Felicity Solar FLB48314TG1 51.2V 16kWh LiFePO4 Battery
Price incl. VATAED 8,101
This is the complete fault table for the Felicity FLB48314TG1 Battery — all 26 codes from the official manual on one page. On this Felicity device, a fault code means the unit has entered protection and stopped normal operation; a warning leaves it running. The exact indication (LED pattern or display code) is listed per code below.
Last checked against the official manuals on 10 July 2026.
Price incl. VATAED 8,101
Charging current reached the trigger value and lasted for 15 seconds. Battery enters fault mode, disabling both charging input and discharging output.
CauseCharging current stayed above the BMS trigger value for 15 seconds — usually because the charge-current setting on the inverter is higher than the battery's recommended value.
Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.
Source:flb48314tg1-manual.pdf
Discharging current reached the trigger value and lasted for 15 seconds. Battery enters fault mode, disabling both charging input and discharging output.
CauseDischarging current stayed above the BMS trigger value for 15 seconds — the connected load or the inverter's discharge-current setting exceeds what the pack is rated to deliver.
Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.
Source:flb48314tg1-manual.pdf
Wrong communication cable used, or battery DIP switch settings are incorrect.
CauseCommunication has been lost between the inverter and a peripheral device — typically a battery BMS, smart meter, or external monitoring dongle.
Recommended fixBefore connecting battery to inverter, set battery DIP switches correctly per the DIP switch table. After setting DIP switches, restart the battery to activate the DIP, then use correct communication cable.
Source:flb48314tg1-manual.pdf
Battery experienced overcurrent causing the external fuse to blow.
CauseThe battery experienced an overcurrent severe enough to blow the external protection fuse — typically a short circuit or a hard current surge on the DC connection.
Recommended fixStep 1: Use Phillips-head screwdriver to remove screws from fuse cover. Step 2: Open fuse cover, remove old fuse, replace with the new one (spare fuse provided). Step 3: Reattach fuse cover and secure. Non-professionals are not allowed to open this cover.
Source:flb48314tg1-manual.pdf
Battery Management System (BMS) temperature fell below the lower protection threshold.
CauseThe BMS internal temperature has fallen below its lower protection threshold — the battery is installed or operating somewhere colder than its rated environment.
Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.
Source:flb48314tg1-manual.pdf
Voltage of any battery cell fell below the rated protection value during discharging. Over-discharging protection activated.
CauseThe voltage of at least one cell fell below the rated protection value during discharging — deep discharge or a weak cell sagging under load — so over-discharging protection activated.
Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.
Source:flb48314tg1-manual.pdf
Total battery pack voltage fell below the rated/protection value. Over-discharge protection activated; system stops supplying power externally.
CauseBattery voltage has fallen below the configured low-voltage cutoff. Causes: deep discharge during a long outage, undersized battery for the load, failing cells, or incorrect battery type setting.
Recommended fixAllow the battery to recharge from PV or grid. Check the battery bank voltage with a multimeter. If a single cell or block reads significantly lower than the others, that cell has failed. Verify the battery type and capacity settings in the inverter menu match the installed bank.
Source:flb48314tg1-manual.pdf
Battery cell temperature fell below lower protection threshold. Cell cannot be charged below 0 C.
CauseA cell temperature reading fell below the lower protection threshold. The cells cannot be charged below 0°C, so a pack sited in a cold location trips this protection.
Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.
Source:flb48314tg1-manual.pdf
Discharging current exceeded protection threshold. See also fault code C06 for discharging overcurrent (15-second trigger).
CauseThe load or inverter is drawing more than the pack's discharge protection limit — beyond the 160 A continuous rating for this model — or a short circuit is present on the output side.
Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.
Source:flb48314tg1-manual.pdf
Total battery pack voltage exceeded the rated/protection value. Indicated by red Power/Running Status LED with LED1 ON only.
CauseBattery voltage has exceeded the configured high-voltage cutoff. Usually a misconfigured charge profile, a runaway charger, or a fault in the battery management system.
Recommended fixDisconnect PV input and verify resting battery voltage. If above the manufacturer's float voltage, the BMS or charge controller has failed. Recheck the inverter's battery profile settings against the battery manufacturer's spec sheet. Stop the system and have a technician inspect before continuing.
Source:flb48314tg1-manual.pdf
Battery cell temperature exceeded upper protection threshold (operating range Charge: 0 to +55 C; Discharge: -20 to +55 C).
CauseA cell temperature reading exceeded the upper protection threshold — ambient heat beyond the working range (0 to +55°C charging, −20 to +55°C discharging), poor ventilation, or sustained heavy current.
Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.
Source:flb48314tg1-manual.pdf
Charging current exceeded protection threshold. See also fault code C05 for charging overcurrent (15-second trigger).
CauseCharge current exceeded the protection threshold — the inverter's charging-current setting is above the battery's recommended value (80 A recommended constant current, 160 A max continuous).
Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.
Source:flb48314tg1-manual.pdf
Voltage of any single cell reached the over-voltage protection value during charging. Charging stopped until cells return to rated range.
CauseA single cell reached the over-voltage protection value during charging — the charge voltage is set too high or an imbalanced cell is rising ahead of the rest — so the BMS stopped charging.
Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.
Source:flb48314tg1-manual.pdf
Internal current sensor reading abnormal/out of expected range. Indicates BMS sensor fault.
CauseThe BMS current sensor is returning an out-of-range reading — a fault in the current-sampling circuit inside the BMS rather than in the cells or wiring.
Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.
Source:flb48314tg1-manual.pdf
Battery Management System (BMS) temperature exceeded the upper protection threshold. May relate to MOSFET heat dissipation through the case.
CauseThe BMS board temperature exceeded its upper protection threshold. The MOSFETs shed heat through the case, so sustained heavy current, hot surroundings, or blocked ventilation can push it over the limit.
Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.
Source:flb48314tg1-manual.pdf
Charging and discharging current set on the inverter is too high.
CauseThe charging and discharging current set on the inverter is higher than the battery's recommended values, so the BMS cuts the output when the limit is exceeded.
Recommended fixSet charging and discharging current on inverter according to recommended values in battery manual (Recommend Charge/Discharge Current: 80A; Max continuous: 160A).
Source:flb48314tg1-manual.pdf
Charging and discharging current settings on the inverter are too high during charging and discharging operations.
CauseThe inverter's charging and discharging current settings are too high for the pack, so current passes the protection limit during operation and the battery interrupts its output.
Recommended fixSet charging and discharging current on inverter according to recommendations in battery manual.
Source:flb48314tg1-manual.pdf
During charging, total voltage of battery pack is higher than rated value or voltage of any single cell reaches protection value. System stops charging.
CauseDuring charging the total pack voltage rose above the rated value, or a single cell reached its protection value — a charge-voltage setting above the recommended 57.6 V, or cell imbalance.
Recommended fixProtection automatically clears when total voltage or all cells return to rated range.
Source:flb48314tg1-manual.pdf
When multiple batteries are connected in parallel, parallel connection of the batteries is not set up correctly.
CauseThe parallel connection between batteries is not set up correctly — inter-battery communication cables are mis-connected or the DIP switches are not set in the correct sequence — so the inverter loses data for some packs.
Recommended fix1) Check the communication cables between the batteries. 2) Check whether the battery DIP switches are set in the correct sequence.
Source:flb48314tg1-manual.pdf
Voltage of any battery cell or total voltage falls below rated protection value during discharging. Over-discharging protection activated; battery stops supplying power externally.
CauseThe voltage of a cell or of the whole pack fell below the rated protection value during discharging — the battery was run down too deeply — so it stopped supplying power externally.
Recommended fixProtection released once voltage of each cell returns to rated range. Recharge within 18 hours.
Source:flb48314tg1-manual.pdf
Surface temperature of case rises abnormally (exceeding normal heat range), accompanied by unusual noises or smells. Note: Some case warmth during normal operation is expected due to MOSFET heat dissipation through the case.
CauseThe BMS MOSFETs dissipate heat through the case, so some warmth is normal — but a rise beyond the usual heat range, especially with unusual noises or smells, points to an internal fault or to operating the pack in an enclosed, hot, or poorly ventilated spot.
Recommended fixStop using the battery pack immediately and contact professional technicians for inspection and maintenance. Do not attempt to disassemble or handle yourself. Ensure proper ventilation around the case during use.
Source:flb48314tg1-manual.pdf
Charging voltage set on the inverter is too low.
CauseThe charging voltage set on the inverter is lower than the battery's recommended 57.6 V, so charging tapers off before the pack is actually full.
Recommended fixSet charging voltage on inverter according to recommended value in battery manual (Max. Charging Voltage: 57.6V; Floating Charging Voltage: 57.6V).
Source:flb48314tg1-manual.pdf
Ambient temperature is too low, preventing the battery from charging.
CauseAmbient temperature is too low for charging — below the pack's 0°C minimum charge temperature the BMS blocks charge current, so the SOC does not rise even though the inverter reports charging.
Recommended fixCharge the battery within the temperature range specified in the manual (Charging temperature: 0 C to +55 C).
Source:flb48314tg1-manual.pdf
Battery in low power state. Charge battery as soon as possible. Recharge within 18 hours after full discharge or over-discharge protection triggered.
CauseThe battery has discharged into its low-power state — remaining charge is nearly exhausted or over-discharge protection has tripped. A pack left in this state can fail to re-activate for charging, which is why recharge within 18 hours is required.
Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.
Source:flb48314tg1-manual.pdf
State of Charge below 10% (default threshold). LED1 flashes during Stand By, Normal, or Discharge modes.
CauseState of charge has fallen below the 10% default warning threshold; LED1 flashes as a recharge prompt while the pack keeps operating normally.
Recommended fixPower down the inverter, wait 5 minutes for capacitors to discharge, then restart. If the fault recurs immediately or repeatedly, record the exact code and contact your installer or the manufacturer's service line.
Source:flb48314tg1-manual.pdf
Battery SOC has not been calibrated.
CauseThe battery's SOC has not been calibrated. The gauge needs one full discharge-charge cycle to calibrate, and the pack should be fully charged at least once a month to keep the reading accurate.
Recommended fixSOC will automatically calibrate after one full charge cycle. Discharge battery to 0%, then charge to 100%. Battery should be fully charged at least once a month.
Source:flb48314tg1-manual.pdf
Send us the code on your screen and a Felicity technician will reply with the exact steps for your unit. If the unit needs replacing, order it online.