Felicity Solar Inverter Datasheet — IVGM10KLP3G1

The Felicity Solar IVGM10KLP3G1 is a 10 kW three-phase hybrid solar inverter rated 10 kVA at 380-400 V, with 97.6% peak efficiency and 15 kW of PV input. Two MPPT trackers and a 40-60 V battery port charging at up to 210 A make it a full grid-tied, off-grid and UPS solution.

SKU: IVGM10KLP3G1 | Last Updated: 2026-03-23

⚡Electrical Specifications

AC Output Line Voltage380-400 V
AC Output Voltage220-230 V
AC Rated Output Current14.5 A
AC Wiring Mode3L+N+PE
Backup Rated Output Power10 kW
Battery Inputs2
Battery TypeLead-Acid, Li-Ion
Battery Voltage Range40-60 V
Charge AlgorithmSelf-Adaption to BMS
DC SwitchYes
Grid Frequency Range (50 Hz)45-55 Hz
Grid Frequency Range (60 Hz)55-65 Hz
Grid RegulationNRS 097-2-1, VDE4105, EN50549-1, AS 4777.2, GB/T 34120, GB/T 34133, GB/T 34129
Ground Fault Current MonitoringYes
Input Voltage Range184-264.5 V
MPPT Efficiency99.9 %
MPPT Full-Load Voltage Range289-800 V
MPPT Trackers2
MPPT Voltage Range160-650 V
Max AC Input Current16 A
Max AC Pass-Through Current70 A
Max Apparent Power11 kVA
Max Charging Current210 A
Max Discharging Current210 A
Max Efficiency97.6 %
Max Output Current16 A
Max Output Overcurrent Protection65 A
Max PV Input Current26+26 A
Max PV Input Power15 kW
Max PV Voltage800 V
Max Short-Circuit Current39+39 A
Nominal AC Input Line Voltage380-400 V
Nominal AC Input Voltage220-230 V
Nominal Input Frequency50/60 Hz
Output Frequency50/60 Hz
Output Short-Circuit ProtectionYes
Overload ProtectionYes
Pass-Through Without BatteryYes
PhaseThree Phase
Power Factor Adjustment Range0.8 leading to 0.8 lagging
ProtectionDC Polarity Reverse Connection Protection, AC Output Overcurrent Protection, AC Output Overvoltage Protection, AC Output Short Circuit Protection, Thermal Protection, DC Terminal Insulation Impedance Monitoring, DC Component Monitoring, Ground Fault Current Monitoring, Arc Fault Circuit Interrupter (AFCI), Power Network Monitoring, Island Protection Monitoring, Earth Fault Detection, DC Input Switch, Overvoltage Load Drop Protection, Residual Current (RCD) Detection
Rated Apparent Output Power10 kVA
Rated Output Power10 kW
Rated PV Input Voltage550 V
Start-Up Voltage160 V
Strings per MPPT2+2
Surge Protection Level (AC)II
Surge Protection Level (DC)II
Surge Rating2*rated (10s)
Total Harmonic Distortion<3 %
Transfer Time20 ms

🔧Mechanical Specifications

BMS CommunicationRS485, CAN
Communication InterfaceRS232, RS485
DisplayLCD Touch Screen
Gross Weight60.2 kg
Installation StyleWall-Mounted
Monitoring ModuleWiFi/4G
Net Weight48.7 kg
Package Dimensions889 x 566 x 397 mm
Parallel Capability10
Safety StandardIEC/EN 62109-1, IEC/EN 62109-2
TopologyNon-Isolated

🌡️Environmental Specifications

CoolingSmart Cooling
IP RatingIP65
Operating Altitude2000 m
Operating Temperature Range-25 to 60 (>45 derating) °C

📏Dimensions

Width
Height
Depth
Weight

✅Certifications

IEC 62109-1EN 62109-1IEC 62109-2EN 62109-2