Défaut

F43

Parallel CAN COMM abnormality.

6 Appareils signalant ce code
Apollo-5KLP1G01-MXSystème de stockage d’énergie↗ voir sur l’appareil
F43Parallel CAN COMM abnormality.Défaut
Description

Parallel CAN communication abnormality.

Cause

Parallel CAN COMM abnormality.

Correction recommandée

Test the parallel communication line, restart still have problems please contact the after-sales service.

Source:Apollo-5KLP1G01-All-in-one-ESS-User-Guide.pdf · page 44
F43Current feedback into the inverter is detected.Défaut
Description

Fault: Current feedback into the inverter is detected.

Cause

Reverse-connected L/N cables or improper sharing-cable wiring in parallel/three-phase systems.

Correction recommandée

1. Restart the inverter. 2. Check if L/N cables are not connected reversely in all inverters. 3. For parallel system in single phase, make sure the sharing cables are connected in all inverters. For supporting three-phase system, make sure the sharing cables are connected in the inverters in the same phase, and disconnected in the inverters in different phases. 4. if the problem remains, please contact your installer.

Source:felicitysolar IVEM 6048 Solar Inverter User Guide.pdf · page 38
F43Current feedback into the inverter is detected.Défaut
Description

Fault: Current feedback into the inverter is detected.

Cause

Reverse current feedback detected at the inverter.

Correction recommandée

1. Restart the inverter. 2. Check if L/N cables are not connected reversely in all inverters. 3. For parallel system in single phase, make sure the sharing cables are connected in all inverters. For supporting three-phase system, make sure the sharing cables are connected in the inverters in the same phase, and disconnected in the inverters in different phases. 4. if the problem remains, please contact your installer.

Source:IVEM8K-12K-II_compressed.pdf · page 45
F43Current feedback into the inverter is detected.Défaut
Description

Current feedback into the inverter is detected.

Cause

Reverse-connected L/N cables, or sharing cables not connected/connected across phases in three-phase setup.

Correction recommandée

1. Restart the inverter. 2. Check if L/N cables are not connected reversely in all inverters. 3. For parallel system in single phase, make sure the sharing cables are connected in all inverters. For supporting three-phase system, make sure the sharing cables are connected in the inverters in the same phase, and disconnected in the inverters in different phases. 4. if the problem remains, please contact your installer.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 39
F43CAN data loss.Défaut
Description

Loss of CAN bus communication data.

Correction recommandée

Check if communication cables are connected well and restart the inverter. if the problem remains, please contact your installer.

Source:T-REX-10KHP3G01-Inverter-User-Guide.pdf · page 29
F43CAN data loss.Défaut
Description

CAN data loss.

Cause

Communication cables not connected well.

Correction recommandée

1. Check if communication cables are connected well and restart the inverter. 2. if the problem remains, please contact your installer.

Source:T-REX-10KLP3G01-Inverter-User-Guide.pdf · page 29

Compilé à partir des manuels utilisateur officiels FelicityESS. Consultez toujours le manuel de votre appareil et un technicien qualifié avant toute réparation.