Felicity Solar Lithium Batteries FLS-ES232LC-G
Five LiFePO4 280Ah modules wired as one 1P260S string give this 3000 kg cabinet 232 kWh at 832 V, with liquid cooling, a touch screen and LAN, Modbus TCP.
Models and prices
- FLS-ES232LC-GAED 104,400incl. VAT
Technical Specifications
| Parameter | FLS-ES232LC-G |
|---|---|
| Performance & Electrical | |
| AC Connection Type | 3P+N+PE |
| AC Nominal Frequency | 50/60 Hz |
| AC Nominal Power | 100 kW |
| AC Nominal Voltage | 400 V |
| AC Voltage Range | 340-460 V |
| Battery Type | LiFePO4 |
| Charge/Discharge Rate | 0.5P |
| Cut-Off Voltage | 650 V |
| Cycle Life | ≥6000 |
| Depth of Discharge | 5-95% |
| Max Charging Voltage | 949 V |
| Max System Efficiency | 87% |
| Nominal Capacity | 280 Ah |
| Nominal Energy | 232 kWh |
| Nominal Voltage | 832 V |
| Operating Voltage | 650-949 V |
| Power Factor Range | -0.99 to 0.99 |
| Protection | Breaker, Fuse |
| Recommended Charge/Discharge Current | 140 A |
| System Nominal Energy | 232.96 kWh |
| System Nominal Voltage | 832 V |
| System Operating Voltage | 650-949 V |
| Build & Interfaces | |
| Battery Modules | 5 |
| Cell Type | LiFePO4 280Ah |
| Communication | LAN, Modbus TCP |
| Display Type | Touch Screen |
| System Battery Configuration | 1P260S |
| Operating Environment | |
| Charging Temperature Range | -20 to 55 °C |
| Discharging Temperature Range | -20 to 55 °C |
| Fire Suppression System | Aerosol fire extinguishing equipment, Water fire protection |
| Humidity Range | 5-95% |
| Noise Level | <75 dB |
| Operating Altitude | <2000 m |
| Protection Degree | IP54 |
| Storage Temperature Range | 20-30 °C |
| Temperature Control Method | Liquid cooling |
Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.
Availability & grid compliance in the UAE
| Market | UAE |
|---|---|
| Grid authority / regulator | DEWA, ADDC, SEWA |
| Quotation currency | AED |
| Support hours timezone | Asia/Dubai |
| Main cities | Dubai, Abu Dhabi, Sharjah, Ajman, Ras Al Khaimah |
Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in the UAE that rests with the local authorities (DEWA, ADDC, SEWA). Confirm the grid code, import requirements and any local certification with them, or with us, before you order.
Key Features & Technical Highlights
- 232 kWh of nominal energy at 832 V, from five LiFePO4 280Ah modules wired as one 1P260S string
- 100 kW AC nominal power on a 400 V 3P+N+PE connection at 50/60 Hz, power factor adjustable from -0.99 to 0.99
- Liquid cooling across a -20 to 55 °C charging and discharging range, at under 75 dB
- ≥6000 cycles over a 5-95% depth of discharge, at a recommended 140 A (0.5P) charge and discharge current
- 87% maximum system efficiency between the 650 V cut-off and the 949 V maximum charging voltage
- IP54 enclosure with aerosol fire extinguishing equipment, water fire protection, breaker and fuse
Frequently Asked Questions
How much energy and power does the FLS-ES232LC-G deliver?
232 kWh at 832 V nominal — 232.96 kWh stated as system nominal energy — with 100 kW of AC nominal power on a 400 V 3P+N+PE connection at 50/60 Hz, and a power factor adjustable from -0.99 to 0.99.
Are the 232 kWh, 832 V and 3000 kg per module or for the whole cabinet?
3000 kg, 232 kWh and 832 V are the complete cabinet, which holds five battery modules wired as a single 1P260S string. The 280 Ah nominal capacity is the string's and is shared by every module because they sit in series, and 1400 × 1400 × 2200 mm is the assembled cabinet's envelope, not one module's.
What are the charging limits and cycle life of the FLS-ES232LC-G?
≥6000 cycles over a 5-95% depth of discharge, charged and discharged at a recommended 140 A — a 0.5P rate — between a 650 V cut-off and a 949 V maximum charging voltage, for a maximum system efficiency of 87%.
Where can the FLS-ES232LC-G be installed and how is it monitored?
IP54 with liquid cooling, rated for charging and discharging from -20 to 55 °C, 5-95% humidity, below 2000 m altitude and under 75 dB, with storage at 20-30 °C. Monitoring is by touch screen over LAN and Modbus TCP, and aerosol fire extinguishing equipment, water fire protection, breaker and fuse are fitted. Warranty: 2 Years.