Felicity MJS Solar Solutions

Felicity IVPS5048

Discover Felicity Solar's IVPS/IVPM Series Inverters with 2500VA/2000W output, 220Vac voltage, and 12V DC input for efficient energy conversion.

Models Covered: IVPS5048

Manufacturer: Shenzhen Felicity Solar Technology Co., Ltd.

Application: The Felicity Solar IVPS/IVPM Series Inverters are designed to deliver reliable and efficient power conversion. With a rated output of 2500VA/2000W and a nominal output voltage of 220Vac, these inverters are ideal for various energy applications. Their sinusoidal input voltage waveform ensures smooth and stable operation.

Technical Specifications

Technical Specifications
Parameter IVPS5048
Additional Specifications
Capable of Starting Electric Yes
Input Voltage Range 90-280Vac
Nominal Input Voltage 220Vac
Low Line Re-connect AC Input Range 180±7Vac (UPS) / 100±7Vac (APL)
High Line Re-connect 270±7Vac
Nominal Input Frequency 50Hz/60Hz
Low Line Frequency Disconnect 40±1Hz
Low Line Frequency Re-connect 42±1Hz
High Line Frequency Disconnect 65±1Hz
High Line Frequency Re-connect 63±1Hz
Pass Through Without Battery No
Capable of Starting Electric Motor Yes
Output Short Circuit Protection Yes
Electrical Data
Efficiency (Line mode) ≥95% (rated R load, battery fully charged)
Max AC Input Voltage 280Vrms
Max Bypass Overload Current AC 63A
Over-Charge Protection Yes
Electrical Characteristics
Over-Load Protection (SMPS load) Air switch protection
Input Voltage Waveform Sinusoidal (utility or generator)
Low Line Disconnect 170±7Vac (UPS) / 90±7Vac (APL)
High Line Disconnect 280±7Vac
Transfer Time (AC to DC) 15ms (typical)
Transfer Time (DC to AC) 15ms (typical)
Input Voltage Range (utility charge) 90~280Vac
Max Charge Current 50A
Charge Current Regulation 0A~50A
Charger Short Circuit AC 63A
Output Voltage Waveform Pure sine wave
Over-Load Protection 5s@≥150% load; 10s@105%~150% load SMPS load
Surge Rating 10000VA for 5 seconds
Cold Start Voltage 46V
Low Battery Recovery 47V (load < 50%) / 46V (load ≥ 50%)
Low DC Input Shut-down 43V (load < 50%) / 42V (load ≥ 50%)
High DC Input Recovery 62±0.4V
Boost Charging Voltage (AGM) 57.6V
Float Charging Voltage (AGM) 54.4V
Boost Charging Voltage (Flooded) 58.4V
Float Charging Voltage (Flooded) 55.2V
Self-Defined Charging Voltage (max) 61.0V
AC Output
Rated Output Power (VA) 5000VA
Rated Output Power (W) 4000W
Nominal Output Voltage 220Vac±5%
Nominal Output Frequency (Hz) 50±0.3Hz / 60±0.3Hz (adjustable)
Output Voltage Regulation ±5%rms
Peak Efficiency 90%
DC Input
Nominal DC Input Voltage 48V
Battery Charging
Max Charging Current (Utility + Solar) 170A | 180A | 200A
Mechanical Data
Package Dimension 607x540x290mm
Operating Conditions
Operating temperature 0°C~40°C
Storage Temperature -15°C~60°C

Figures are measured at the test conditions the manufacturer’s datasheet states. A dash means the manufacturer publishes no figure for that model.

Availability & grid compliance in Yemen

Market Yemen
Grid authority / regulator Public Electricity Corporation (PEC), Ministry of Electricity and Energy
Quotation currency YER
Support hours timezone Asia/Aden
Delivery & installation coverage Sana'a, Aden, Taiz, Al Hudaydah, Mukalla

Figures on this page are the manufacturer's own, measured at the test conditions the datasheet states — they do not change by country. What changes is the approval that has to be met before the unit is energised: in Yemen that is Public Electricity Corporation (PEC), Ministry of Electricity and Energy. Confirm the grid code, import requirements and any local certification with them, or with us, before you order.

Key Features & Technical Highlights

  • Bypass charging function: Bypass charging function
  • High charging current: High charging current
  • Wide range of AC: input voltage
  • 50/60HZ compatible: 50/60HZ compatible
  • Intelligent adjustment of over-discharge: voltage
  • Comprehensive protection features: Comprehensive protection features

Frequently Asked Questions

What are the main performance specifications of the IVPS/IVPM Series inverter?

The IVPS/IVPM Series inverter has a rated output power of 2500VA and 2000W, with a nominal output voltage of 220Vac. It operates at a nominal frequency of 50±0.3Hz or 60±0.3Hz, and offers a peak efficiency of 90%.

Is the IVPS/IVPM Series inverter compatible with generators?

Yes, the IVPS/IVPM Series inverter is compatible with generators as it accepts a sinusoidal input voltage waveform from utility or generator sources.

What are the physical specifications of the IVPS/IVPM Series inverter?

The IVPS/IVPM Series inverter has package dimensions of 552x408x290mm. Please note that the weight and IP rating are not specified in the provided information.

What are the installation requirements for the IVPS/IVPM Series inverter?

The inverter should be installed in an environment with an operating temperature range of 0°C to 40°C. Ensure proper ventilation and follow all safety guidelines during installation.