Défaut

F46

Inconsistency in parallel versions.

7 Appareils signalant ce code
Apollo-5KLP1G01-MXSystème de stockage d’énergie↗ voir sur l’appareil
F46Inconsistency in parallel versions.Défaut
Description

Inconsistency in firmware versions across paralleled inverters.

Cause

Inconsistency in parallel versions.

Correction recommandée

1. Update all inverter firmware to the same version. 2. Check the version of each inverter via the LCD settings to ensure that the CPU versions are the same. if it is not the same, please contact after-sales personnel to update the firmware. 3. After updating, if the problem still exists, please contact after-sales.

Source:Apollo-5KLP1G01-All-in-one-ESS-User-Guide.pdf · page 44
F46AC output mode setting is different.Défaut
Description

Fault: AC output mode setting is different.

Cause

Inconsistent AC output mode (program 28) settings across paralleled inverters.

Correction recommandée

1. Switch off the inverter and check LCD setting program 28. 2. For parallel system in single phase, make sure no 3P1, 3P2 or 3P3 is set on program 28. For supporting three-phase system, make sure no "PAL" is set on program 28. 3. if the problem remains, please contact your installer.

Source:felicitysolar IVEM 6048 Solar Inverter User Guide.pdf · page 39
F46AC output mode setting is different.Défaut
Description

Fault: AC output mode setting is different.

Cause

AC output mode setting (LCD program 28) does not match across parallel units.

Correction recommandée

1. Switch off the inverter and check LCD setting program 28. 2. For parallel system in single phase, make sure no 3P1, 3P2 or 3P3 is set on program 28. For supporting three-phase system, make sure no 'PAL' is set on program 28. 3. if the problem remains, please contact your installer.

Source:IVEM8K-12K-II_compressed.pdf · page 45
F46AC output mode setting is different.Défaut
Description

AC output mode setting is different.

Cause

Inconsistent AC output mode (program 28) settings across inverters.

Correction recommandée

1. Switch off the inverter and check LCD setting program 28. 2. For parallel system in single phase, make sure no 3P1, 3P2 or 3P3 is set on program 28. For supporting three-phase system, make sure no "PAL" is set on program 28. 3. if the problem remains, please contact your installer.

Source:FelicitySolar IVEM8048-LV Single Phase Hybrid Inverter User Guide.pdf · page 39
F46The firmware version of each inverter is not the same.Défaut
Description

Inverters in parallel have different firmware versions.

Correction recommandée

Update all inverter firmware to the same version. Check the version of each inverter via LCD setting and make sure the CPU versions are same. if not, please contact your installer to provide the firmware to update. After updating, if the problem still remains, please contact your installer.

Source:T-REX-10KHP3G01-Inverter-User-Guide.pdf · page 29
F46The firmware version of each inverter is not the same.Défaut
Description

The firmware version of each inverter is not the same.

Cause

Inverter firmware versions are mismatched across parallel units.

Correction recommandée

1. Update all inverter firmware to the same version. 2. Check the version of each inverter via LCD setting and make sure the CPU versions are same. if not, please contact your installer to provide the firmware to update. 3. After updating, if the problem still remains, please contact your installer.

Source:T-REX-10KLP3G01-Inverter-User-Guide.pdf · page 29
F46Inverter software overcurrent fault.Défaut
Description

Inverter current is too high, check the given power and load size.

Source:T-REX-50KHP3G01-user-manual-.pdf · page 47

Compilé à partir des manuels utilisateur officiels FelicityESS. Consultez toujours le manuel de votre appareil et un technicien qualifié avant toute réparation.