Felicity Solar Inverter Datasheet — IVGM125KHP3G1
Ten MPPT trackers feed the IVGM125KHP3G1 with 250 kW of array, which it turns into 125 kW of three-phase output, 137 kVA at its apparent-power ceiling and 198.6 A of current, drawn against a 160-950 V LFP bank on two inputs.
SKU: IVGM125KHP3G1 | Last Updated: 2026-08-17
⚡Electrical Specifications
| AC Output Line Voltage | 380-400 V |
| AC Output Voltage | 220-230 V |
| AC Rated Output Current | 181.2 A |
| AC Wiring Mode | 3L+N+PE |
| Backup Rated Output Power | 125 kW |
| Battery Inputs | 2 |
| Battery Type | LFP |
| Battery Voltage Range | 160-950 V |
| Charge Algorithm | Self-Adaption to BMS |
| Grid Frequency Range (50 Hz) | 45-55 Hz |
| Grid Frequency Range (60 Hz) | 55-65 Hz |
| Grid Regulation | IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25, G99, VDE-AR-N 4110 |
| Ground Fault Current Monitoring | Yes |
| Input Voltage Range | 184-264.5 V |
| MPPT Full-Load Voltage Range | 555-950 V |
| MPPT Trackers | 10 |
| MPPT Voltage Range | 150-950 V |
| Max AC Input Current | 198.6 A |
| Max AC Pass-Through Current | 270 A |
| Max Apparent Power | 137 kVA |
| Max Charging Current | 120+120 A |
| Max Discharging Current | 120+120 A |
| Max Efficiency | 97.6 % |
| Max Output Current | 198.6 A |
| Max Output Overcurrent Protection | 270 A |
| Max PV Input Current | 45+45+45+45+45+45+45+45+45+45 A |
| Max PV Input Power | 250 kW |
| Max PV Voltage | 1000 V |
| Max Short-Circuit Current | 68+68+68+68+68+68+68+68+68+68 A |
| Nominal AC Input Line Voltage | 380-400 V |
| Nominal AC Input Voltage | 220-230 V |
| Nominal Input Frequency | 50/60 Hz |
| Output Frequency | 50/60 Hz |
| Output Short-Circuit Protection | Yes |
| Overload Protection | Yes |
| Overvoltage Category (AC) | III |
| Overvoltage Category (DC) | II |
| Phase | Three Phase |
| Power Factor Adjustment Range | 0.8 leading to 0.8 lagging |
| Protection | PV Input Lightning Protection, PV String Input Reverse Polarity Protection, Battery Input Lightning Protection, Battery Input Reverse Polarity Protection, DC Component Detection, Insulation Resistor Detection, Residual Current Monitoring Unit, Arc Fault Monitoring (optional), Output Over Current Protection, Output Shorted Protection, Output Over Voltage Protection, Remaining Current (RCD) Monitoring, Overheat Protection, Anti-islanding Protection, AC Output Lightning Protection |
| Rated Apparent Output Power | 125 kVA |
| Rated Output Power | 125 kW |
| Rated PV Input Voltage | 600 V |
| Start-Up Voltage | 180 V |
| Strings per MPPT | 2 |
| Surge Protection Level (AC) | III |
| Surge Protection Level (DC) | III |
| Surge Rating | 1.5*rated (10s) |
| Total Harmonic Distortion | <3 % |
| Transfer Time | 0 ms |
🔧Mechanical Specifications
| BMS Communication | RS485, CAN |
| Communication Interface | RS232, RS485 |
| Display | LCD, LED |
| Gross Weight | 198 kg |
| Installation Style | Wall-Mounted |
| Monitoring Module | WiFi/Bluetooth/4G/LAN (optional) |
| Net Weight | 155.5 kg |
| Package Dimensions | 1410 x 960 x 646 mm |
| Parallel Capability | 12 |
| Safety Standard | IEC/EN 62109-1, IEC/EN 62109-2 |
| Topology | Non-Isolated |
🌡️Environmental Specifications
| Cooling | Smart Cooling |
| IP Rating | IP66 |
| Operating Altitude | 4000 m |
| Operating Temperature Range | -40 to 60 (>45 derating) °C |
| Relative Humidity | 0-100 (non-condensing) % |
📏Dimensions
Width
Height
Depth
Weight
✅Certifications
IEC 62109-1EN 62109-1IEC 62109-2EN 62109-2