Felicity Solar Inverter Datasheet — IVCM3224P1G2
A single-phase 24 V inverter, the IVCM3224P1G2 pairs a 3.2 kVA / 3.2 kW rating with a 3.2 kW backup output, a 1.6 kW PV input capped at 105 V, and 28.2 V boost / 27 V float charging for AGM, Flooded, Li-Ion and self-defined banks.
SKU: IVCM3224P1G2 | Last Updated: 2026-07-23
⚡Electrical Specifications
| AC Output Voltage | 230 V |
| AC Wiring Mode | L+N+PE |
| Backup Rated Output Power | 3.2 kW |
| Battery Inputs | 1 |
| Battery Type | AGM, Flooded, Li-Ion, Self-Defined |
| Battery Voltage Range | 21-31.5 V |
| Bulk Charging Voltage | 28.2 V |
| Charge Algorithm | Three-Stage: Boost CC, Boost CV, Float |
| Float Charging Voltage | 27 V |
| High DC Input Recovery Voltage | 29 V |
| High Frequency Disconnect | 65 Hz |
| High Frequency Reconnect | 63 Hz |
| High Line Disconnect Voltage | 280 V |
| High Line Reconnect Voltage | 270 V |
| Input Voltage Range | 90-280 V |
| Input Voltage Range (Appliance Mode) | 90-280 V |
| Input Voltage Range (UPS Mode) | 170-280 V |
| Input Voltage Waveform | Sinusoidal (utility or generator) |
| Line Mode Output Waveform | Same As Input Waveform |
| Low DC Shutdown (<50% Load) | 20.4 V |
| Low DC Shutdown (>50% Load) | 19.2 V |
| Low Frequency Disconnect | 40 Hz |
| Low Frequency Reconnect | 42 Hz |
| Low Line Disconnect (Appliance Mode) | 90 V |
| Low Line Disconnect (UPS Mode) | 170 V |
| Low Line Reconnect (Appliance Mode) | 100 V |
| Low Line Reconnect (UPS Mode) | 180 V |
| Low-Battery Recovery (<50% Load) | 22.4 V |
| Low-Battery Recovery (>50% Load) | 21.2 V |
| MPPT Efficiency | 99 % |
| MPPT Trackers | 1 |
| MPPT Voltage Range | 30-90 V |
| Max AC Charge Current | 120 A |
| Max AC Input Voltage | 280 V |
| Max AC Pass-Through Current | 25 A |
| Max Charging Current | 120 A |
| Max Charging Voltage | 30 V |
| Max Discharging Current | 135 A |
| Max Efficiency | 93 % |
| Max Inverter/Rectifier Current | 25 A |
| Max PV Input Power | 1.6 kW |
| Max PV Voltage | 105 V |
| Max Solar Charging Current | 60 A |
| Motor Start Capable | Yes |
| Nominal AC Input Voltage | 230 V |
| Nominal DC Input Voltage | 24 V |
| Nominal Input Frequency | 50/60 Hz |
| Output Frequency | 50/60 Hz |
| Output Short-Circuit Protection | Yes |
| Output Voltage Waveform | Pure Sine Wave |
| Overload Protection | Yes |
| Overload Trip Time (>105% Load) | 10 s |
| Overload Trip Time (>150% Load) | 5 s |
| Pass-Through Without Battery | Yes |
| Phase | Single Phase |
| Protection | Over Charge Protection, Overload Protection, Output Short Circuit Protection, Over Temperature Protection |
| Rated Apparent Output Power | 3.2 kVA |
| Rated Output Power | 3.2 kW |
| Short-Circuit Protection (Battery Mode) | Electronic Circuit |
| Start-Up Voltage | 21.0 V |
| Strings per MPPT | 1 |
| Transfer Time (Appliance Mode) | 20 ms |
| Transfer Time (UPS Mode) | 4 ms |
🔧Mechanical Specifications
| BMS Communication | RS485, CAN |
| Communication Interface | RS485, CAN |
| Display | LCD, LED |
| Gross Weight | 8.2 kg |
| Installation Style | Wall-Mounted |
| Monitoring Module | Built-In WiFi |
| Net Weight | 6.5 kg |
| Package Dimensions | 438 x 358 x 202 mm |
| Parallel Capability | 6 |
| Topology | High-Frequency |
🌡️Environmental Specifications
| Cooling | Intelligent Air Cooling |
| IP Rating | IP21 |
| Operating Temperature Range | -10 to 55 °C |
| Storage Temperature | -15 to 60 °C |
📏Dimensions
Width
Height
Depth
Weight