Felicity IVGM5KLP1G1
The Felicity IVGM5KLP1G1 is a hybrid inverter with a 360V nominal bus, 5000VA/5000W rated output.
Technical Specifications
| Parameter | IVGM5KLP1G1 |
|---|---|
| Battery Data | |
| Battery Voltage Range | 40V~60V |
| Max Charge/Discharge Current | 100A/100A |
| Max Charge Current | 100A |
| Additional Specifications | |
| Max. charging and discharging power | 5000W |
| Max. Input Current | 40A |
| Nominal Input Voltage | 230Vac |
| Nominal Grid Frequency | 50/60Hz |
| Displacement Power Factor | 0.8(Leading) to 0.8(Lagging) |
| PV String Input Data | |
| Max Recommended PV Power | 6500W (3500W for Single PV) |
| Max PV / DC Voltage | 550V Start Oltage 130V |
| PV Operating Voltage Range | 90V-550V |
| MPPT Voltage Range | 100V-500V |
| MPPT Voltage Range at Full Load | 220V-500V |
| Nominal DC Voltage | 360V |
| Max PV Short-Circuit Current | 18A/18A |
| Number of MPP Trackers | 2/1 |
| Electrical / AC Output Data | |
| Max. AC Output Power | 5000W |
| Rated AC Output Current | 21.7A |
| Max AC Output Current | 30A |
| Max. Continuous AC Passthrough | 40A |
| Power Factor | >0.99 |
| THD / THDi | <3% |
| Rated Apparent Power | 5000VA/5000W |
| AC Output Voltage | 230Vac |
| Output Frequency | 50/60Hz |
| Communication | |
| BMS Communication | CAN/RS485 |
| Protection Features | |
| Safety / EMC Standards | IEC 62109-1/-2 EMC IEC/EN 61000-6-1/2/3/4 EN/IEC 61000-3-11/12 |
| IP Rating | IP65 |
| Mechanical Data | |
| Installation / Mounting | Wall-mounted |
| Net Weight | 32.4KG |
| Gross Weight | 39.1KG |
| Dimensions (W×H×D) | 530*493*228MM |
| Package Dimensions | 632*570*315MM ME |
| Cooling | Nature |
| Operating Conditions | |
| Operating Temperature | -25°C~60°C, -45°C Derating |
Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.
Availability & grid compliance in Yemen
| Market | Yemen |
| Grid authority / regulator | Public Electricity Corporation (PEC), Ministry of Electricity and Energy |
| Quotation currency | YER |
| Support hours timezone | Asia/Aden |
| Delivery & installation coverage | Sana'a, Aden, Taiz, Al Hudaydah, Mukalla |
Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in Yemen that is Public Electricity Corporation (PEC), Ministry of Electricity and Energy. Confirm the grid code, import requirements and any local certification with them, or with us, before you order.