| Parameter | IVPS7548 |
|---|---|
| Performance & Electrical | |
| AC Output Voltage | 220 V |
| AC Wiring Mode | L+N+PE |
| Backup Rated Output Power | 6 kW |
| Battery Inputs | 1 |
| Battery Type | AGM, Flooded, Li-Ion, Self-Defined |
| Battery Voltage Range | 42-63 V |
| Bulk Charging Voltage | 57.6 V |
| Charge Algorithm | Three-Stage: Boost CC, Boost CV, Float |
| Float Charging Voltage | 54.4 V |
| High DC Input Recovery Voltage | 62 V |
| High Frequency Disconnect | 65 Hz |
| High Frequency Reconnect | 63 Hz |
| High Line Disconnect Voltage | 280 V |
| High Line Reconnect Voltage | 270 V |
| Input Voltage Range | 90-280 V |
| Input Voltage Range (Appliance Mode) | 90-280 V |
| Input Voltage Range (UPS Mode) | 170-280 V |
| Input Voltage Waveform | Sinusoidal (utility or generator) |
| Line Mode Efficiency | >95% |
| Line Mode Output Waveform | Same As Input Waveform |
| Low DC Shutdown (>50% Load) | 42 V |
| Low Frequency Disconnect | 40 Hz |
| Low Frequency Reconnect | 42 Hz |
| Low Line Disconnect (Appliance Mode) | 90 V |
| Low Line Disconnect (UPS Mode) | 170 V |
| Low Line Reconnect (Appliance Mode) | 100 V |
| Low Line Reconnect (UPS Mode) | 180 V |
| Low-Battery Recovery (>50% Load) | 46 V |
| Max AC Charge Current | 60 A |
| Max AC Input Voltage | 280 V |
| Max AC Pass-Through Current | 63 A |
| Max Charging Current | 60 A |
| Max Charging Voltage | 61.0 V |
| Max Efficiency | 90% |
| Motor Start Capable | Yes |
| Nominal AC Input Voltage | 220 V |
| Nominal DC Input Voltage | 48 V |
| Nominal Input Frequency | 50/60 Hz |
| Output Frequency | 50/60 Hz |
| Output Short-Circuit Protection | Yes |
| Output Voltage Regulation | 5% |
| Output Voltage Waveform | Pure Sine Wave |
| Overload Protection | Air Switch Protection |
| Overload Trip Time (>105% Load) | 10 s |
| Overload Trip Time (>150% Load) | 5 s |
| Pass-Through Without Battery | No |
| Phase | Single Phase |
| Protection | Over Charge Protection, Over Discharge Protection, Overload Protection, Output Short Circuit Protection, Over Temperature Protection |
| Rated Apparent Output Power | 7.5 kVA |
| Rated Output Power | 6 kW |
| Short-Circuit Protection (Line Mode) | Air Switch Protection |
| Start-Up Voltage | 46 V |
| Surge Rating | 2*rated (5s) |
| Transfer Time | 15 ms |
| Build & Interfaces | |
| BMS Communication | RS485 |
| Communication Interface | RS232 |
| Display | LCD, LED |
| Gross Weight | 32.5 kg |
| Net Weight | 29.1 kg |
| Package Dimensions | 607 x 540 x 290 mm |
| Parallel Capability | 6 |
| Topology | Low-Frequency (transformer-based) |
| Operating Environment | |
| Cooling | Intelligent Air Cooling |
| IP Rating | IP21 |
| Operating Temperature Range | 0-40 °C |
| Storage Temperature | -15 to 60 °C |
Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.
Availability & grid compliance in the UAE
| Market | UAE |
|---|---|
| Grid authority / regulator | DEWA, ADDC, SEWA |
| Quotation currency | AED |
| Support hours timezone | Asia/Dubai |
| Main cities | Dubai, Abu Dhabi, Sharjah, Ajman, Ras Al Khaimah |
Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in the UAE that rests with the local authorities (DEWA, ADDC, SEWA). Confirm the grid code, import requirements and any local certification with them, or with us, before you order.
Key Features & Technical Highlights
- 6 kW rated output and 7.5 kVA apparent power, single phase at 220 V, 50/60 Hz
- 48 V battery bank with a 42-63 V operating window and charging up to 60 A
- Low-frequency design carries 2x rated power for 5 seconds to start motor loads
- Two AC input windows: 170-280 V UPS mode or 90-280 V appliance mode, 15 ms transfer
- Three-stage charging at 57.6 V bulk and 54.4 V float for AGM, flooded, Li-Ion and self-defined banks
- Up to 6 units in parallel, 90% peak efficiency and over 95% in line mode
Frequently Asked Questions
What is the rated output power of the Felicity Solar IVPS7548?
It is rated 6 kW of real power and 7.5 kVA apparent, single phase at 220 V and 50/60 Hz, with a pure sine wave output. The low-frequency design carries twice rated power for 5 seconds, so motor loads such as pumps and compressors start without tripping the inverter.
Which battery bank does the IVPS7548 need?
A 48 V bank. It operates from 42 V to 63 V, starts up at 46 V, and charges at up to 60 A through a three-stage boost CC, boost CV and float profile at 57.6 V bulk, 54.4 V float and 61.0 V maximum. AGM, flooded, lithium-ion and self-defined types are supported, with RS485 for BMS communication.
How does the IVPS7548 handle a weak grid or a generator?
You choose the input window. UPS mode accepts 170-280 V for sensitive electronics and appliance mode accepts 90-280 V on unstable supply, and transfer takes 15 ms in either case. It disconnects below 40 Hz or above 65 Hz, and it will not pass utility power through unless a battery is connected.
What are the dimensions, weight and installation conditions?
The unit measures 494 x 420 x 195 mm and weighs 29.1 kg net, 32.5 kg gross, packed at 607 x 540 x 290 mm. It is rated IP21, so it mounts indoors in a protected location, and it runs from 0 to 40 °C with intelligent air cooling, an LCD and LED indicators.