a recoverable condition that clears automatically once the trigger (temperature, current, or voltage out of range) is removed.

Recommended fixCheck whether the red light on the LPBA48100-OL is on; whether the battery can be output voltage or not. Refer to the 'LED fault message' table for detailed fault-shooting steps. The system normally clears the alarm automatically once the trigger condition is removed.

Source:felicity-5.1-kwh-user-manual.pdf· page 11

Still seeing a code on your LPBA48100-OL?

Send us the code on your screen and a Felicity technician will reply with the exact steps for your unit. Support is free for life — a first diagnosis never needs a callout.

Keep troubleshooting

Related devices

Common questions about LPBA48100-OL error codes

What is the difference between a fault and a warning on the LPBA48100-OL?
A fault puts the unit into protection and stops normal operation — this page lists 33 of them for the LPBA48100-OL. A warning leaves the unit running; there are 5 warning codes here. Resolve the cause of a fault before restarting; warnings can usually be cleared while the unit runs.
Does this page apply to other Felicity models?
No — this table was transcribed specifically from the LPBA48100-OL manual. Other Felicity devices have their own pages; start from the error-code hub to find the one matching the model number on your unit's label.
Where do these codes come from?
Every entry was transcribed from Felicitysolar LPBA48100-OL Felicity Storage Battery User Manual.pdf, felicity-5.1-kwh-user-manual.pdf — Felicity's official documentation. Each row cites its source manual (and page where printed), so you can verify the wording before acting on it.

Compiled from official Felicity user manuals. Always consult your device manual and a qualified technician before performing repairs.