LUX-X-48100LG01

Batterie25 codes
also coversLUX-X-48100LCG01LUX-X-48100LMG01
21 Critique 4 Avertissement
C01Battery overvoltage.Critique
Description

Total battery pack voltage has exceeded the upper protection threshold.

Correction recommandée

Restart the unit; if the error persists, contact the repair center.

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 17
C02Battery undervoltage.Critique
Description

Total battery pack voltage has dropped below the lower protection threshold.

Correction recommandée

Restart the unit; if the error persists, contact the repair center.

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 17
C03Cell overvoltage.Critique
Description

An individual cell voltage has exceeded its upper protection threshold.

Correction recommandée

Restart the unit; if the error persists, contact the repair center.

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 17
C04Cell undervoltage.Critique
Description

An individual cell voltage has dropped below its lower protection threshold.

Correction recommandée

Restart the unit; if the error persists, contact the repair center.

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 17
C05Charge overcurrent.Critique
Description

Charging current has exceeded the protection limit.

Correction recommandée

Restart the unit; if the error persists, contact the repair center.

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 17
C06Discharge overcurrent.Critique
Description

Discharging current has exceeded the protection limit.

Correction recommandée

Restart the unit; if the error persists, contact the repair center.

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 17
C07MOS overtemperature.Critique
Description

MOSFET (power switch) temperature has exceeded the upper protection limit.

Cause

1. The inner temperature is over the limitation. 2. Check whether the ambient temperature is too high.

Correction recommandée

Reduce ambient temperature and improve ventilation; if the error persists, return to repair center.

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 17
C08MOS undertemperature.Critique
Description

MOSFET (power switch) temperature is below the lower protection limit.

Cause

1. The internal temperature is lower than the limit range. 2. Check whether the ambient temperature is too low.

Correction recommandée

Raise ambient temperature above the operating minimum; if the error persists, return to repair center.

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 17
C09Cell overtemperature.Critique
Description

A battery cell temperature has exceeded the upper protection limit.

Correction recommandée

Restart the unit; if the error persists, contact the repair center.

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 17
C10Cell undertemperature.Critique
Description

A battery cell temperature has dropped below the lower protection limit.

Correction recommandée

Restart the unit; if the error persists, contact the repair center.

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 17
C11Abnormal current sampling.Avertissement
Description

Internal current sensor / sampling circuit returned an abnormal reading.

Correction recommandée

Restart the unit; if the error persists, contact the repair center.

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 17
C12Abnormal output impedance.Avertissement
Description

Detected abnormal output-side impedance (e.g. faulty contactor, bad connection or load anomaly).

Correction recommandée

Restart the unit; if the error persists, contact the repair center.

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 17
C13Parallel failed.Avertissement
Description

Parallel-mode handshake/operation between battery packs failed.

Cause

1. Check whether a single unit is wrongly installed into a parallel system. 2. if error happens during parallel installation, wires may be misconnected.

Correction recommandée

1. Please check if single unit is installed to parallel system. 2. if this error happens during parallel installation, please check wires connection. if they are connected correctly, please finish parallel installation first, and then restart the unit. 3. if the problem remains, please contact your installer.

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 17
C14Output loss.Critique
Description

Battery pack has lost its output (no DC output detected at the terminals).

Cause

Open circuit breaker, blown fuse or other output-path interruption.

Correction recommandée

1. Please check whether the circuit breaker is closed; 2. Please check whether the fuse is normal; 3. Restart the unit. if the error persists, contact the repair center.

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 17
FAULT-LED-BMSTHBMS temperature high.Critique
Description

FAULT mode indicated by RED LED ON with LED1 ON, LED2 ON, LED3 ON, LED4 OFF: BMS PCB / MOSFET temperature above safe limit.

Cause

Inner BMS temperature exceeds limitation; ambient too hot or excessive current.

Correction recommandée

Reduce ambient temperature, ensure clearance for heat dissipation, reduce current; allow to cool.

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 15
FAULT-LED-BMSTLBMS temperature low.Critique
Description

FAULT mode indicated by RED LED ON with LED1 OFF, LED2 OFF, LED3 OFF, LED4 ON: BMS PCB temperature below safe limit.

Cause

BMS internal temperature below operating range; ambient too cold.

Correction recommandée

Move battery to environment within operating temperature range (above 0 degC).

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 15
FAULT-LED-BVHBattery voltage high.Critique
Description

FAULT mode indicated by RED LED ON, GREEN LED OFF, with LED1 ON, LED2 OFF, LED3 OFF, LED4 OFF: total battery voltage above safe threshold.

Cause

Battery pack voltage above safe threshold.

Correction recommandée

Stop charging and check charger/inverter charge-voltage settings; allow voltage to recover.

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 15
FAULT-LED-BVLBattery voltage low.Critique
Description

FAULT mode indicated by RED LED ON with LED1 OFF, LED2 ON, LED3 OFF, LED4 OFF: total battery voltage below safe threshold.

Cause

Battery pack voltage below safe threshold (deeply discharged).

Correction recommandée

Recharge the battery promptly using AC or PV; do not leave the pack idle in low-power state.

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 15
FAULT-LED-CCHCharging current high.Critique
Description

FAULT mode indicated by RED LED ON with LED1 ON, LED2 OFF, LED3 ON, LED4 OFF: charging current above protection limit.

Cause

Charger / inverter requesting current above pack limit.

Correction recommandée

Reduce charge current setting on the inverter/charger to within the pack rating.

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 15
FAULT-LED-CSACurrent sensor abnormal.Avertissement
Description

FAULT mode indicated by RED LED ON with LED1 ON, LED2 ON, LED3 OFF, LED4 ON: internal current sensor reports abnormal reading.

Cause

Faulty current sampling circuit / sensor inside BMS.

Correction recommandée

Restart the unit; if the error persists, return to repair center.

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 15
FAULT-LED-CTHCell temperature high.Critique
Description

FAULT mode indicated by RED LED ON with LED1 ON, LED2 OFF, LED3 OFF, LED4 ON: a cell temperature is above safe limit.

Cause

Cell temperature exceeds protection threshold.

Correction recommandée

Stop charging/discharging, allow battery to cool; check ambient temperature and ventilation.

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 15
FAULT-LED-CTLCell temperature low.Critique
Description

FAULT mode indicated by RED LED ON with LED1 OFF, LED2 ON, LED3 OFF, LED4 ON: a cell temperature is below safe limit.

Cause

Cell temperature below operating range.

Correction recommandée

Warm the battery to above 0 degC before charging/discharging.

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 15
FAULT-LED-CVHCell voltage high.Critique
Description

FAULT mode indicated by RED LED ON with LED1 ON, LED2 ON, LED3 OFF, LED4 OFF: an individual cell voltage exceeds the safe upper limit.

Cause

One or more cells over-voltage; possible cell imbalance or charger overvoltage.

Correction recommandée

Stop charging; verify charger/inverter max charge voltage; allow BMS to balance and recover.

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 15
FAULT-LED-CVLCell voltage low.Critique
Description

FAULT mode indicated by RED LED ON with LED1 OFF, LED2 OFF, LED3 ON, LED4 OFF: an individual cell voltage is below the safe lower limit.

Cause

Cell undervoltage / over-discharge.

Correction recommandée

Recharge promptly; if cells fail to recover, return battery to repair center.

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 15
FAULT-LED-DCHDischarging current high.Critique
Description

FAULT mode indicated by RED LED ON with LED1 OFF, LED2 ON, LED3 ON, LED4 OFF: discharge current above protection limit.

Cause

Load / inverter draws current above pack limit; possible short circuit.

Correction recommandée

Reduce load; check for short-circuit on output; verify inverter sizing matches battery count.

Source:LUX-X-48100LG01-Litium-Battery-User-Guide.pdf · page 15

Compilé à partir des manuels utilisateur officiels FelicityESS. Consultez toujours le manuel de votre appareil et un technicien qualifié avant toute réparation.