Felicity Solar Inverter Datasheet — IVPM10048
Off-grid inverter-charger giving 8 kW (10 kVA apparent) of pure sine power at 220 V, with an 80 A utility charger and a 120 A solar charger for one 48 V bank.
SKU: IVPM10048 | Last Updated: 2026-08-07
⚡Electrical Specifications
| AC Output Voltage | 220 V |
| AC Wiring Mode | L+N+PE |
| Backup Rated Output Power | 8 kW |
| Battery Inputs | 1 |
| Battery Type | AGM, Flooded, Li-Ion, Self-Defined |
| Battery Voltage Range | 42-63 V |
| Bulk Charging Voltage | 57.6 V |
| Charge Algorithm | Three-Stage: Boost CC, Boost CV, Float |
| Float Charging Voltage | 54.4 V |
| High DC Input Recovery Voltage | 62 V |
| High Frequency Disconnect | 65 Hz |
| High Frequency Reconnect | 63 Hz |
| High Line Disconnect Voltage | 280 V |
| High Line Reconnect Voltage | 270 V |
| Input Voltage Range | 90-280 V |
| Input Voltage Range (Appliance Mode) | 90-280 V |
| Input Voltage Range (UPS Mode) | 170-280 V |
| Input Voltage Waveform | Sinusoidal (utility or generator) |
| Line Mode Efficiency | 95 % |
| Line Mode Output Waveform | Same As Input Waveform |
| Low DC Shutdown (<50% Load) | 43 V |
| Low DC Shutdown (>50% Load) | 42 V |
| Low Frequency Disconnect | 40 Hz |
| Low Frequency Reconnect | 42 Hz |
| Low Line Disconnect (Appliance Mode) | 90 V |
| Low Line Disconnect (UPS Mode) | 170 V |
| Low Line Reconnect (Appliance Mode) | 100 V |
| Low Line Reconnect (UPS Mode) | 180 V |
| Low-Battery Recovery (<50% Load) | 47 V |
| Low-Battery Recovery (>50% Load) | 46 V |
| MPPT Trackers | 1 |
| MPPT Voltage Range | 65-145 V |
| Max AC Charge Current | 80 A |
| Max AC Input Voltage | 280 V |
| Max AC Pass-Through Current | 63 A |
| Max Charging Current | 80 A |
| Max Charging Voltage | 61.0 V |
| Max Efficiency | 90 % |
| Max PV Input Power | 6.6 kW |
| Max PV Voltage | 170 V |
| Max Solar Charging Current | 120 A |
| Motor Start Capable | Yes |
| Nominal AC Input Voltage | 220 V |
| Nominal DC Input Voltage | 48 V |
| Nominal Input Frequency | 50/60 Hz |
| Output Frequency | 50/60 Hz |
| Output Short-Circuit Protection | Yes |
| Output Voltage Regulation | 5 % |
| Output Voltage Waveform | Pure Sine Wave |
| Overload Protection | Air Switch Protection |
| Overload Trip Time (>105% Load) | 10 s |
| Overload Trip Time (>150% Load) | 5 s |
| PV Working Voltage Range | 65-145 V |
| Pass-Through Without Battery | No |
| Phase | Single Phase |
| Protection | Over Charge Protection, Over Discharge Protection, Overload Protection, Output Short Circuit Protection, Over Temperature Protection |
| Rated Apparent Output Power | 10 kVA |
| Rated Output Power | 8 kW |
| Short-Circuit Protection (Line Mode) | Air Switch Protection |
| Start-Up Voltage | 46 V |
| Strings per MPPT | 1 |
| Surge Rating | 2*rated (5s) |
| Transfer Time | 15 ms |
🔧Mechanical Specifications
| BMS Communication | RS485 |
| Communication Interface | RS232 |
| Display | LCD, LED |
| Gross Weight | 67.7 kg |
| Net Weight | 55.4 kg |
| Package Dimensions | 670 x 470 x 355 mm |
| Parallel Capability | 6 (battery required) |
| Topology | Low-Frequency (transformer-based) |
🌡️Environmental Specifications
| Cooling | Intelligent Air Cooling |
| IP Rating | IP21 |
| Operating Temperature Range | 0-40 °C |
| Storage Temperature | -15 to 60 °C |
📏Dimensions
Width
Height
Depth
Weight