HE-GF-FLA-48500

Batterie14 codes
also coversFLA48500
14 Défaut
C01Battery overvoltage.Défaut
Description

Battery overvoltage protection triggered (pack-level voltage exceeded threshold).

Cause

Battery pack voltage above operating limit (operating range 44.8-57.6V; max charging voltage 57.6V).

Correction recommandée

Restart the unit. if the error persists, contact the repair center.

Source:HE-GF-FLA-48500 Manual_20250327_EN.pdf
C02Battery undervoltage.Défaut
Description

Battery undervoltage protection triggered (pack-level voltage below threshold).

Cause

Battery pack voltage below cut-off (cut-off voltage 48V); over-discharge condition.

Correction recommandée

Restart the unit. if the error persists, contact the repair center.

Source:HE-GF-FLA-48500 Manual_20250327_EN.pdf
C03Cell overvoltage.Défaut
Description

Individual cell overvoltage protection triggered.

Cause

One or more cells exceeded the per-cell upper voltage limit.

Correction recommandée

Restart the unit. if the error persists, contact the repair center.

Source:HE-GF-FLA-48500 Manual_20250327_EN.pdf
C04Cell undervoltage.Défaut
Description

Individual cell undervoltage protection triggered.

Cause

One or more cells dropped below the per-cell lower voltage limit.

Correction recommandée

Restart the unit. if the error persists, contact the repair center.

Source:HE-GF-FLA-48500 Manual_20250327_EN.pdf
C05Charge overcurrent.Défaut
Description

Charging current exceeded the allowable limit.

Cause

Charge current above recommended (≤200A continuous, 300A 15s peak).

Correction recommandée

Restart the unit. if the error persists, contact the repair center.

Source:HE-GF-FLA-48500 Manual_20250327_EN.pdf
C06Discharge overcurrent.Défaut
Description

Discharging current exceeded the allowable limit.

Cause

Discharge current above recommended (≤200A continuous, 300A 15s peak).

Correction recommandée

Restart the unit. if the error persists, contact the repair center.

Source:HE-GF-FLA-48500 Manual_20250327_EN.pdf
C07MOS overtemperature.Défaut
Description

MOSFET (BMS power switch) over-temperature protection.

Cause

1. The inner temperature is over the limitation. 2. Check whether the ambient temperature is too high.

Correction recommandée

Reduce ambient temperature / improve ventilation; restart the unit. if the error persists, return to repair center.

Source:HE-GF-FLA-48500 Manual_20250327_EN.pdf
C08MOS undertemperature.Défaut
Description

MOSFET (BMS power switch) under-temperature protection.

Cause

1. The internal temperature is lower than the limit range. 2. Check whether the ambient temperature is too low.

Correction recommandée

Raise ambient temperature into operating range (charging 0-55°C; discharging -20-55°C); restart the unit. if the error persists, return to repair center.

Source:HE-GF-FLA-48500 Manual_20250327_EN.pdf
C09Cell overtemperature.Défaut
Description

Battery cell over-temperature protection triggered.

Cause

Cell temperature exceeded upper limit (charging temperature range 0-55°C, discharging -20-55°C).

Correction recommandée

Restart the unit. if the error persists, contact the repair center.

Source:HE-GF-FLA-48500 Manual_20250327_EN.pdf
C10Cell undertemperature.Défaut
Description

Battery cell under-temperature protection triggered.

Cause

Cell temperature below lower limit.

Correction recommandée

Restart the unit. if the error persists, contact the repair center.

Source:HE-GF-FLA-48500 Manual_20250327_EN.pdf
C11Abnormal current sampling.Défaut
Description

Internal current measurement / sampling circuit abnormal.

Cause

Hardware/sensor abnormality in current sampling path.

Correction recommandée

Restart the unit. if the error persists, contact the repair center.

Source:HE-GF-FLA-48500 Manual_20250327_EN.pdf
C12Abnormal output impedance.Défaut
Description

Output impedance abnormal.

Cause

Abnormal impedance detected on output (possible bad connection, contactor or wiring issue).

Correction recommandée

Restart the unit. if the error persists, contact the repair center.

Source:HE-GF-FLA-48500 Manual_20250327_EN.pdf
C13Parallel failed.Défaut
Description

Parallel connection / parallel-mode start-up failed.

Cause

Parallel condition not satisfied (e.g. pack-to-pack voltage difference ≥3V, or wiring issue between paralleled units).

Correction recommandée

1. Please check if single unit is installed in parallel system. 2. if this error happens during parallel installation, please check wires connection. if they are connected correctly, please finish parallel installation first, and then Restart the unit. 3. if the problem remains, please contact your installer.

Source:HE-GF-FLA-48500 Manual_20250327_EN.pdf
C14Output loss.Défaut
Description

Output loss / no output detected.

Cause

Breaker open, blown fuse, or output path interrupted.

Correction recommandée

1. Please check whether the circuit breaker is closed; 2. Please check whether the fuse is normal; 3. Restart the unit. if the error persists, contact the repair center.

Source:HE-GF-FLA-48500 Manual_20250327_EN.pdf